System-disconnection relay EU400 NA-protection
10
Subject to technical changes
Menu
Parameter / Unit
Default settings
Medium voltage
VDE-AR-N 4110:2018-11
High Voltage
VDE-AR-N 4120:2018-11
Users Data
3 AC
+N
57,7V
3 AC
100V
3/2/1AC+
N
230V
3 AC
400V
Pr11
Pr12
Pr13
Pr14
F_
81.S1
81<S1
F_
Alarm on/off
oFF
oFF
on
on
F_
Underfrequenc
y
Hz
47.50
47.50
47.50
47.50
H_
Hysteresis
Hz
2.40
4
2.40
4
2.40
4
2.40
4
dAL
Response time
s
0.40
0.40
0.10
0.10
doF
OFF-delay
s
60
60
60
60
F_ _
81.S2
81<S2
F_ _
Alarm on/off
oFF
oFF
oFF
oFF
F_ _
Underfrequency
Hz
47.50
47.50
47.50
47.50
H_ _
Hysteresis
Hz
2.40
4
2.40
4
2.40
4
2.40
4
dAL
Response time
s
0.10
0.10
0.10
0.10
doF
OFF-delay
s
60
60
60
60
UFon
UFon
Switching
conditions
oFF
oFF
on
on
UonF
UonF
on/off
oFF
oFF
oFF
oFF
UonF
voltage
V
20.0
20.0
46.0
46.0
uSr
78
uSr
Alarm on/off
StbY
StbY
StbY
StbY
uSr
Vector shift
°
10.0
10.0
10.0
10.0
doF
OFF-delay
s
3
3
3
3
dEon
Suppression time s
3
3
3
3
uSr
Number of phases
3ph
3ph
3ph
3ph
rocf
81r
rocf
Alarm on/off
oFF
oFF
oFF
oFF
dfdt
delta f / delta t
Hz/s
2.000
2.000
2.000
2.000
Per
periods
20
20
20
20
dAL
Response time
s
0.10
0.10
0.10
0.10
doF
OFF-delay
s
60
60
60
60
U-0
59v0
U-0
Alarm on/off
oFF
oFF
oFF
oFF
U-0
Zero voltage
V
46.0
80.0
46.0
80.0
H-0
Hysteresis
V
10.0
10.0
10.0
10.0
dAL
Response time
s
1.50
1.50
1.50
1.50
doF
OFF-delay
s
60
60
60
60
rEL
trEL
Response time Yx s
oFF
oFF
oFF
oFF
doFA
Mode
ind
ind
ind
ind
doFA
Off-delay all
s
0
0
0
0
ddi
ddi
Display delay
s
0.5
0.5
0.5
0.5
dit
Display duration
SCn
s
3.5
3.5
3.5
3.5
Si
U
Voltage
V
57.7
100
230
400
F
Frequency
Hz
50.00
50.00
50.00
50.00
uSr
Vector shift
°
0.0
0.0
0.0
0.0
CodE
pin
Pincode
504
504
504
504
Code
on / off
oFF
oFF
oFF
oFF
Info
Fnr
Firmware version
0-16
0-16
0-16
0-16
Snr
Serial number
xxxx
xxxx
xxxx
xxxx
h
Operating hours
h
xxxx
xxxx
xxxx
xxxx
Err
Error counter
xxx
xxx
xxx
xxx
Pr
Program
11
12
13
14
4