Haes ESENTO ESEN-8MAR Installation, Commissioning & Operating  Manual Download Page 34

Esento Marine 8-12 Installation, Commissioning & Operating Manual

Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0

32

SETUP & PROGRAMMING

DEPENDENCY MODES (FALSE ALARM MANAGEMENT)

Dependency modes are features described in EN54-2 for the processing of confirmation alarms. It is a 
requirement by some monitoring stations and local fire authoities in order to reduce the possibility of false 

alarms.

The panel has 3 dependency mode options, A, B & C. Only one type can be applied to the panel but any 

or all zones can be independently set for dependency mode.

Dependency mode, if assigned to a zone, is set to type A by default.

Dependency ‘A’ will apply the following sequence:

1. 

The first detector alarm is inhibited.

2. 

The panel resets and re-checks the inhibited zone within 15-30 seconds.

3. 

If an alarm is detected then the panel activates a full fire condition.

4. 

If no alarm is detected, the panel stays in an alert condition for 30 minutes. Any new alarm from 
the same zone within this time activates a full fire condition.

5. 

After 30 minutes or if RESET, the panel reverts to step 1.

Note:

 220Ω ‘Evacuate’ call points should be used on such zones to provide an instant un-delayed alarm.  

A 470Ω call point will be included in the dependency delay sequence.

Dependency ‘B’ will apply the following sequence:

1. 

The first detector alarm will indicate at the control panel but not activate the sounders.

2. 

The panel resets and re-checks the inhibited zone within 1 - 4 minutes (programmable, see code 
2-1-3-4) 

1

.

3. 

If an alarm is detected then the panel activates a full fire condition.

4. 

If no alarm is detected, the panel stays in an alert condition for 5 - 30 minutes (programmable, 
see code 2-1-3-4) 

2

. Any new alarm from the same or a different zone within this time activates a 

full fire condition.

5. 

After the time set above or if RESET, the panel reverts to step 1.

Note:

 220Ω ‘Evacuate’ call points should be used on such zones to provide an instant un-delayed alarm.  

A 470Ω call point will be included in the dependency delay sequence.

Dependency ‘C’ will apply the following sequence:

1. 

The first detector or 470Ω call point alarm will indicate at the control panel but not activate the 

sounders.

2. 

The panel will not activate a full fire condition unless a second detector or 470Ω call point is 

activated in the same or any other zone.

Note:

 A 220Ω ‘Evacuate’ call point can be used on such zones to provide an instant un-delayed alarm.

Summary of Contents for ESENTO ESEN-8MAR

Page 1: ...Installation Commissioning Operating Manual MARINE APPROVED 8 12 ZONE CONVENTIONAL CONTROL PANEL Approved Document UI ESEN12MAR 01 Issue 8 0 MED Ref 0832 15...

Page 2: ...ted by the manufacturer or distributors of this fire alarm panel for any misinterpretation of an instruction or guidance note or for the compliance of the system as a whole The manufacturer s policy i...

Page 3: ...UIT SCHEMATIC 11 INSTALLATION 12 SAFETY 12 ESD PRECAUTIONS 13 GENERAL 13 MOUNTING THE CABINET 13 MAINS CONNECTIONS 14 CONNECTING THE BATTERIES 15 SETUP PROGRAMMING 16 NETWORK PANELS SETUP 16 LEVEL 3 E...

Page 4: ...button keypad is used to control the system and allow access to the function options The three main buttons RESOUND red SILENCE blue and RESET green being much larger and colour coded to assist the e...

Page 5: ...Esento Marine 8 12 Installation Commissioning Operating Manual Approved Document Ref UI ESEN12MAR 01 Issue 8 0 3 ABOUT THIS PANEL CABINET 60mm 85mm 310mm 455mm 300mm 450mm Fire Detection System...

Page 6: ...CIRCUIT BOARDS Esento Marine 8 12 panels comprise of two main circuit boards plus optional ancillary boards PSU 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP SNDR1 SNDR2 ZONE1 ZONE2 ZON...

Page 7: ...3 4 5 6 1 2 3 4 ON ADDRESS ZONE A ZONE B ZONE C ZONE D 1 2 3 4 ON D C B A TWIN OPA OPB AUX SNDR A SNDR B C NO TPCA04 S Std spec 4 zone extension card TPCA05 Comms PCB TPCA04 H High spec 4 zone extensi...

Page 8: ...sed Max 3A 30vdc Commmon fault VFCO relay maintained fail safe unfused Max 3A 30vdc Programmable O P Programmable O P Alert pulses sounders Precint class change activates sounders Switched ve inputs S...

Page 9: ...A SNDR B C NO Conventionalfire zone circuits fused 500mA Relay Coil Relay Coil Programmable O P Programmable O P Programmable relay O P unfused Max 3A 30vdc 28v 28v Switched ve outputs Max load 40mA...

Page 10: ...Monitoring current limit 28mA fused 500mA Typical max load 22 devices 18mA each per circuit Ensure 2 4A is not exceeded Zone 1 4 Conventionally wired fire alarm zone circuits 4K7 Ohm 5 0 25W EOL resi...

Page 11: ...imum load shared between outputs 2 4A Power supply output voltage 21 27 29 68vdc Tolerance 0 1 Max continuous load ImaxA Max continuous load whilst battery charging is not required ImaxB ImaxA 610mA I...

Page 12: ...Esento Marine 8 12 Installation Commissioning Operating Manual Approved Document Ref UI ESEN12MAR 01 Issue 8 0 10 DESIGN CONSIDERATIONS GENERAL DETECTION CIRCUIT SCHEMATIC...

Page 13: ...ved Document Ref UI ESEN12MAR 01 Issue 8 0 11 DESIGN CONSIDERATIONS GENERAL SOUNDER CIRCUIT SCHEMATIC 4K7 OHM END OF LINE RESISTOR SNDR1 MOTORISED BELL POLARISED MOTORISED BELL POLARISED ELECTRONIC SO...

Page 14: ...to take such steps as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned with its use This equipment is designed to be operated f...

Page 15: ...ds used in the system must be suppressed to avoid damage to the control equipment The panel is only suitable for mounting in dry control rooms or dry accomodation spaces The site chosen for the locati...

Page 16: ...outs provided A suitable cable gland must be used to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using a suitable rin...

Page 17: ...voltage will appear on the output leads or terminals due to intelligent battery controls b Check the power supply voltage at the 28v 0v supply output terminals With the batteries disconnected the vol...

Page 18: ...n the top of the Comms PCB to re connect the display board ribbon cable Each panel to be included in the network is defined by setting switch 5 on the 6 way DIL switch located on the main circuit boar...

Page 19: ...loop configuration from comms A to B and back to the Master panel again see drawing below This enables the network to still function if there is a break in the cables If replacing an older system wher...

Page 20: ...signify that Level 3 access is active Programming throughout the panel is carried out in a sequence where the fire LEDs indicate the options to set and the fault LEDs indicate the status of these set...

Page 21: ...one to silent mode provides visual audible indication at the panel but no sounder operation Turn off priority alarm feature for zone Turn off detector removal monitoring for zone Set detector removal...

Page 22: ...ults If a sounder circuit fault is displayed pressing and holding the ENTER button will reveal which sounder circuit was at fault This is indicated by the fire LEDs 1 6 as per the table below Repeater...

Page 23: ...3 seconds Any disabled zone sounder circuit output or delay will now be enabled The panel will bleep to acknowledge the reset When finished enter the next programming code or disable the controls and...

Page 24: ...larm 3 for changing muster alarm priority or 4 for Muster Alarm Synchronisation LED 1 LED 2 LED 3 LED 4 LED 5 Select muster alarm zones Set RESOUND button Set muster alarm priority OFF Muster synch mo...

Page 25: ...and exit programming mode Then enter next programming code or return DIL switch 6 to OFF position and disable controls 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP 28V 0V C NC NO C NC N...

Page 26: ...ls on system 11 Inhibit fire fault buzzer on network slave panel The keypad can be used to activate the panel controls instead of using the key switch The default code is 1 2 3 4 however this can be c...

Page 27: ...ton 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2 1 2 3 The panel delay time for all outputs is set here To actually apply the delay to the desired outputs see pro...

Page 28: ...rogramming mode 2 1 2 3 The control panel monitors all internal PCBs for correct function If adding or removing any of the additional extension zone cards the panel must be programmed for the new conf...

Page 29: ...fire LED will pulse to indicate edit mode Now use button 2 to change the setting indicated by the amber fault LED ON or OFF as per above When finished press the ENTER button again and the zone 6 fire...

Page 30: ...1 fault LED Beeps are now silenced When finished press the ENTER button again and the zone 7 fire LED will return to steady view mode Press button 1 to move to next option or hold button 1 for 3 seco...

Page 31: ...to add or remove all 7 addresses in one go When finished press the ENTER button again and the zone 10 fire LED will return to steady view mode Press button 1 to move to next option or hold button 1 fo...

Page 32: ...safe operation This option changes the zone alarm and short circuit thresholds to allow for an MTL 5561 type intrinsically safe barrier to be used in the circuit Silent mode This setting provides a vi...

Page 33: ...press the ENTER button to enter editing mode The fire zone 1 LED will now pulse to indicate the editing of attribute 1 fire latching for the selected zone Use button 1 to scroll to the attribute that...

Page 34: ...ints should be used on such zones to provide an instant un delayed alarm A 470 call point will be included in the dependency delay sequence Dependency B will apply the following sequence 1 The first d...

Page 35: ...ED will change back to a slow pulse Press and hold button 1 for 3 seconds to save the settings and exit the programming mode There are two programmable timings for dependency mode B the confirmation t...

Page 36: ...lse Zone is under selection and is set to have alarms resound default Slow Pulse Zone is under selection and has been set to not resound alarms on new fire condition LED Off Zone has been set to not r...

Page 37: ...are to be delayed The choice toggles between all sounder circuits all aux outputs or all sounder circuits and all aux outputs The selection is indicated by the Sounder Status LED and the Aux Output St...

Page 38: ...function of the CC input Use button 1 to move to zone 2 fire LED for setting the function of the PUL input and then back to zone 1 again The current setting for the input will be indicated by the ambe...

Page 39: ...s constant and dissapears when a fault occurs for fail safe operation To set either of the two miscellaneous options above or to make outputs programmable enter the above code and press ENTER The fire...

Page 40: ...fire LED 1 10 as per table below The setting of the output is indicated by the amber fault LED ON OFF or PULSING RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESO...

Page 41: ...fire LED 1 6 as per table below The setting of the sounder circuit is indicated by the amber fault LED ON OFF or PULSING RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test La...

Page 42: ...10 Fire Relay Main PCB Fault Relay Main PCB Fire O P Main PCB Fault O P Main PCB OPA Zone ext card 1 Zones 5 8 OPB Zone ext card 1 Zones 5 8 Aux Relay Zone ext card 1 Zones 5 8 OPA Zone ext card 2 Zon...

Page 43: ...n cards with same custom reponses as above the process is exactly the same but using the code 4 3 4 4 I e Use button 1 to select the sounder circuit first indicated by a steady fire zone LED as per ta...

Page 44: ...e required relay or output then use button 2 to change the response indicated by the amber fault LED Each press of button 2 will toggle through the 3 available responses RESOUND SILENCE RESET ENTER 1...

Page 45: ...LEDs 1 6 respectively A pulsing red fire LED indicates which circuit is selected and the setting is represented by the amber fault LED as per table below Use button 1 to move the pulsing fire LED to t...

Page 46: ...e above indicated by the amber fault LED ON Pulsing or OFF Then use button 1 to move to the next function if required Press the ENTER button to return back to the output selection indicated by a stead...

Page 47: ...will display for 10 seconds and then the panel will automatically exit the diagnosis mode Pressing button 2 will reveal the origin of a system fault indication Note After power up the system should be...

Page 48: ...ter panels on the system See panel wide settings 2 1 2 3 option 2 Set Number of Repeater Panels on System Addressing Each repeater panel needs to have a seperate address The addressing is done using t...

Page 49: ...default o p 1 is set to activate on common fire and o p 2 is set to activate for common fault There are 4 programming options available for the inputs and outputs in the repeater panels Outputs 1 6 ac...

Page 50: ...The use of a code entry to activate the controls is enabled by default but can be disabled in the Level 3 engineering functions To activate the controls using the key switch Turn the key clockwise to...

Page 51: ...ode entries It can also be used for fault diagnosis see FAULT DIAGNOSIS section LED On LED Pulsing Zones in Fire 1 12 N A Indicates alarm condition in zone Zone Fault Disabled Test 1 12 Indicates zone...

Page 52: ...LED and finally to the Delay LED Pressing the button once more will move the selection back to Zone 1 again When the desired circuit outputs or delays to be disabled is indicated by a slow pulsing LE...

Page 53: ...Pressing the button once more will move the selection back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the ind...

Page 54: ...fter pressing ENTER LED Steady after pressing ENTER LED Off after pressing ENTER Location Zone 1 Fire LED off Sounder circuit 1 short circuit Sounder circuit 1 open circuit OK Main PCB SNDR 1 Zone 2 F...

Page 55: ...re occurs alarm sounders and outputs will still function Main Board or zone extender boards System Fault LED continous and General Fault LED pulsing and continous buzzer sound Main board or extender c...

Page 56: ...is no longer compliant with this part of BS 5839 THE NEED FOR MAINTENANCE ROUTINE MAINTENANCE TESTING DUTIES OF THE RESPONSIBLE PERSON The system user needs to appoint a single named member of the pr...

Page 57: ...s would normally be a qualified electrical contractor or fire alarm specialist Inspection servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warran...

Page 58: ...Y INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 8 12 Installation Commissioning Operating Manual Approve...

Page 59: ...Y INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 8 12 Installation Commissioning Operating Manual Approve...

Page 60: ...Y INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 8 12 Installation Commissioning Operating Manual Approve...

Page 61: ...Y INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 8 12 Installation Commissioning Operating Manual Approve...

Page 62: ...AULTS ENGINEERS VISITS Esento Marine 8 12 Installation Commissioning Operating Manual Approved Document Ref UI ESEN12MAR 01 Issue 8 0 60 Fault Reason For Call Out Action Taken Date Work Completed Engi...

Page 63: ...AULTS ENGINEERS VISITS Esento Marine 8 12 Installation Commissioning Operating Manual Approved Document Ref UI ESEN12MAR 01 Issue 8 0 61 Fault Reason For Call Out Action Taken Date Work Completed Engi...

Page 64: ...AULTS ENGINEERS VISITS Esento Marine 8 12 Installation Commissioning Operating Manual Approved Document Ref UI ESEN12MAR 01 Issue 8 0 62 Fault Reason For Call Out Action Taken Date Work Completed Engi...

Page 65: ...RATING section and press the blue SILENCE ALARMS button fig 1 To sound the alarms again press the red RESOUND button fig 2 4 In the event of a false alarm look for the device that has caused the alarm...

Page 66: ......

Page 67: ......

Page 68: ...www haes tech com...

Reviews: