9
Table 3 Information on labels affixed to the fiber between the device and the ODF
Content Meaning
Example
MN-B-C-D-R/T
MN
—Rack number
•
M
—Row number of the rack in the
equipment room, in the range of A to Z.
•
N
—Column number of the rack in the
equipment room, in the range of 01 to
99.
For example, A01.
B
—Chassis number
Numbered in bottom-up order with two digits,
for example, 01.
C
—Slot number
Numbered in top-down and left-right order
with two digits, for example, 01.
D
—Fiber port number
Numbered in top-down and left-right order
with two digits, for example, 05.
R
—Optical receiving interface
T
—Optical transmitting
interface
N/A
ODF-MN-B-C-R/T
MN
—Row number and column
number of ODF
•
M
—Row number of the rack in the
equipment room, in the range of A to Z.
•
N
—Column number of the rack in the
equipment room, in the range of 01 to
99.
For example, G01 is the ODF of Row G and
Column 01.
B
—Row number of the terminal
device
In the range of 01 to 99, for example, 01-01.
C
—Column number of the
terminal device
R
—Optical receiving interface
T
—Optical transmitting
interface
N/A
Figure 11 Example of a label on an optical fiber between the device and the ODF
{
ODF-G01-01-01-R
—The local end of the optical fiber is connected to the optical receiving
terminal on Row 01, Column 01 of the ODF in Row G Column 01 in the equipment room.
{
A01-01-05-05-R
—The peer end of the optical fiber is connected to Optical Receiving
Interface 5 on Slot 05, Chassis 01 in the cabinet on Row A, Column 01 in the equipment
room.
Summary of Contents for S7500X Series
Page 119: ...12 Figure 14 Example of a device label...
Page 124: ...4 Figure 6 Power cord management...