Trouble Shooting

Error display ( For  *

EAA

  series )

For remote type, flash times

1

2

3

4

5

6

8

9

10

11

12

13

15

17

18

19

20

Failure description

Indoor ambient temp. sensor failure

Indoor coil temp. sensor failure

Outdoor ambient temp. sensor failure

Outdoor coil temp. sensor failure/Compressor

dischar

ging temp. sensor abnormal

Over

-current protection / Power supply

abnormal

High/Low pressure abnormal

Communication between wired

controller and indoor abnormal

Communication between indoor and outdoor abnormal

Drainage system abnormal

Outside alarm signal input

Gas pipe temp. sensor abnormal

Temperature protection malfunction

EEPROM abnormal

Compressor overheat

Abnormal mode

Outdoor coil B(suction temp sensor

-for MR

V II)

Outdoor dischar

ging B(oil temp sensor

-for MR

V II)

Reason

Sensor broken down or short circuit for more than 2m continuously

Sensor broken down or short circuit for more than 2m continuously

Sensor broken down or short circuit for more than 2m continuously

Sensor broken down or short circuit for more than 2m continuously

CT

 check abnormal 3 times in 30m / Fault phase, short of phase,

out of balance greatly

High pressure switch acts 3 times in 30m/Low pressure switch acts

in normal running

Communication abnormal for more than 4m continuously

Communication abnormal for more than 4m continuously

Float switch broken down for more than 25m continuously

Outside signal broken down for more than 10s

Sensor broken down or short circuit for more than 2m continuously

Solenoid valve act incorrectly 3 times continuously

EEPROM data missing

The dischar

ging temperature is higher than 120degree

Indoor operation mode is dif

ferent with the running indoor unit.

Sensor broken down or short circuit for more than 2m continuously

Sensor broken down or short circuit for more than 2m continuously

Remarks

Failure code on wired controller

01(01H)

02(02H)

74(4AH)

73(49H)

72(48H)

83(53H)

07(07H)

06(06H)

08(08H)

11(0BH)

03(03H)

13(0DH)

05(05H)

80(50H)

12(0CH)

75(4BH)

77(4DH)

For central control, failure 

code

01D

02D

11

D

12D

10D

14D

06D

05

D

21D

30D

20D

31D

17D

15D

23D

18D

15D

Resumable if lower than 100 degree

 

shows resumable fault, 

 

shows it is not resumable fault.

All manuals and user guides at all-guides.com

Summary of Contents for AD182AMEAA

Page 1: ...AD182AMEAA AD242AMEAA AD282AMEAA AD362AMEAA AD482AMEAA AD242AMERA AD282AMERA AD362AMERA Please read this operation manual before using the air conditioner Please keep this manual carefully and safely...

Page 2: ...enance 9 For Preparation of Heating Hot Keep 10 Is The Unit Installed Correctly 11 Installation Manual For Indoor Unit 12 18 Safety Precautions 3 5 Parts and Functions 6 Cautions 2 Trouble Shooting 19...

Page 3: ...lution method of disposal Disposal of the packaging of your new air conditioner All the packaging materials employed in the package of your new air conditioner may be disposed without any danger to th...

Page 4: ...handing Do not install nearby the place where may have leakage of flammable gas Depending on the place of installation a circuit breaker may be necessary Drain pipe should be arranged to provide a pos...

Page 5: ...inity of such equip ment which generates steam condensed water may drip during cooling operation or it could cause a fault current or short circuit When operating the system simultaneously with a comb...

Page 6: ...F 4G 0 75mm2 All the cables shall have got the European authentication certificate During installation when the connecting cables break off it must be assured that the grouding wire is the last one to...

Page 7: ...Parts and Functions 6 Air outlet Air inlet Duct Air outlet Air inlet Duct For series 182 242 282 362 For series 482 All manuals and user guides at all guides com...

Page 8: ...let Cooling is not sufficient Isn t sun shine invading direct Isn t any unexpected heating load generated Isn t the room much crowded Isn t the swing louver horizontal At HEATING mode If swing louver...

Page 9: ...ng To prevent frost from being accumulated on the indoor unit heat exchanger it is sometimes automatically switched to the FAN mode but it will soon return to the cooling mode Even if the operation sw...

Page 10: ...he air inlet and air outlet of both indoor and outdoor units Make sure that the air filter is not dirty Cut in the power supply switch 12 hours before starting run Post Season Care Operate the unit wi...

Page 11: ...ARMING OPERATION Heat pump type warming Defrosting operation Atmospheric temperature and warming capacity Period of warm up With the heat pump type warming the mechanism of heat pump that concentrate...

Page 12: ...area etc The place where salt breeze blows Seaside etc The place where dense soot smoke exists The place where humidity is extraordina rily high The place where near the machine which radiates the el...

Page 13: ...cient injury can result from a falling of the unit Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes etc Improper installation...

Page 14: ...r a Places where chilled or heated air circulates freely When the installation height exceeds 3m warmed air stays close to the ceiling In such cases suggest your client users to install air circulator...

Page 15: ...Indoor Unit For series 482 For series 182 242 282 362 3 Avoid installation and use at those places listed below a Places exposed to oil splashes or steam e g kitchens and machine plants Installation...

Page 16: ...tention not to apply excess force to the piping on the unit side Also fix the piping at a point as close as possible to the unit For drain pipe use hard PVC general purpose pipe VP 25 I D 1 which can...

Page 17: ...s higher than 500 mm the back flow quantity of drain at the event of interruption of the operation gets too much and it may cause overflow at the drain pan Therefore make the height of the drain pipe...

Page 18: ...duct installation work before finishing the ceiling 8 Connection of suction exhaust ducts a Duct connection position i Fresh air inlet Inlet can be selected from the side or rear faces depending on t...

Page 19: ...ent protector rated capacity A Power source wire size minimum mm2 Switch breaker A Earth leakage breaker Leak current mA Installation Manual For Indoor Unit 1 40 26 6 0 40 For series 282 362 30 30 20...

Page 20: ...circuit for more than 2m continuously CT check abnormal 3 times in 30m Fault phase short of phase out of balance greatly High pressure switch acts 3 times in 30m Low pressure switch acts in normal ru...

Page 21: ...al 3 times in 30m High pressure switch acts 3 times in 30m Fault phase short of phase out of balance greatly Communication abnormal for more than 4m continuously Communication abnormal for more than 4...

Page 22: ...gdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266500 P R China Web Site http www haier com All manuals and user guides at...

Reviews: