For your safety
Technical changes reserved
5
2
For your safety
- Avoid dangers. Adherence to the safety information in this section is a prerequisite for the safe
assembly and use of the field distributor.
- Also observe the safety information provided in other sections.
2.1 Proper use
The Hager New VegaD enclosure is a product offering for flush-mounted and surface installations,
protected to IP30/40/41, for residential and commercial buildings with a maximum supply current of 160 A.
New VegaD flush enclosures are installed at a depth of 110 mm in the wall. They are available in 6 different
heights and 2 different depths.
New VegaD surface enclosures are installed at a depth of 193 mm on the wall. They are available in
6 different heights.
The New VegaD enclosures have been equipped with components from the New VegaD internal fitting system.
Hager’s tried and tested New VegaD enclosures and the New VegaD internal fitting system enable the
implementation of switchgear and controlgear assemblies according to EN 61439 Part 3 (Distribution
boards intended to be operated by ordinary persons / DBO).
Fixed indoor installation/wall mounting
With its enclosed design, the New VegaD enclosures
are intended for stationary, indoor, surface- and
flush-mounting in walls/hollow walls. The operating
conditions for the indoor installation according to
EN 61439 and the maximum ambient temperatures
must be observed at the place of installation.
The New VegaD enclosures meet protection types IP30/IP40/IP41 when equipped with internal system
and/or closed or slotted doors. The instructions in this manual regarding compliance with the protection
type must be observed during installation works.
The New VegaD enclosures are available in protection class II (double insulated). The instructions in this
manual regarding compliance with the protection type must be observed during installation works.
For more detailed information, refer to the technical data.
Intended use also includes:
- Reading and observing this manual, the installation manuals and the manuals for the internal
fitting system
- Complying with the requirements for authorised personnel.
Misuse
Any other or additional use as well as changes and modifications to the field distributor enclosure are
considered to be misuse. Hager does not assume any liability for damages resulting from misuse.
Limitation of operating areas
There are certain areas in which the New VegaD enclosure may not be used, in order to prevent hazards
or damage to the enclosure.
Summary of Contents for FD22ACN
Page 1: ...Technical Manual New VegaD for surface mounting flush mounting Accessories...
Page 42: ...Accessories 42 Technical changes reserved...
Page 47: ...Accessories Technical changes reserved 47 See mounting instruction below...
Page 48: ...Accessories 48 Technical changes reserved...
Page 52: ...Accessories 52 Technical changes reserved...