Drainage Test
Conduct a drainage test after completion of the electrical work.
During the trial, make sure that drain flows properly through the piping and that
no water leaks from connections.
In case of a new building, conduct the test before it is furnished with the ceiling.
Be sure to conduct this test even when the unit is installed in the heating season.
Procedures
Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.
Check the drain while cooling operation.
(g)
1
2
3
4
1
2
VP 30
Secure the elevation as high as possible
(approx. 100 mm)
A downhill grade of
1/100 or more
When constructing drain piping for several units,
position the common pipe about 100 mm below
the drain outlet of each unit as shown in the sketch.
Use VP-30(11/4") or thicker pipe for this purpose.
(d)
(e) The stiff PVC pipe put indoor side should be heat insulated.
(f) Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain
hose directly into drainage, where the gas with sulfur may be generated.
Backwater bend
Because the drain spout is at the position, which negative pressure may occur. So with the rise of
water level in the drain pan, water leakage may occur. In order to prevent water leakage, we designed a
backwater bend.
The structure of backwater bend should be able to be cleaned. As the below figure shown, use T
type joint. The backwater bend is set near the air conditioner.
As figure shown, set a backwater bend in the middle of drain hose.
H
1
H
2
H1=100mm or the static pressure of air sending motor
H2=1/2H1 (or between 50~100mm)
6. Installation of air suction and discharging duct
A
Insulation
muffler cavity (air sending)
Sacking joint
Air volume adjuster
Air outlet
Enlarging chart of
profile chart A
Vibration resistance hook
Checking meatus
Air conditioner
main unit
Ceiling
Air suction grille with air filter
Please consult the after-sales service worker of Haier Air Conditioner for the choosing and installation
of suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawing
and outer static pressure, and choose the discharging duct with proper length and shape.
Good example
Bad example
Bad example
The length difference among every duct is limited below 2:1.
Reduce the length of duct as possible as can.
Reduce the amount of bend as possible as can.
Use heat insulation material to bind and seal the part connecting main unit and the flare part of air
discharging duct. Perform duct installation work, before the ceiling fit.
>a__WcU[S^ <[c >a`V[e[a`Wc
-161-
Summary of Contents for AB092ACBHA
Page 47: ... a__WcU S c a V e a Wc AU88NATBEA 66 33 1 23 4 43 33 61 2 3 160 2 15 3 52 47 ...
Page 235: ... N2 4 C N344 C J eab d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 235 ...
Page 236: ... a__WcU S c a V e a Wc N2 4 C N344 C J Taeea_ d VW bc eWV V SYcS_ 236 ...
Page 238: ... N364 A D N3 4 A E J eab d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 238 ...
Page 239: ... N364 A D N3 4 A E J Taeea_ d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 239 ...
Page 241: ... N464 C D J eab d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 241 ...
Page 242: ... N464 C D J Taeea_ d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 242 ...
Page 244: ... N364 A N3 4 A J eab d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 244 ...
Page 245: ... N364 A N3 4 A J Taeea_ d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 245 ...
Page 247: ... a__WcU S c a V e a Wc AU242AHBEA AU282AHBEA PCB top side printed diagram 247 ...
Page 248: ... a__WcU S c a V e a Wc AU242AHBEA AU282AHBEA PCB bottom side printed diagram 248 ...
Page 250: ... a__WcU S c a V e a Wc AU28NAHBEA AU36NAIBEA AU42NAIBEA PCB top side printed diagram 250 ...
Page 251: ... a__WcU S c a V e a Wc AU28NAHBEA AU36NAIBEA AU42NAIBEA PCB bottom side printed diagram 251 ...
Page 253: ... a__WcU S c a V e a Wc AU52NAIBEA PCB top side printed diagram 253 ...
Page 254: ... a__WcU S c a V e a Wc AU52NAIBEA PCB bottom side printed diagram 254 ...
Page 256: ... a__WcU S c a V e a Wc AU88NATBEA PCB top side printed diagram 256 ...
Page 257: ... a__WcU S c a V e a Wc AU88NATBEA PCB bottom side printed diagram 257 ...
Page 272: ... a__WcU S c a V e a Wc Indoor units except for AP18 AP88 PCB printed diagram 272 ...
Page 278: ... a__WcU S c a V e a Wc Cabinet indoor units PCB circuit diagram 278 ...
Page 279: ... a__WcU S c a V e a Wc Cabinet indoor units PCB printed diagram 279 ...
Page 343: ... a__WcU S c a V e a Wc 14 Air volume and external static pressure curves 343 ...
Page 364: ...MEMO Commercial Air Conditioner ...