background image

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

EN54 APPROVED 8-12 ZONE PULSE2 ALARMSENSE PLUS 

CONTROL PANEL 

 

810a/06

 

 
 
 
 
 
 
 
 
 

 
 
 

 

Document EUFS-UI-ASP-02 Issue 1.0

 

Summary of Contents for AlarmSense PLUS

Page 1: ...EN54 APPROVED 8 12 ZONE PULSE2 ALARMSENSE PLUS CONTROL PANEL 810a 06 Document EUFS UI ASP 02 Issue 1 0 ...

Page 2: ...s and used in accordance with this manual Hazardous voltages are present inside the panel DO NOT open it unless you are qualified and authorised to do so There is no need to open the panel s enclosure except to carry out commissioning maintenance and remedial work This work must only be carried out by competent service personnel who are fully conversant with the contents of the panel s installatio...

Page 3: ...ll capacity are capable of delivering very high currents which can cause fire or injury therefore battery connections should be done with caution The panel is supplied with battery leads already connected to the battery terminals on the main PCB These leads are coloured red for ve and black for ve 2 x 12v batteries should be connected in series using the white jumper lead provided See diagram To o...

Page 4: ...mSense panels have special programming options incorporated for use with AlarmSense devices Setting as to whether non priority mode is available per zone Programmable time delay for non priority alarms 30 60 or 120 seconds Panel display response during non priority alarms either no indication or zone LED with buzzer Non Priority Functionality When a sounder base has been set as non priority If smo...

Page 5: ...visual audible indication a t the panel but no sounder operation Turn off priority alarm feature for zone 3121 AlarmSense Options Set non priority zones Set alarm confirmation delay time Set non priority mode indication 1212 EN54 Sounder Resound Options Set zones to not resound alarms after an initial fire condition 1114 Delays to Outputs Apply delays to outputs in response to selected zones 2323 ...

Page 6: ...ineering functions To activate the controls using the key switch Turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off position and the Access Level indicator LED will extinguish If the key switch is in the On position the keypad will remain active NOTE It is ...

Page 7: ...icated by the Aux Output Status LED and finally to the Delay LED Pressing the button once more will move the selection back to Zone 1 again When the desired circuit outputs or delays to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the circuit between disabled and enable...

Page 8: ... not the sounders will ring during test Pressing the button once more will move the selection back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the zone between in and out of test Then use Test Mode button again to move to the next...

Page 9: ... ENTER Location Zone 1 Fire LED off Sounder circuit 1 short circuit Sounder circuit 1 open circuit OK Main PCB SNDR 1 Zone 2 Fire LED off Sounder circuit 2 short circuit Sounder circuit 2 open circuit OK Main PCB SNDR 2 Zone 3 Fire LED off Sounder circuit 3 short circuit Sounder circuit 3 open circuit OK High Spec Extension Zone Card Zone 4 Fire LED off Sounder circuit 4 short circuit Sounder circ...

Page 10: ... This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System DATE DEVICE TESTED LOCATION COMMENTS IF ANY INITIALS OF TESTER TIME OF TEST Excel EN Quick Start Guide Approved Document Ref UI XLEN 03 Issue 1 0 ...

Page 11: ...heck to see if a call point glass is broken if so replace the glass or call an engineer 5 When fully satisfied that there is no fire return to the control panel and press the green RESET button fig 3 The panel display should return to normal and only the green SUPPLY HEALTHY LED should be lit on the control panel Disable Mode Test Mode Mute Buzzer Test Lamps Disable Mode Test Mode Mute Buzzer Test...

Page 12: ...EU Fire Security Units 2 4 The Pavilions Bridgefold Road Rochdale OL11 5BY ...

Reviews: