After oil return in cooling mode, the quit condition of refrigerant eliminated:
1 minute later after oil return is over
&
Td Tc
‐
>
30
℃
OR
OR
Ts Tc2AVE
‐
>
30
℃
Tc2AVE
<
35
‐
℃
Max. 10 minutes
Oil return procedure in heating mode:
Quit condition of oil return:
Max. 9 minutes (E)
OR
OR
Td Tc
‐
<
20
℃
for 30s continuously(5 minutes later, begin
to count)
&
Ts Tc2AVE
‐
<
15
℃
for 30s continuously(5 minutes later,
begin to count)
Running for min. 5 minutes(E)
Send oil return signal
oil return begins
oil return over
Inverter compressor
indicated FQCY
60s
oil return FQCY
60s
soft startup
0HZ 0HZ
5s
Outdoor motor AUTO AUTO
AUTO (TC control)
4-way valve ON
OFF
15s
450pulse 450pulse
350pulse(E)
All expansion valves
auto angle
auto angle
All indoors ON
OFF
anti-freezed startup
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-86-