Service diagnosis 

                                                                                 

3

7

                   Domestic air conditioner 

 

10.3.7 The communication fault between IPM and outdoor PCB   

 

Outdoor display:    LED1 flash  4 times  

 

 

 

Method of       Communication is detected by checking the IPM module and the outdoor PCB 
Malfunction             
Detection 
 
Malfunction           

    The outdoor PCB broken leads to communication fault 

Decision                 

    The IPM module broken leads to communication fault 

Conditions    
     
Supposed                 

    The outdoor PCB is broken   

Causes                     

   The IPM module is broken       

      Communication wiring disconnected 

 
Troubleshooting    * Caution  Be sure to turn off power switch before connect or disconnect connector,   or 
else parts damage may be occurred.   
 

 

 

1) Check whether Terminal CN23 and CN24 on the outdoor mainboard 

CN10 and CN11 on IPM module 

2) Check whether the connected wire between IPM and outdoor 

Are they good? 

Electrify the machine again and turn it

on, Check whether the voltage between

1 and 2 of Terminal CN23 is about DC5V,

Check whether the voltage between2

and 3 of Terminal CN23 is about DC15V,

Replace the outdoor mainboard with a new one 

Replace the outdoor IPM module 

with a new one. 

YES 

NO 

NO 

YES 

Malfunction  unsolved 

1) Pull out and reinsert the terminals.   

2) Replace connected wire 

Summary of Contents for AS09TH3HRA

Page 1: ...l dangers in attempting to service a product Products powered by electricity should be serviced or repaired only by experienced professional technicians Any attempt to service or Repair the product or products dealt with in this service information by anyone else could result in serious injury or death WARNING 2015 Qingdao Haier Air Conditioner General corp Ltd All rights reserved Unauthorized cop...

Page 2: ...troduction 1 2 Features 7 3 Specifications 8 4 Sensors list 9 5 Piping diagrams 10 6 Printed circuit board connector wiring diagram 11 7 Functions and control 8 Dimensional drawings 9 Center of gravity 10 Service Diagnosis 11 Circuit diagrams 14 44 27 26 26 ...

Page 3: ...ion 1 1 Model name explanation A S 0 9 T H 3 H R A Indoor unit Type of indoor unit S wall mounted Nominal cooling capacity 9000BTU h Platform of indoor units T T platform 20TPlatform Version number Indoor units DC inverter Apply toT1 220 240V50HZ 1ph ...

Page 4: ...efore disassembling the equipment for a repair Working on the equipment that is connected to a power supply can cause an electrical shook If it is necessary to supply power to the equipment to conduct the repair or inspecting the circuits do not touch any electrically charged sections of the equipment If the refrigerant gas discharges during the repair work do not touch the discharging refrigerant...

Page 5: ...ing the welder in an enclosed room can cause oxygen deficiency 1 2 2 Cautions Regarding Products after Repair Warning Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair work Never attempt to modify the equipment The use of inappropriate parts or tools can cause an electrical shock excessive heat generation or fire When relocating t...

Page 6: ...generation or fire Do not damage or modify the power cable Damaged or modified power cable can cause an electrical shock or fire Placing heavy items on the power cable and heating or pulling the power cable can damage the cable Do not mix air or gas other than the specified refrigerant R 410A R22 in the refrigerant system If air enters the refrigerating system an excessively high pressure results ...

Page 7: ...operly water can enter the room and wet the furniture and floor 1 2 3 Inspection after Repair Warning Check to make sure that the power cable plug is not dirty or loose then insert the plug into a power outlet all the way If the plug has dust or loose connection it can cause an electrical shock or fire If the power cable and lead wires have scratches or deteriorated be sure to replace them Damaged...

Page 8: ...k Be sure to check the drainage of the indoor unit after the repair Faulty drainage can cause the water to enter the room and wet the furniture and floor 1 2 4 Using Icons Icons are used to attract the attention of the reader to specific information The meaning of each icon is described in the table below 1 2 5 Using Icons List Icon Type of Information Description Note Note A note provides informa...

Page 9: ... comfortable level when you set the sleep mode during night sleep Super match One outdoor unit can match two or more indoor unit DIY auto mode Adjust the last fixed operation mode automatically Turbo mode Quick cooling or heating Auto restart Automatic return to previous operation conditions after sudden power blackout 24 hours timer Use the timer function to set on or off or from on to off or fro...

Page 10: ...d e t a R n o i t p m u s n o C r e w o P 61 3 21 3 W W EER COP 389 h W K n o i t p m u s n o c y g r e n e l a u n n A h m l a v o m e R e r u t s i o M TECHNICAL SPECIFICATIONS m m D W H s n o i s n e m i D Packaged Dimensions m m D W H G K t h g i e W G K t h g i e w s s o r G r o l o C Sound level Sound peessure Hi Mid Lo 1 2 10 387 5 dB A White 2 5 1 0 3 0 8500 3400 10240 2 8 1 2 3 5 9550 410...

Page 11: ... filter Removable Washable Mildew Proof Temperature control Microcomputer Control E H R Y l e d o m r e l l o r t n o c e t o m e R Note the data are based on the conditions shown in the table below h t g n e l g n i p i P g n i t a e h g n i l o o c Indoor 27 DB 19 WB Outdoor 35 DB 24 WB Indoor 20 DB Outdoor 7 DB 6 WB 5m 4 Sensors list type Description Qty 1 r o f d e s u s t I m and pipe sensor ...

Page 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 ...

Page 13: ... L 7 CN17 Connector for power L wire 8 CN7 Connector for display board 9 CON1 CON3 Connector for ions generator 10 CN23 Connector for communicate between the indoor board and the outdoor board 11 CN36 Connector for long range control 12 CN35 Connector for Net Module 13 CON2 Connector for fresh air Note Other designations PCB 1 Indoor Control PCB 1 CN48 Connector for Forced operation ON OFF switch ...

Page 14: ...Printed circuit board connector wiring diagram 12 Domestic air conditioner PCB ...

Page 15: ...LACK BL BLUE W WHITE Y G YELLOW GREEN 80 120 POWER SUPPLY TO OUTDOOR UNIT 1 N C 3 L 2 W B Y G Y G GND CN48 AMBIENT TEMP SENSOR PIPING TEMP SENSOR CN6 CN12 Right stepmotor left stepmotor CN11 R C0N2 BL Fresh air L CN21 N S R W CN18 CN23 WIFI The Ion Generator Fresh air WIFI Room card marked with is optional CN35 M Fan motor CN8 CN9 BL BL Transformer R R CN3 CN36 Central controller CN17 L CN21 N CN1...

Page 16: ...opened the indoor fan will operate at the set speed and the mode signal will be sent to the outdoor system The system will keep the original status if Tr Ts Airflow speed control temperature difference 1 Automatic When Tr Ts 3 high speed When Ts 1 Tr Ts 3 medium speed When Tr Ts 1 low speed When the sensor is off low speed When the airflow speed has no delay from the high to low switching the spee...

Page 17: ...utes before the next switch Manual When the sensor is off or Tr Ts 3 the manual operation can not be made obligatory automatic operation Airgate location control the location for the airgate can be set according to your needs Defrosting function preventing the frosting on the indoor heat exchanger when cooling or dehumidifying When the compressor works continuously for 1 6 minutes adaptable in EEP...

Page 18: ...the outdoor system Residue heat sending The indoor fan will send the residue heat at a low speed for 12 seconds If other conditions are satisfied when the compressor stops the indoor system will operate at a light speed The indoor fan will stop when the coil temperature is below the heat start temp 4 Defrosting When the system receives the defrosting signal from outdoors the indoor fan will stop a...

Page 19: ...n the fan operates 7 1 8 Timing You can set 24 hours on off timing accordingly After the setting the timing indicator will be lightened Also the light will be turning off after the timing is finished The followings are several timing methods 1 system on timing The timing indicator will be lightened and the indoor system is under the waiting mode The light will be turned off when the timing is fini...

Page 20: ...peration the press on the urgency key will stop it Under the system off mode the display screen will show automatic running sign Under the system off mode the system will not receive the remote control signal if the press on the urgency key doesn t last for 15 seconds or if the key is loosened Urgency operation If you press the urgency key for less than 5 seconds the buzzer will ring when you pres...

Page 21: ...control only receives the signals for stop According to the signals the malfunction resume presentation finishes The resume restores after the power supply restores 7 1 15 Abnormality confirmation approaches 1 indoor temperature sensor abnormality Under the operation the normal temperature ranges from 120 degree to 30 degree When the temperature goes beyond this range the abnormality can be confir...

Page 22: ...indoor system should be as the followings Remote control urgency signal operate according to the remote control and the urgent conditions the present status will be stored into the EEPROM of the indoor system Quitting conditions Press dormant button 10 times within 7 seconds and the buzzer will ring twice 7 1 18 Test program First connect the test program terminal on the mainboard Then connect the...

Page 23: ...8 19 99 66 4 19 9 137 87 29 19 09 67 4 04 8 130 096 30 18 23 68 3 9 7 122 799 31 17 42 69 3 76 6 115 946 32 16 65 70 3 63 5 109 51 33 15 97 71 3 5 4 103 462 34 15 22 72 3 38 3 97 779 35 14 56 73 3 26 2 92 437 36 13 93 74 3 15 1 87 415 37 13 34 75 3 04 0 82 691 38 12 77 76 2 94 1 78 248 39 12 23 77 2 84 2 74 067 40 11 71 78 2 74 3 70 133 41 11 22 79 2 65 4 66 43 42 10 76 80 2 56 5 62 943 43 10 31 6...

Page 24: ... 15 70 0342 64 3023 58 9863 1 66 1 54 14 66 3463 61 0123 56 0565 1 64 1 52 13 62 8755 57 9110 53 2905 1 62 1 51 12 59 6076 54 9866 50 6781 1 60 1 49 11 56 5296 52 2278 48 2099 1 58 1 47 10 53 6294 49 6244 45 8771 1 56 1 46 9 50 8956 47 1666 43 6714 1 54 1 44 8 48 3178 44 8454 41 5851 1 51 1 42 7 45 8860 42 6525 39 6112 1 49 1 40 6 43 5912 40 5800 37 7429 1 47 1 39 5 41 4249 38 6207 35 9739 1 45 1 ...

Page 25: ... 9 8975 9 5974 9 2980 0 76 0 76 27 9 5129 9 2132 8 9148 0 80 0 80 28 9 1454 8 8465 8 5496 0 84 0 83 29 8 7942 8 4964 8 2013 0 87 0 86 30 8 4583 8 1621 7 8691 0 91 0 90 31 8 1371 7 8428 7 5522 0 95 0 93 32 7 8299 7 5377 7 2498 0 98 0 97 33 7 5359 7 2461 6 9611 1 02 1 00 34 7 2546 6 9673 6 6854 1 06 1 04 35 6 9852 6 7008 6 4222 1 10 1 07 36 6 7273 6 4459 6 1707 1 13 1 11 37 6 4803 6 2021 5 9304 1 17...

Page 26: ...4 2 38 70 2 0983 1 9393 1 7908 2 59 2 42 71 2 0337 1 8778 1 7324 2 63 2 46 72 1 9714 1 8186 1 6761 2 68 2 50 73 1 9113 1 7614 1 6219 2 73 2 54 74 1 8533 1 7064 1 5697 2 78 2 58 75 1 7974 1 6533 1 5194 2 83 2 63 76 1 7434 1 6021 1 4710 2 88 2 67 77 1 6913 1 5528 1 4243 2 92 2 71 78 1 6409 1 5051 1 3794 2 97 2 75 79 1 5923 1 4592 1 3360 3 02 2 80 80 1 5454 1 4149 1 2942 3 07 2 84 81 1 5000 1 3721 1 ...

Page 27: ...6 0 6303 4 34 3 92 105 0 7641 0 6845 0 6127 4 40 3 97 106 0 7441 0 6661 0 5957 4 46 4 02 107 0 7247 0 6482 0 5792 4 51 4 07 108 0 7059 0 6308 0 5632 4 57 4 12 109 0 6877 0 6140 0 5478 4 63 4 16 110 0 6700 0 5977 0 5328 4 69 4 21 111 0 6528 0 5820 0 5183 4 74 4 26 112 0 6361 0 5667 0 5043 4 80 4 31 113 0 6200 0 5518 0 4907 4 86 4 36 114 0 6043 0 5374 0 4775 4 92 4 41 115 0 5891 0 5235 0 4648 4 98 4...

Page 28: ...Seivice diagnosis Domestic air conditioner 8 Dimensional drawings unit mm 9 Center of gravity unit mm 26 708 ...

Page 29: ...door PCB is broken Operation sometimes stops Check the power supply A power failure of 2 to 10 cycles can stop air conditioner operation Equipment operates but does not cool or does not heat only for heat pump Check for faulty operation of the electronic expansion valve Set the units to cooling operation and compare the temperatures of the liquid side connection pipes of the connection section amo...

Page 30: ... electricity for the outdoor model Page 35 4 Communication fault between the IPM and outdoor PCB Page 37 Power voltage is too high or low Page 38 8 Overheat protection for Discharge temperature Page 39 10 Defrost temperature sensor failure Page 29 1 1 Suction temperature sensor failure Page 29 12 Ambient temperature sensor failure Page 29 13 Discharge temperature sensor failure Page 29 18 deviate ...

Page 31: ...s more than 4 92V or less than 0 08V during compressor n o i t a r e p o n o i s i c e D Conditions Note The values vary slightly in some models Supposed Faulty connector connection Causes Faulty thermistor Faulty PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Thermistor resistance check method Remove the con...

Page 32: ...ta detected by the EEPROM are used to determine MCU Malfunction Detection Malfunction When the data of EEPROM is error or the EEPROM is damaged Decision Conditions Supposed Faulty EEPROM data Causes Faulty EEPROM Faulty PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Replace the indoor or outdoor mainboard ...

Page 33: ...aulty indoor unit PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Check whether terminals on indoor pcb is well Electrify the machine again and turn it on in the cooling operation Measure voltage between the positions 1and 3 of Terminal CN5 on the indoor PCB the voltage is about 90 220vac check whether motor c...

Page 34: ...an run Yes Measure the voltage between 3 and 6 of the terminal about 0 5v Is it normal N0 the motor of the outdoor unit is damaged and needs replacing Measure the voltage between 1 and 3 of the terminal of fan motor on the mainboard about DC310V Measure the voltage between 3 and 4 of the terminal about DC15V Measure the voltage between 5 and 3 of the terminal about 1 6v NO Is it normal The mainboa...

Page 35: ...ng condition and so on Malfunction Detection Malfunction when the data of EEPROM is error or the EEPROM is damaged Decision Conditions Supposed DC fan motor protection dues to the DC fan motor faulty Causes DC fan motor protection dues to faulty PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred ...

Page 36: ... faulty PCB of IPM module Compressor wiring disconnected Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Electrify the machine again and turn it on with the remote controller If malfunctions are reported before or upon the compressor being started up IPM Module is damaged and needs replacing 1 The system may have ...

Page 37: ...r is too high Malfunction Detection Malfunction when the IPM Module is damaged Decision or the compressor is damaged Conditions power supply voltage is too low or too high Supposed Faulty IPM Module Causes Faulty compressor Faulty power supply Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred ...

Page 38: ...ressor being started up IPM Module is damaged and needs replacing Repair the power supply The system may have been over or under charged with gas which can be judged through the pressure of the measuring system YES NO Yes NO The compressor is started normally but malfunctions are reported after it has run for some time Check the power supply is too low or too high NO ...

Page 39: ...ted Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred 1 Check whether Terminal CN23 and CN24 on the outdoor mainboard CN10 and CN11 on IPM module 2 Check whether the connected wire between IPM and outdoor Are they good Electrify the machine again and turn it on Check whether the voltage between 1 and 2 of Terminal C...

Page 40: ...pply voltage not as specified Causes the IPM module is broken the outdoor PCB is broken Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Electrify the machine again and turn it on with the remote controller Check whether the compressor is started normally Is it ok Yes Maybe there is some disturbance NO No 230 is ok...

Page 41: ...red Electrify the machine again and turn it on with the remote controller then measure the temperature at the exhaust temperature sensor of the compressor on the outdoor unit The temperature exceeds 110 shortly after the machine starts up 1 The cryogen may have been leaked during installation or there may be leakage in the piping system 2 There may be other causes to make the exhaust temperature t...

Page 42: ...sconnected Causes The indoor PCB is broken The outdoor PCB is broken The Module PCB is broken Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred NO A Yes NO Yes No YES Restart the a c and it becomes normally If starting up normally but malfunction occurs again after a while Check whether the linking cable between the...

Page 43: ...outdoor unit with a multimeter If 230VAC is available but 310DC not the power module is damaged replace it with a new one Test the outdoor power supply 230VAC and 310VDC with a multimeter The outdoor mainboard is damaged replace it with a new one The indoor mainboard is damaged replace it with a new one If the value varies between 0 and 80 VAC the outdoor mainboard is damaged replace it with a new...

Page 44: ...r Faulty PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Within 3 minutes after the machine is supplied with power and turned on with the remote controller check whether the compressor can start up 1 The wiring of compressor is incorrect or the connection is poor 2 The compressor is damaged At first the compressor ...

Page 45: ... exchanger Faulty heat exchange sensor Insufficient gas Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Electrify the machine again and turn it on with the remote controller check whether the wind temperature is below 65 The malfunction is reported after the machine has run for some time 1 Check room temperature a...

Page 46: ...119 10K 1 42 COM1 1 43 DIG1 1 42 COM1 1 43 DIG1 XT1 CSTLS8M00G56 R508 10K R507 10K 1 23 LSTEP_D 1 22 LSTEP_C 1 21 LSTEP_B 1 13 BUZZ 1 15 RSTEP_A 12V 5V J9 J24 E ON OFF J9 J24 ON ON ON EK 387 317 OFF OFF OFF C4 0 1uF C28 0 01uF C11 0 1uF C12 0 1uF C30 0 1uF C19 0 001uF C39 0 1uF A0 1 A1 2 A2 3 GND 4 SDA 5 SCL 6 WP 7 VCC 8 IC4 CAT24C04 SOIC8 BUZZ1 PKM13EPY 4002 VREF 61 KI0 AN8 P10 49 AN7 P00 50 AN6 ...

Page 47: ...IC7 R3BMF51 1A 600V C1 0 1uF C6 0 1uF 0805 C21 0 1uF C31 0 1uF 0805 C34 0 1uF C35 0 001uF E2 100uF 16V 105 E10 100uF 16V 105 C26 0 01uF C41 0 1uF C44 0 001uF C43 0 001uF 2 36 TX 2 35 RX LED1 220V N 5V 5V R4 330Ω 0805 IC2 TLP421 IC1 TLP371 R1 330K 0805 R12 2K R7 10K R17 2 2K 0805 D1 1N4007 D2 1N4007 R8 6 8K 2W 1 CN23 D250 室内外通讯 C20 0 001uF 0805 C3 0 001uF 0805 C2 0 01uF 0805 φ3 绿色 散光 低亮 1 CN18 D250...

Page 48: ...tic air conditioner Sincere Forever Haier Group Haier Industrial Park No 1 Haier Road 266101 Qingdao China_ Http www haier com Edited by Signed by Approved by Jing Yanqin Yang Xiaodong He shiquan Wu Hongjin ...

Page 49: ... to service a product Products powered by electricity should be serviced or repaired only by experienced professional technicians Any attempt to service or Repair the product or products dealt with in this service information by anyone else could result in serious injury or death WARNING 2016 Qingdao Haier Air Conditioner General corp Ltd All rights reserved Unauthorized copying and distribution i...

Page 50: ...1 DRemove of front panel Indoor unit Step Procedure Points 1 Features 2 Remove the front panel 1 Hold the front panel by the tabs on the both sides and lift it ...

Page 51: ...oosen the screw and lift up the casing cover 2 Lift up the cssing cover Pull the Harness out of the control box and then release the pivots on both sides of the unit to remove the front panel Lift up the casing cover Loosen the screw ...

Page 52: ...he air filters 1 Lift an air filter upwards slightly and then pull it out downwards Remove the horizontal flap 1 Release the side of pivot and then Release the Center of the pivot Bend the horizontal blade slightly and remove it The horizontal flap is Single Remove the casing ...

Page 53: ...4 Step Procedure Points 1 2 Release the screw covers 3EA Loosen the marked Screw 4EA ...

Page 54: ...d hooks 3EA and then Pull the front grille out Horizontally and remove it When assembling install the front grille horizontally so as not to stuff the flap inside When assembling make sure these three hooks are caught properly Holes 3EA HOOK 3EA ...

Page 55: ...control box Step Procedure Points 1 Pull the Harness out of the PCB unit and then Loosen the control Box screws 2EA Pull the control box from of the frame and remove it Harness Stepping motor and fan motor harness Loosen screws 2EA ...

Page 56: ...7 Release stepping motor and control box Step Procedure Points 3 Loosen the stepping motor screws 2EA and then Release the stepping motor ...

Page 57: ... Removal of Heat Exchanger Step Procedure Points 1 2 Loosen the marked screw 1EA Pull mounting plate and heat exchanger bracket out from Hook of the base frame and then release them Loosen the Screw 1EA ...

Page 58: ...9 Step Procedure Points 3 Release the fixture plate from the base frame hook and remove it ...

Page 59: ...10 Step Procedure Points 4 Loosen the marked screws 4EA And then Remove the heat exchanger Remove Fan Motor 1 Loosen the marked screws 4EA and release the cover of fan motor ...

Page 60: ...2 Loosen the marked screw 2EA of fan motor up bracket and remove it Loosen the marked screw 1EA of fan motor and remove fan motor and remove it Screw of Fan Motor up bracket Screw of fan rotor Fan motor bracket UP Fan motor assy ...

Page 61: ...Lift up the right part of the fan and remove it Remove horizontal louver and fan motor bracket 1 Release the marked hooks 4EA and then Pull the guide air plate and remove it Two blades assemble The guide air pltate then remove it ...

Page 62: ...13 Remove fan motor bracket and fan bearing Step Procedure Points 1 2 Pull the hook of fan motor bracket and upward remove it Pull the hook of bearing bracket and upward remove it ...

Page 63: ...14 Remove frame work board Step Procedure Points 1 2 Loosen the marked screw of frame work board Pull the hook of frame work board remove it Screw of frame work board ...

Page 64: ...15 Remove drain pipe and drain pipe stem Step Procedure Points 1 2 Loosen the marked screw of drain pipe and then remove it Pull the drain pipe stem from base frame and the remove it ...