3.3.8 Zones
The Commission Zones option lists all the zones in use by this panel and allows the zone text
description to be changed.
[Commission Zones]
Zone Location
0001 BASEMENT WEST
0002 RECEPTION
0015 EAST WING
0018 TOWER BLOCK
To change the location text assigned to the Zone, press the
button when the Zone Location Text
is highlighted. Refer to Section
3.1.4
for guidance on how to change text descriptions.
To select a different zone, use either the scroll up/down keys, or just type in the number of the
required zone, followed by the
button. Note that only zones in use are displayed.
3.3.9 Exit
To exit the Commission Mode and return the panel to normal operation (i.e. level 2), select the “Exit”
option. The display will prompt for confirmation of the Level 3 password. For example:
[Commission Menu 1]
Please Enter Your Password
Next
Menu
If the password is incorrect (this will be indicated) or if the password is not entered within 5-seconds,
the display will revert to the Commission Level Menu and level-2 will not be entered.
After commissioning, the panel must always be returned to level 2 (or level 1) to give normal fire
coverage.
3.3.10 Disable
This function is the same as User Level 2 function – refer to User Manual for further information.
The following options can be disabled:
Zones / Inputs
Outputs
Groups
P
P
C
C
O
O
N
N
L
L
Y
Y
If beacon outputs are configured so that they can be independently disabled /
enabled, then configure one of the front panel “Function” LED indicators to
indicate the disabled state of these devices.
3.3.11 Enable
This function is the same as User Level 2 function – refer to User Manual for further information.
The following options can be disabled:
Zones / Inputs
Outputs
Groups