Installation, handling and maintenance
76
Technical changes reserved
7.3.5
Cable feeds
-
The installation of feeder units requires the busbar trunking run to be free of
applied voltage (disconnected and secured from being switched on again).
Cable end feeder
The cable end feeder is supplied complete with joint block.
Assembly is carried out according to the principle of assembly of connection
joints.
Cable intermediate feeder
The cable intermediate feeder can only be installed at the connection joint
between two adjacent straight busbar elements.
The cable intermediate feeder is supplied complete with joint block.
The supplied joint block (with special clamping block) replaces the standard joint
block that may be present. The standard joint block between the adjacent
straight busbar elements is exchanged.