2941/2942 Magnetic Lock
Installation Instructions
I-EA00053
Rev 5, Rev Date: 11/15/22
Always visit www.hagerco.com for the latest Installation Instructions
HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104
• (800) 325
-
9995
Installation
1. Fold template as indicated on dotted line. For single doors locate template against the door and header on the lock jamb
side of the frame.
2. Mark and drill holes as indicated by the template.
3. Mount the armature plate to the door using 1 rubber washer sandwiched between 2 steel washers as shown below.
4. Install mounting plate to header. Loosely fasten screws going through adjustment slot. Assure that the mounting plate
and armature line up properly, then tighten down ALL mounting screws.
5. Secure socket head screws provided inside the housing at each end. Start screws into threads carefully to avoid stripping
the threads. Check alignment and tighten screws. Pull wires through frame, mounting plate and magnet housing
CAUTION: The magnetic lock body must be held in place until secured with mounting screws.
6. Select jumper position for 12VDC or 24VDC. Connect power to magnetic lock.
REINFORCEMENT
TUBE
1
-
3/4“
HOLLOW
METAL DOOR
5/8“
DRILL
STEEL WASHER 2X
RUBBER WASHER
ARMATURE
1/2”
DRILL
SEXNUT
REINFORCEMENT
TUBE
1
-
3/4“
HOLLOW
METAL DOOR
5/8“
DRILL
STEEL WASHER 2X
RUBBER WASHER
ARMATURE
1/2”
DRILL
SEXNUT
7. Test operation. When all is operating properly. Install anti-tamper plugs over socket head
screws using a soft hammer to avoid damage to the housing.
COM
NC
NO
Door Position Sensor (Reed switch)
RED (open with door closed)
GREEN (closed with door closed)
BLACK COM
NC
NO
Door Position Sensor (Reed switch)
RED (open with door closed)
GREEN (closed with door closed)
BLACK
Power
Supply
Lock
Status
Switch
Voltage Jumper
12VDC
24VDC
12VDC
24VDC
A RED LED INDICATES ENERGIZED &
UNSECURED (GREEN=ENERGIZED &
SECURE)
LED
2942
2941
Voltage Jumper
Power
Supply
Lock
Status
Switch
LED
Performance Level
Destructive: Level 1
Line Security: Level 1
Endurance: Level 2
Standby Power: Level 1
•
Installation & wiring in compliance with ANSI/NFPA70 requirements
•
Wiring must be cased to avoid outer cable damage
•
Terminal: 12~22AWG