5. Electric wiring

DANGER OF BODILY INJURY OR DEATH

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER
SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS.
GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING
 LINE VOLTAGE CONNECTIONS.

(1)  Selection of size of power supply and interconnecting wires.

Precautions for Electric wiring

Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round
type crimped terminal lugs with insulated grip on the ends of the wires.

Use copper conductor only,the parameter of connecting cable is H05RN-F 4G
0.75mm

2

,but for AU182AEEAA,the parameter of connecting cable should 

be

H05RN-F 3G 2.0mm

2

+H05RN-F 1x0.75mm

2

The wiring method should be in line with the local wiring standard.
The breaker of the air conditioner should be all-pole switch; and the distance
between its two contacts should be no less 3 mm.
If the supply cord is damaged, it must be replaced by the manufacturer or its
service agent or a similar qualified person.
If the fuse on PC board is broken please change it with the type of T3.15A/250VAC.

Select wire sizes and circuit protection from table below. (This table shows 20 m
length wires with less than 2% voltage drop.)

WARNING

(2)  Wiring connection

Make wiring to supply power to the outdoor unit, so that the power for the indoor
unit is supplied by

 

terminals.

11

Installation Procedure

Electric wiring

For the detailed wiring connection with the indoor units, see the corresponding indoor

operation and instruction manual.

30

Item

Model

Phase

3

Switch breaker

(A)

Circuit  breaker

Overcurrent protector

rated capacity (A)

Power source

wire size

(minimum)

(mm

2

)

30

20

4.0

1

40

26

2.5

Switch

breaker(A)

Earth leakage breaker

Leak

current(mA)

30

40

AU48NAIEAA
AU60NAIEAA

AU28NAHEAA
AU36NAIEAA

AU182AEEAA

AU282AHEAA
AU362AIEAA

3

30

2.5

30

20

1

40

26

6.0

40

30

30

30

AU242AGEAA

1

40

26

4.0

40

30

Note: the power cable and connecting cable are self-provided.

Summary of Contents for AU182AEEAA

Page 1: ...ad this manual carefully Please keep this manual properly for future use CONTENTS Name of Parts 1 Safety Cautions 2 3 Installation Procedure 4 13 INSTALLATION INSTRUCTIONS No 0010577959 D AU242AGEAA A...

Page 2: ...unit Compressor AU36NAIEAA AU362AIEAA AU48NAIEAA AU60NAIEAA AU242AGEAA AU182AEEAA Air inlet Air outlet Inside of unit Compressor Air inlet Air outlet Inside of unit Compressor Air inlet Air outlet In...

Page 3: ...autions Carefully read the following information in order to operate the airconditioner correctly WARNING If any abnormal phenomena is found e g smell of firing please cut off the power supply immedia...

Page 4: ...tioner Incorrect installation may cause water leak electrical shock and fire hazard Call the dealer to take measures to prevent the refrigerant from leaking If conditioner is installed in a small room...

Page 5: ...b the neighborhood Place where there is not heavy snowfall in the winter time Place where obstacles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a st...

Page 6: ...HEAA Install the unit so that the angle of inclination must be less than 3 degrees Note 1 Give enough room for the concrete foundation to fix by anchor bolts 2 Place the concrete foundation deep enoug...

Page 7: ...ion Procedure AU182AEEAA AU282AHEAA AU28NAHEAA AU242AGEAA 730 630 308 335 Power Wiring Terminal Power Wiring Distribution Hole 860 Power Wiring Terminal Power Wiring Distribution Hole 25 780 640 500 2...

Page 8: ...id pipe Flare connection Indoor unit Flare connection 3 way stop valve Outdoor unit 3 way stop valve Gas pipe Liquid pipe Flare connection Indoor unit Flare connection 2 way stop valve AU362AIEAAAU36N...

Page 9: ...pe hold the pipe centre to centre then screw nut on by hand refer to Fig Be careful not to let foreign matters such as sands enter the pipe 4 Piping connection Forced fastening without centering may d...

Page 10: ...ll in close state In order to prevent the nitrogen entering the circulation system of outdoor unit tighten the valve rod before giving pressure both gas and liquid valve rods Outdoor Completely tighte...

Page 11: ...remove the air inside the system After air tightness test and discharging all the nitrogen connect the vacuum pump as the following figure shown Refrigerant piping 10 When the total length L of the t...

Page 12: ...o contacts should be no less 3 mm If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similar qualified person If the fuse on PC board is broken please chan...

Page 13: ...on the side panel WARNING DO NOT CONNECT THE NEUTRAL WIRE TO OR PHASE INTERCONNECTING WIRES MUST BE WIRED ACCORDING TO FIG 1 FIG 2 FIG 3 INCORRECT WIRING CAUSE EQUIPMENT DAMAGE N R S T Installation Pr...

Page 14: ...abnormal Temperature protection malfunction 0D Power LED flashes 13 times Drainage system malfunction 08 Power LED flashes 10 times 0B Power LED flashes 11 times Alarm of exterior annunciator 7 Troub...

Page 15: ...HAIER GROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266500 P R China Web Site http www haier com...

Reviews: