111
SCADA-Modbus
®
System Guidelines
With the exception of baud rate, the communication parameters must not vary from this
format.
E.8 User Memory Customizing
The most familiar component of existing SCADA networks today is the Programmable
Logic Controller (PLC). Because the network integrator is most familiar with this type of
device, the flow meter emulation of an existing PLC simplifies the process of integrating
the manufacturer’s instrumentation into the SCADA network. Modbus ASCII uses a
referencing system to identify the various types of memory inputs and outputs. Each
reference number has a leading digit that identifies its data type (discrete input, discrete
output, register input, register output) followed by a string of digits that indicates its
location in RAM (
The memory data is stored in 16-bit words. Within the predefined function codes of the
Modbus ASCII protocol, the data fields are subject to interpretation by the device
manufacturer. For example, the 950 Flow Meter places temperature information in
registers 40001-40002.
E.9 Modbus ASCII Function Codes Supported
Currently, the 950
Flow Meter is capable of a read-only function to retrieve channel and
total flow information. All data addresses in the Modbus ASCII message are referenced to
zero. Therefore, a reference to holding register 40001 is addressed as register 0000. The
function code field specifies the type of register accessed; therefore, the 4XXXX is
implicit.
Function 03: Read Holding Registers
Reads the register (4X reference) contents of the 950 Flow Meter as defined in the tables
that follow.
Table 40 Modbus ASCII Memory Input/Output Referencing System
Reference
Indicator
Reference Type
Meaning
0xxxx
discrete output or coil
binary
1xxxx
discrete input
binary
3xxxx
input register
real
4xxxx
output holding register
real
6xxxx
extended memory register
real
Summary of Contents for Sigma 950
Page 2: ......
Page 6: ...4...
Page 20: ...18 Introduction...
Page 34: ...32 Basic Programming Setup...
Page 50: ...48 Sensor Installation...
Page 82: ...80 Maintenance...
Page 83: ...81 Appendix A Program Flow Charts Figure 22 Overview of Basic Program Menus...
Page 84: ...82 Program Flow Charts Figure 23 Setup Flow Chart...
Page 85: ...83 Program Flow Charts Figure 24 Options Flow Chart...
Page 86: ...84 Program Flow Charts Figure 25 Alarms Menus Flow Chart...
Page 87: ...85 Program Flow Charts Figure 26 Calibration Menus Flow Chart Page 1...
Page 88: ...86 Program Flow Charts...
Page 102: ...100 Programming Features...
Page 106: ...104 Primary Devices Head Measurement Locations...
Page 126: ...124 SCADA Modbus System Guidelines...