PAGE HEADER
Esento Marine 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
25
OPTION 2.
Set Number of Repeater Panels on System
OPTION 3.
Set Time For Panel Delay Timer
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
If repeater panels are to be used, the quantity on the system, 1- 8, must be set up for monitoring purposes.
An incorrect quantity will cause a repeater fault to be shown on the panel.
With the zone 2 fire LED lit, the amber, fault LEDs will show the current quantity of repeaters set 0 - 8. (1
LED lit = 1 repeater, 2 = 2 etc..).
Press the ENTER button, zone 2 fire LED will pulse to indicate ‘edit mode’.
Now use buttons 1 & 3 to increase or decrease the quantity. Button 1 increases, button 3 decreases.
When finished press the ENTER button again and the zone 2 fire LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
The panel delay time for all outputs is set here. To actually apply the delay to the desired outputs, see
programming code 2-3-2-3. The default setting is 3 minutes but can be changed to between 1 - 10
minutes.
With the zone 3 fire LED lit, the amber, fault LEDs will show the current time set. The time is represented
by a binary code using LEDs 1 - 4.
LED 1 = 1min, LED 2 = 2min, LED 3 = 4min, LED 4 = 8min. Therefore if LEDs 1 & 2 are lit the time is 3
minutes (1 + 2). If LEDs 2 & 4 are lit the time = 10 minutes (2 + 8).
Press the ENTER button, zone 3 fire LED will pulse to indicate ‘edit mode’.
Now use buttons 1 & 3 to increase or decrease the time, each press will increase or decrease the time by
1 minute. Button 1 increases, button 3 decreases.
When finished press the ENTER button again and the zone 3 fire LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps