3.10.2 Disable
-
Outputs
The Disable Outputs Option enables the isolation of some or all of the outputs. If disabled, the
outputs will not activate in the event of a fire alarm or other programmed event.
If the current User ID does not have the necessary permission, the display prompts for entry of a
password to guard against inadvertent changes.
[Disable]
Enter the password as normal. Once a valid password has been entered, a pop-up window is shown
on the display to select the type of outputs to disable. Scroll down to view / select the available
options. The list below details all of the possible options – the available options will have been
configured by the installation engineer.
ALL OUTPUTS
ALL SOUNDERS
ALL BEACONS
FIRE ROUTING OUTPUTS
FIRE PROTECTION OUTPUTS
↓
FAULT ROUTING OUTPUTS
ALL OTHER RELAY OUTPUTS
ONLY SELECTED OUTPUTS
PAGERS
3.10.2.1 All Sounder Outputs
Press the
buttons to scroll through and highlight the ALL SOUNDERS Option and then press
the
button to disable them. The display automatically reverts to the Main Disable Menu.
The ‘Sounder Disabled’ Indicator will be illuminated.
3.10.2.2 All Beacon Outputs
Press the
buttons to scroll through and highlight the ALL BEACONS Option and then press the
button to disable them. The display automatically reverts to the Main Disable Menu.
NOTE: This only applies to individually addressable beacons. For some combined sounder/beacon
devices, the beacon follows the operation of the sounder and it is only possible to disable both the
sounder and the beacon together.
3.10.2.3 Fire Routing Outputs
Press the
buttons to scroll through and highlight the FIRE ROUTING OUTPUT Option and then
press the
button to disable all fire routing outputs. The display automatically reverts to the Main
Disable Menu.
The ‘Fire Routing Disabled’ Indicator will be illuminated.
3.10.2.4 Fire Protection Outputs
Press the
buttons to scroll through and highlight the FIRE ROUTING OUTPUT Option and then
press the
button to disable all fire protection outputs. The display automatically reverts to the
Main Disable Menu.
3.10.2.5 Fault Routing Outputs
Press the
buttons to scroll through and highlight the FAULT ROUTING OUTPUT Option and
then press the
button to disable all fault routing outputs. The display automatically reverts to the
Main Disable Menu.