AlarmSense PLUS Quick Start Guide

 

Document Ref: EUFS-UI-ASP-02 Issue 1.0

 

6

 

 

 

 

 

RESOUND

 

 

 

SILENCE

 

 

 

RESET

 

 

 

TEST MODE

 

Test  Mode  is  used  when  testing  the  fire  alarm  system.  In  test  mode  the  devices  in  the  zone(s)  in  test, 
detectors and call points etc, can be activated and the panel will automatically reset, enabling the system 
to be tested by one person. It is possible to test head removal monitoring and to test the system with  or 
without the sounders.

 

 

To initialise  Test Mode,  firstly  activate  the  controls  by  turning  the  key 
switch or by entering the four digit code. Then press and hold the Test 
Mode button (2) for 3 seconds.

 

 

After 3 seconds the panel will bleep and the Test Mode LED and Zone 
1  Fault  LED  will  pulse  slowly,  indicating  that  Zone  1  is  in  test

 

 

Mute 

Buzzer

 

 

Test 

Lamps

 

selection mode. The Sounder Status LED will also be pulsing rapidly, this indicates that the test will be

 

with 

sounders. (Test mode without sounders is explained below)

 

 

Pressing the Test Mode button again will move test selection mode to Zone 2 and the Zone 2 Fault LED will 
be pulsing instead. Subsequent presses will move the selection to Zones 3 - 12, dependant on the number 
of zones fitted to the panel. I.e up to zone 4 on a 4 zone, 6 on a 6 zone, 8 on a 8 zone etc..

 

 

After the last available zone the next press will move the selection mode to the sounder circuits, indicated 
by no Zone Fault LEDs on. This position selects whether or not the sounders will ring during test. Pressing 
the button once more will move the selection back to Zone 1 again.

 

 

When the desired zone to be tested is indicated by a slow pulsing LED, use the ENTER button to select 
it. Once selected the indicator LED will change to a rapid pulse. Pressing

 

ENTER again  will toggle the  zone  between in  and out of test. Then  use 
Test Mode button again to move to the next zone. Any or all zones can be 
in test mode simultaneously.

 

 

When at the sounder status position, use the ENTER button to toggle

 

between testing with or without sounders. A rapid pulse = with sounders 
(default), a slow pulse = without sounders.

 

Disable 

Mode

 

Test 

Mode

 

 

When all zones to be tested have been selected, press and hold the Test Mode button for 3 seconds again. 
This will exit the test selection mode. All zones in test and the Test Mode will now be indicated by a steady 
LED.

 

 

To take zones out of test mode, repeat the above process using the Test Mode button to select the zone 
and the ENTER button to change the status.

 

 

Test Mode With Sounders

 

 

Activation of a call point or detector - sounders will pulse twice, device is automatically reset. 
Removal of a detector - sounders will pulse once.

 

 

Test Mode Without Sounders

 

 

Activation of a call point or detector - panel buzzer and LED response only, device is automatically reset.

 

 

 

Tip:

 

With the controls active, pressing the Test Mode button briefly will reveal which circuits are in test mode (as 
opposed to disabled). This is useful if using Disable Mode and Test Mode at the same time.

 

2

 

Disable 

Test

 

Mode 

Mode

 

3

 

4

 

 

ENTER

 

 

 

RESOUND

 

 

 

SILENCE

 

 

 

RESET

 

1

 

2

 

3

 

Mute 

Buzzer

 

4

 

Test 

Lamps

 

ENTER

 

Summary of Contents for AlarmSense PLUS

Page 1: ...EN54 APPROVED 8 12 ZONE PULSE2 ALARMSENSE PLUS CONTROL PANEL 810a 06 Document EUFS UI ASP 02 Issue 1 0 ...

Page 2: ...s and used in accordance with this manual Hazardous voltages are present inside the panel DO NOT open it unless you are qualified and authorised to do so There is no need to open the panel s enclosure except to carry out commissioning maintenance and remedial work This work must only be carried out by competent service personnel who are fully conversant with the contents of the panel s installatio...

Page 3: ...ll capacity are capable of delivering very high currents which can cause fire or injury therefore battery connections should be done with caution The panel is supplied with battery leads already connected to the battery terminals on the main PCB These leads are coloured red for ve and black for ve 2 x 12v batteries should be connected in series using the white jumper lead provided See diagram To o...

Page 4: ...mSense panels have special programming options incorporated for use with AlarmSense devices Setting as to whether non priority mode is available per zone Programmable time delay for non priority alarms 30 60 or 120 seconds Panel display response during non priority alarms either no indication or zone LED with buzzer Non Priority Functionality When a sounder base has been set as non priority If smo...

Page 5: ...visual audible indication a t the panel but no sounder operation Turn off priority alarm feature for zone 3121 AlarmSense Options Set non priority zones Set alarm confirmation delay time Set non priority mode indication 1212 EN54 Sounder Resound Options Set zones to not resound alarms after an initial fire condition 1114 Delays to Outputs Apply delays to outputs in response to selected zones 2323 ...

Page 6: ...ineering functions To activate the controls using the key switch Turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off position and the Access Level indicator LED will extinguish If the key switch is in the On position the keypad will remain active NOTE It is ...

Page 7: ...icated by the Aux Output Status LED and finally to the Delay LED Pressing the button once more will move the selection back to Zone 1 again When the desired circuit outputs or delays to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the circuit between disabled and enable...

Page 8: ... not the sounders will ring during test Pressing the button once more will move the selection back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the zone between in and out of test Then use Test Mode button again to move to the next...

Page 9: ... ENTER Location Zone 1 Fire LED off Sounder circuit 1 short circuit Sounder circuit 1 open circuit OK Main PCB SNDR 1 Zone 2 Fire LED off Sounder circuit 2 short circuit Sounder circuit 2 open circuit OK Main PCB SNDR 2 Zone 3 Fire LED off Sounder circuit 3 short circuit Sounder circuit 3 open circuit OK High Spec Extension Zone Card Zone 4 Fire LED off Sounder circuit 4 short circuit Sounder circ...

Page 10: ... This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System DATE DEVICE TESTED LOCATION COMMENTS IF ANY INITIALS OF TESTER TIME OF TEST Excel EN Quick Start Guide Approved Document Ref UI XLEN 03 Issue 1 0 ...

Page 11: ...heck to see if a call point glass is broken if so replace the glass or call an engineer 5 When fully satisfied that there is no fire return to the control panel and press the green RESET button fig 3 The panel display should return to normal and only the green SUPPLY HEALTHY LED should be lit on the control panel Disable Mode Test Mode Mute Buzzer Test Lamps Disable Mode Test Mode Mute Buzzer Test...

Page 12: ...EU Fire Security Units 2 4 The Pavilions Bridgefold Road Rochdale OL11 5BY ...

Reviews: