Electric wiring
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE
COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped
terminal lugs with insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with
less than 2% voltage drop.)
(2) Wiring connection
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by
terminals.
Item
Model
Phase Switch breaker
(A)
Circuit breaker
Overcurrent protector
rated capacity (A)
Power source
wire size
(minimum)
Switch
breaker
Earth leakage breaker
Leak
current
OUTDOOR UNIT TERMINIAL BLOCK
INDOOR UNIT
TERMINIAL BLOCK
1
2
3
1
2
3
L1 L2 L3 N
3
30
20
2.5mm
2
30
30mA
Connecting cable
is self-provided.
Power cable
is self-provided.
380-400V~,50Hz
Power
21
Y/G
INSTALLATION MANUAL FOR INDOOR UNIT