Service diagnosis
3
1
Domestic air conditioner
10.3.3 Indoor fan motor malfunction
Indoor Display
■
E14
Method of The rotation speed detected by the Hall IC during fan motor operation is used to determine
Malfunction abnormal fan motor operation
Detection
Malfunction when the detected rotation feedback signal don’t received in 2 minutes
Decision
Conditions
Supposed
■
Operation halt due to breaking of wire inside the fan motor.
Causes
■
Fan motor overheat protection
■
Operation halt due to breaking of the fan motor lead wires
■
Detection error due to faulty indoor unit PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
Check whether terminals
on indoor pcb is well ?
Electrify the machine again and turn it on in the cooling operation,
Measure voltage between the positions 1and 3 of Terminal CN5
on the indoor PCB
the voltage is about 90-220vac
check whether motor can run
when turn on the unit
the indoor motor is damaged and need replace
Yes
NO
NO
Yes
Measure whether there is voltage pulse (0-5VDC)
between the positions middle wire and black wire
of Terminal CN2 on the indoor PCB
NO
the indoor pcb is damaged and need replace
Pull out the terminals on the indoor
mainboard and reinsert them.
No
Yes
Is it ok?
Yes
Summary of Contents for AS09TH3HRA
Page 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 ...
Page 14: ...Printed circuit board connector wiring diagram 12 Domestic air conditioner PCB ...
Page 53: ...4 Step Procedure Points 1 2 Release the screw covers 3EA Loosen the marked Screw 4EA ...
Page 58: ...9 Step Procedure Points 3 Release the fixture plate from the base frame hook and remove it ...