background image

02

T +61 1300 850 253   F +61 1300 424 372   [email protected]   hager.com - 12.2021

„

Press rotary knob again for approx. 3 s or more 

until the load fl ashes once.

„

Release the rotary knob.

„

Select the additional program function required 

by pressing the rotary knob slowly, waiting for 

the load to fl ash after each press (selected from 

Table 3)  before pressing again.
After approx. 10 s without operation, the change 

of additional function is stored and the device 

switches to standard operation.

Confi gurable

additional 

functions

Factory 

setting

Number of times 

the rotary knob is 

pressed

Kick-start

OFF

1 x

Reduced 

maximum

brightness

OFF

2 x

Recovery of the 

load state when 

the power is 

restored

OFF

4 x

Table 3: Confi gurable additional functions

Reset to factory setting

„

Switch off  load.

„

Press and hold rotary knob for approx 10 

seconds.

The load will fl ash once after 3 seconds and 

then fl ash a second time after 10 seconds.

„

Release the rotary knob.

The device is in fi ne adjustment mode for the 

minimum brightness level and the lamp is 

switched on at the minimum brightness level.

„

Press and hold rotary knob again for approx 10 

seconds.

The load will fl ash once after 3 seconds and 

then fl ash a second time after 10 seconds.

„

Release the rotary knob.
The reset has been completed, the load is 

switched off  and the dimmer is in standard op-

eration with the factory settings being eff ective.

Information for electricians
Installation and electrical connection

DANGER!
Electrical shock when live parts are 

touched!
An electric shock can lead to death!
Isolate all power before working on 

the device and cover any live parts in 

the area!

ç

Connection diagram

A

N

Active / L

Load /

Remote

WBMDUR

Remote cable.
Not required for

1 way switched

dimming.

Fig. 5: 1 way connection

WBMSLL

A

N

Active / L

Load /

Remote

to additional 

Slaves

WBMSLL

Active

/L

Neutral

Remote

WBMDUR

Fig. 6: 2 way connection

 Load side of device is not considered isolated in 

OFF position.

 Install a circuit breaker of max. 10 A as device 

protection.

 For 2 way or multiple way switching. Refer to 

WBMSLL instructions.

Appendix

Technical data

Operating voltage

230 V~ +/-10%

Frequency

50 Hz

Miniature circuit breakers

max. 10 A

Degree of protection

IP2X

Standby power consumption

< 0.07 W

230 V incandescent lamps, 

halogen lamps and cold-light 

refl ector lamps

7 … 300 W

Dimmable, electronic 

transformers with low voltage 

halogen lamps

20 … 350 W

Dimmable 230 V LED lamps

3 ... 250 W

Slave units cable length

Load and slave unit cable

- in one cable

- in separate cables

 max. 20 m

max. 50 m

Terminal block cables

max. 2 x 1.5 mm²
max. 1 x 2.5 mm²

Flying leads, fl exible

100 mm x 1,5 mm²

Operating temperature

-5 to 50 °C

Storage temperature

-20 to 70 °C

Relative humidity (without 

dewing)

0 … 65 %

Operating conditions

Load type

Maximum output 

power (W)

25 °C

35

50 °C

Ohmic loads

300

265

210

Dimmable, electronic 

transformers with low 

voltage halogen lamps

350

310

250

230 V LED lamps

250

220

175

Table 4: Reduced performance, ambient temperature

When operating dimmers in combination with oth-

ers beneath a cover plate, the maximum connect-

ed load must be reduced depending on the number 

of dimmers.

Number of dimmers per 

combination

Connect load reduction

1

100%

2

75%

3

55%

4

40%

5

35%

6

30%

Table 5: Dimmer combination load reduction

 Carry out loading of conventional, electronic 

transformers according to manufacturer's 

instructions.

 Do not use non-dimmable 230 V LED lamps.
 If 230 V LED lamps are used, the power supply 

to the dimmer can cause the lamp to glow 

slightly even when it is switched off .

Troubleshooting

Dimmer switches off  of its own accord.

The electronic overload protection has tripped.

Check the load connected (excessive load).
Reduce the number of lamps or use lamps with 

a lower power rating.

The electronic short-circuit protection has tripped.

Check electrical installation.

The load cannot be dimmed down suffi  ciently.

The dimming angle is set too high.

Decrease the value in fi ne-setting of the mini-

mum brightness.

The load switches off  while being dimmed 

down.

The dimming angle is set too low.

Increase the value in fi ne-setting of the mini-

mum brightness.

The load does not switch on.

The dimming angle and brightness value are set 

too low.

Increase the value in fi ne-setting of the mini-

mum brightness.

Load fl ickers while switched off .

LED load too low.

Increase LED load at output.

The connected load cannot be dimmed or load 

fl ickers while switched ON.

Lamps are not suitable for dimming.

Be sure always to use dimmable loads.

Undefi ned fault during operation.

Slave unit cable length is too long or no separate 

slave unit cable has been used.

Keep to slave unit cable length or, if necessary, 

use separate slave unit cable.

Note:

LED loads should be tested with this dimmer 

prior to installation. Some LED loads may not be 

compatible due to the type of LED driver within the 

LED light.

End of life treatment of electrical/

electronic equipment and batteries 

in the European Union countries. 

The crossed-out ‘wheeled bin symbol’ marked on 

the equipment or its packaging, indicates that this 

product is not to be disposed off with unsorted 

municipal / household waste. Please check with 

your local authority or retailer for recycling and 

collection advice. This will enable you to contribute 

to the disposal, treatment and recycling in an 

environmentally sound way and help to prevent 

potential negative effects on the environment and 

human health.