6LE007318A
7
4.3.
LED Functioning modes
LED indicator
(cf image)
LED blinking
LED ON**
LED OFF*
1
Source 1 availability
Source 1 present but not available for
following possible reason:
- Source under voltage / under
frequency
- Source overvoltage / over frequency
- Phase rotation order of source 1 & 2
are different
Source is available
Source is not available
2
Position I indicator
-
RTSE is in position I / Load is
connected to source 1
RTSE is not in position 1 / Load is not
connected to source 1
3
Position 0 indicator
-
RTSE is in position 0 / Load is not
connected to source 1 or source 2
RTSE is in position 0 / Load is not
connected to either source 1 or source
2
4
Load supplied indicator
-
Load is being supplied by a source
which is available
Load is not being supplied by a source
which is available
5
Position II indicator
-
RTSE is in position II / Load is
connected to source 1
RTSE is not in position II / Load is not
connected to source 1
6
Source 2 availability
Source 2 present but not available for
following possible reason:
- Source under voltage / under
frequency
- Source overvoltage / over frequency
- Phase rotation order of source 1 & 2
are different
Source is available
Source is not available
7
AUTO/MANUAL indicator
A timer is counting down and a transfer
will be initiated.
(If fault is blinking with buzzer AUTO/
MANU will be blinking)
The controller is in automatic mode
Controller is not in automatic mode
possible modes:
- Manual
- Inhibited
- Fault detected
8
TEST led
-
Test is ongoing
No test ongoing
A
Power
-
Controller is powered up
Controller is OFF
Z
Fault indicator
Fast blinking (3Hz)
: one or more Dip
switch has changed and configuration
has not been saved.
Long blinking (2Hz):
Inhibit input is
active or fault is active
-
Inhibit is not active / no faults active
and dip switch configuration has been
saved.
E
Fire LED
-
Fire input is activated
-
R
Communication (only for
HZI825)
Controller is sending / receiving
information
Communication parameters have been
modified (Baud rate / Parity / Address)
No communications orders are
currently being sent or received
* Considering that the controller is powered.
** Considering that lamp TEST has not been initiated.