6LE007318A
6
4. General overview
4.1.
Product identification
1
Source 1 availability information (Green fixed when source 1 is
present and available and within threshold limits, green blinking
when source 1 is present but outside of threshold limits, off when
under 50 VAC).
2
Switch 1 LED position indication (Green fixed when in position 1).
3
Zero position LED indication (Yellow when in position 0).
4
Load supplied information (Green fixed when load is supplied by an
available source).
5
Switch 2 LED position indications (Green fixed when in position 2).
6
Source 2 availability information (Green fixed when source 2 is
present and available and within threshold limits, green blinking
when source 2 is present but outside of threshold limits, off when
under 50 VAC).
7
Auto LED indication (Green fixed when in automatic, blinking when
transfer is ongoing, off when in manual mode).
8
Test LED (Yellow fixed when test on load is ongoing).
9
Configurations dip switches (see settings).
A
Run LED (Green when product is powered).
Z
Fault LED (Red blinking – long blink when fault or inhibit is activated
(63 A - 64 A open), short blink when a dip switch parameter has been
changed and needs validation).
E
Fire (Red when fire input is activated).
R
COM LED (yellow blinking when RS communications is ongoing)
(for HZI825 only).
T
Change AUTO/MANU pushbutton, press at least 3 seconds to
switch from AUTO to MANU or MANU to AUTO.
Y
Remote order to switch positions, controller must be in MANU
mode for the buttons to be active.
U
Test button with two functions lamp test and TEST ON LOAD. To
start a lamp test short press on the test button (<3s), press again
(<3s) to end test. To start a TEST ON LOAD, long press on the test
button (>3s), when LED (8) is blinking press the “0” button. To end
the TEST on load long press on the test button (>3s).
1
Auto/Manual selector
2
Controller state LED
3
Remote position order selector
4
ATSE Synoptic
5
Test function selector
6
DIP switch programing
4.2.
Controller HMI