Page 2 of 72
Item
Specification Details
HS-5100
HS-5200
HS-5400
Enclosure
Steel IP30
Steel IP30
Steel IP30
Dimensions H x W x
D mm
345 x 345 x 85
(/M) 345 x 430 x 120
(/L) 475 x 450 x 120
(/D) 475 x 450 x 190
345 x 430 x 120
(/L) 475 x 450 x 120
(/D) 475 x 450 x 190
475 x 450 x 120
(/D) 475 x 450 x 190
Weight (excluding
batteries)
6Kg
(/M) 8Kg
(/L) 10Kg
8Kg
(/L) 10Kg
(/D) 12Kg
10Kg
(/D) 12Kg
Temperature
-5°C to 40°C
-5°to 40°C
-5°C to 40°C
Humidity (RH)
95 % Max
95 % Max
95 % Max
Cable Entries
(20mm knockouts)
13x top / 8x top rear
(/M) 17x top / 11x top rear / 2
bottom
(/L) 19x top / 11x top rear / 2
bottom
(/D) 30x top / 11x top rear / 3
bottom
17x top / 11x top rear / 2 bottom
(/L) 19x top / 11x top rear / 2
bottom
(/D) 30x top / 11x top rear / 3
bottom
19x top / 11x top rear / 2 bottom
(/D) 30x top / 11x top rear / 3
bottom
AC Supply
(ratings marked on
label inside panel –
see section 2.1 for
location)
200-240V +10%, -15%
47 –63 Hz AC
1.0A max
200-240V, +10%, -15%
47 –63 Hz AC
1.4A max
200-240V, +10%, -15%
47 –63 Hz AC
1.4A max
Battery Capacity
24V 4Ah Internal (min)
24V 7Ah Internal (max)
(/M) 24V 12Ah Internal (max)
(/L) 24V 18Ah Internal (max)
(/D) 24V 24Ah Internal (max)
24V 4Ah Internal (min)
24V 12Ah Internal (max)
(/L) 24V 18Ah Internal (max)
(/D) 24V 45Ah Internal (max)
24V 4Ah Internal (min)
24V 18Ah Internal (max)
(/D) 24V 45Ah Internal (max)
Charging Current
1.0A Temp Compensated
2.0A Temp Compensated
2.0A Temp Compensated
Power Supply
On-board 24V DC, 3A High
Efficiency Off-Line Switched
Mode
On-board 24V DC, 5A High
Efficiency Off-Line Switched
Mode
On-board 24V DC, 5A High
Efficiency Off-Line Switched
Mode
Output Voltage
1
18.0V – 28.0V
18.0V – 28.0V
18.0V – 28.0V
Ripple (Vpkpk)
1.0V 1.0V 1.0V
Max Battery Ohms
1.6
Ω
± 0.1
Ω
0.8
Ω
± 0.1
Ω
0.8
Ω
± 0.1
Ω
Imax(a)/
Imax(b)
2
1.6A
3.0A
2.6A
5.0A
2.6A
5.0A
Number of Fire
Zones
200 max
(2000 when networked)
200 max, across 2 loops
(2000 when networked)
200 max, across 4 loops
(2000 when Networked)
Number of Loops
1
2
1 to 4
Devices per Loop
Apollo
126 detector/call points per loop (max)
Hochiki
127 detector/call points per loop (max)
AV
240 detector/call points per loop (max)
Nittan
254 detector/call points per loop (max)
VdS
2095
Clause 6.2.5
Not more than 128
devices per loop
V d S
2095
Not more than 512
devices per panel
or 12000m
2
Loop Current
3
500mA max.
500mA max. per Loop
500mA max. per Loop
Protocols
Apollo S90, XP95, Discovery, Explorer and Hochiki ESP or AV or Nittan Evolution
Sounder Outputs
3
2 x 1A Programmable
2 x 1A Programmable
4 x 1A Programmable
Relay Outputs
(Programmable)
2 x1A 30VAC/DC (max)
10mA 5V (min)
2 x 1A 30V AC/DC (max)
10mA. 5V (min)
2 x 1A 30V AC/DC (max)
10mA. 5V (min)
Auxiliary Output
3
4
24V DC, 500mA
24V DC, 500mA
24V DC, 500mA
Display
LCD White backlit 240 x 64 Graphical LCD
Programmable
Inputs
8x Switch inputs, 1 x Hard wired input and Four x programmable push buttons c/w slide in labels
USB/RS232
USB B type interface and RS232 for PC connection
Event Log
5000 Event & Diag 500 Fire
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
1
Minimum/maximum specifications for the AUX, and Sounder outputs. Detector Loop voltage is not dependant on AC or battery
voltage.
2
Only applicable if the panel is configured to turn off the charger in alarm. Otherwise, Imax(b)=Imax(a).
3
Total output current from panel not to exceed Imax(b) less internal power consumption.
4
Aux supply tracks a maximum of 0.5V below battery terminal voltage when no mains supply is available.
www.acornfiresecurity.com
www.acornfiresecurity.com