Eclipse Installation, Commissioning & Operating Manual
Approved Document Ref: UI-ECL-01 Issue 8.0
2
ABOUT THIS PANEL
PRODUCT OVERVIEW
Eclipse is a 2 or 4 zone Conventional /Twin Wire (sav-wire) control panel with integral power supply &
Eclipse is a 2 or 4 zone Conventional /Twin Wire (sav-wire) control panel with integral power supply &
space for standby batteries.
space for standby batteries.
Eclipse panels are fully approved to European standards EN54-2 & 4, Fire Detection and Alarm Systems
Eclipse panels are fully approved to European standards EN54-2 & 4, Fire Detection and Alarm Systems
– Control & Indicating Equipment.
– Control & Indicating Equipment.
The control panel comprises of a sheet steel enclosure suitable for wall mounting with a hinged, lockable
The control panel comprises of a sheet steel enclosure suitable for wall mounting with a hinged, lockable
front access door. It can be semi recessed, using a suitable recessing bezel. Cable entry is via 20mm
front access door. It can be semi recessed, using a suitable recessing bezel. Cable entry is via 20mm
‘knockouts’ located at the top and rear of the cabinet.
‘knockouts’ located at the top and rear of the cabinet.
Different key types are used for the door lock and the ‘activate controls’ key-switch. It is also possible
Different key types are used for the door lock and the ‘activate controls’ key-switch. It is also possible
to enable the controls via a 4 digit code entry if preferred. An eight button keypad is used to control the
to enable the controls via a 4 digit code entry if preferred. An eight button keypad is used to control the
system and allow access to the function options. The three main buttons, ‘RESOUND’ (red), ‘SILENCE’
system and allow access to the function options. The three main buttons, ‘RESOUND’ (red), ‘SILENCE’
(blue) and ‘RESET’ (green) being much larger and colour coded to assist the end users.
(blue) and ‘RESET’ (green) being much larger and colour coded to assist the end users.
Two or four fire zone circuits are provided plus two monitored sounder circuits. Fire & Fault VFCO relays,
Two or four fire zone circuits are provided plus two monitored sounder circuits. Fire & Fault VFCO relays,
Fire & Fault switched negative outputs, class change and an alert input are also included. The fire zone
Fire & Fault switched negative outputs, class change and an alert input are also included. The fire zone
outputs can be set as ‘Twin Wire’ by DIL switch selection. In ‘Twin Wire’ configuration, special detector
outputs can be set as ‘Twin Wire’ by DIL switch selection. In ‘Twin Wire’ configuration, special detector
bases and call points must be used.
bases and call points must be used.
Eclipse panels support a large range of conventional detectors including, Apollo, Hochiki & Nittan.
Eclipse panels support a large range of conventional detectors including, Apollo, Hochiki & Nittan.
The panels are supplied with a 1.5 amp internal power supply module. This module complies with the
The panels are supplied with a 1.5 amp internal power supply module. This module complies with the
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
Quiesecent and alarm current details for standby battery calculations
Model
Standby Current
Alarm Current
ECL-2
75mA
116mA
ECL-2 (set to Twin Wire mode)
75mA
134mA
ECL-4
85mA
133mA
ECL-4 (set to Twin Wire mode)
85mA
170mA