36
6LE007596Ad
Positions of the drawout circuit breaker in the chassis
8.3 Changing from disconnected position to test position
Action
Illustration
4
Press the padlocking and
position acknowledgement
tab.
5
Turn the racking handle
clockwise...
... until the status indicator
is displayed:
TEST
and the padlocking and
position acknowledgement
tab comes out of its
housing.
Clac !