GB
19
G. Pellet fuel has too low a
calorific value
F. Screw motor defective - contact
service department
G. Clean burner - switch to high
quality pellet type
F006
A. Combustion chamber door
open during operation
B. Damper in front of the door
contact switch not in the right
position
C. Cable broken in the electric
wiring to the door contact switch
D. The connector has come out
on the door contact switch or on
the central unit
A. Clean burner - close door
B. Clean burner - Adjust damper
in front of the door contact switch
C. Cable broken on door contact
switch - contact service
department
D. Contact service department
F007
A. Flue gas temperature sensor
defective or not connected
A. Contact service department
F008
A. Flue gas temperature sensor
defective
A. Contact service department
F009
A. Note: Combustion chamber
door open during "Off or standby"
A. No correction necessary -
Close door - Error is automatically
cleared
F011
A. Room temperature sensor
defective or not connected
A. Contact service department
F012
A. Room temperature sensor
defective
A. Contact service department
F015
A. Induced draught fan defective
B. Power supply to the fan motor
interrupted
A. Contact service department
B. Check cable - contact service
department
F018
A. Power cut
A. Clean burner - Clear error 018
F021
A. Burner dirty
B. Pellet tank empty
C. Downpipe / screw conveyor
blocked
D. Room too airtight – required
combustion air cannot flow into
the room
E. Flue gas temperature sensor
defective
F. Screw motor defective
G. Pellet fuel has too low a
calorific value
A. Clean burner
B. Clean burner - fill pellet tank
C. Clean the intake on the screw
conveyor housing with a vacuum
cleaner. – Clean burner
D. Clean burner - Ensure
adequate combustion air
E. Flue gas temperature sensor
defective - contact service
department
F. Screw motor defective - contact
service department
G. Clean burner - switch to high
quality pellet type
F022
A. Flue draught too low
B. Flue draught too high
C. Burner dirty
D. Flue tube pipeline too long
(horizontal)
E. Flue gas temperature sensor
defective
A. Measure flue draught - contact
service department
B. Measure flue draught - contact
service department
C. Clean burner
D. Change flue tube pipeline-
contact service department
E. Flue gas temperature sensor
defective - contact service
engineer