2941/2942 Magnetic Lock

Installation Instructions

I-EA00053

Rev 5, Rev Date: 11/15/22

Always visit www.hagerco.com for the latest Installation Instructions

HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 

• (800) 325

-

9995

Installation

1. Fold template as indicated on dotted line.  For single doors locate template against the door and header on the lock jamb 

side of the frame.

2. Mark and drill holes as indicated by the template.

3. Mount the armature plate to the door using 1 rubber washer sandwiched between 2 steel washers as shown below.

4. Install mounting plate to header. Loosely fasten screws going through adjustment slot.  Assure that the mounting plate 

and armature line up properly, then tighten down ALL mounting screws.

5. Secure socket head screws provided inside the housing at each end.  Start screws into threads carefully to avoid stripping 

the threads.  Check alignment and tighten screws.  Pull wires through frame, mounting plate and magnet housing

CAUTION:   The magnetic lock body must be held in place until secured with mounting screws.

  

6. Select jumper position for 12VDC or 24VDC. Connect power to magnetic lock.

REINFORCEMENT

TUBE

1

-

3/4“ 

HOLLOW

METAL DOOR

5/8“ 

DRILL

STEEL WASHER 2X

RUBBER WASHER

ARMATURE

1/2” 

DRILL

SEXNUT

REINFORCEMENT

TUBE

1

-

3/4“ 

HOLLOW

METAL DOOR

5/8“ 

DRILL

STEEL WASHER 2X

RUBBER WASHER

ARMATURE

1/2” 

DRILL

SEXNUT

7. Test operation.  When all is operating properly. Install anti-tamper plugs over socket head 

screws using a soft hammer to avoid damage to the housing.

COM

NC

NO

Door Position Sensor (Reed switch)

RED (open with door closed)

GREEN (closed with door closed)

BLACK COM

NC

NO

Door Position Sensor (Reed switch)

RED (open with door closed)

GREEN (closed with door closed)

BLACK

Power 

Supply

Lock 

Status 

Switch

Voltage Jumper

12VDC

24VDC

12VDC

24VDC

A RED LED INDICATES ENERGIZED & 

UNSECURED (GREEN=ENERGIZED & 

SECURE)

LED

2942

2941

Voltage Jumper

Power 

Supply

Lock 

Status 

Switch

LED

Performance Level

Destructive: Level 1

Line Security: Level 1

Endurance: Level 2

Standby Power: Level 1

• 

Installation & wiring in compliance with ANSI/NFPA70 requirements

• 

Wiring must be cased to avoid outer cable damage

• 

Terminal: 12~22AWG