Condition

Possible Cause

Remedy

Overfilling

Damaged component(s)

Contact H2flow Controls

Overfilling

Improper installation

Attempt pairing process of sensor and valve controller

Overfilling

Valve solenoid is not in 

the OFF position

Ensure the valve solenoid is in the fully closed / OFF position

Overfilling

Sensor removed from 

pool. 

If the sensor is in a dry location, it will believe water is needed in the 

pool and the valve will open at every opportunity. Re-apply the sensor 

in the desired location on the side of the pool. Alternativly, disconnect 

the valve controller power supply and reconnect when you are ready 

to pair the unit again.  

Overfilling

Sensor mounted with 

screws

The sensor should only be mounted with epoxy provided in the 

LevelSmart kit. Check that the level sensor is not cracked. If needed, 

contact H2flow Controls for further assistance.

Overfilling

Use of out of spec valve 

(DC, Voltage, etc.)

Use only the components supplied with the LevelSmart unit. If need-

ed, replacement parts can be purchased from H2flow Controls.

Damaged 

Valve

Improper installation, 

over tightening, freezing, 

etc.

Refer to the Instruction Manual, Quick Start Guide and Online 

Tutorials for guidance on proper installation and maintenance of Lev-

elSmart. If needed, replacement parts can be purchased from H2flow 

Controls. 

Damage

Freeze damage from 

improper winterization

In colder climate areas, a flexible garden hose is the recommended 

water supply, rather than PVC pipe. This allows for easy drainage/

winterization.

Water level 

draining down 

fast

Vacuum Breaking check 

valve installed instead 

of regular check valve 

in water supply line and 

hose spigot turned off. 

Pump’s water pressure 

causes valve to vent and 

discharge pool water.

Replace Vacuum Breaking check valve with regular check valve. In-

struct people to not turn water spigot off.

TROUBLESHOOTING

8

Summary of Contents for levelsmart

Page 1: ...Instruction Manual English levelsmart Wireless Autofill USER INSTRUCTION MANUAL...

Page 2: ...e Antenna 7 Install the Power Supply and connect to the Valve Controller 8 Pair the Level Sensor and Valve Controller 8 Mount the Level Sensor 9 Mount the Antenna 10 Set and calibrate the water level...

Page 3: ...tallation setup and troubleshooting c Media The following QR Code will take you to avaliable videos that cover the installation and commissioning of the system SUPPORTING DOCUMENTS MEDIA 1 LevelSmart...

Page 4: ...mmunicates this condition to the valve controller via a wireless signal The valve controller opens the water supply valve for 7 minutes to restore the desired level Every 30 minutes the valve controll...

Page 5: ...ss Autofill 5 LevelSmart valve controller LevelSmart level sensor Automatic valve Antenna Accessory kit epoxy x2 wire nuts x2 screws Power supply Antenna extension cable optional Quick Start Guide WHA...

Page 6: ...nd calibrate the water level INSTALLATION AND SETUP 4 a Installing the Valve The valve has 1 Female NPT sockets on each end The valve also has a directional arrow molded into the top of the sockets it...

Page 7: ...r s responsibility to check into this and to install an appropriate device if necessary b Install and connect the Valve Controller The valve controller should be mounted on the wall next to the equipm...

Page 8: ...nect the Power Supply s 120 VAC plug into the outlet At this point you should see the three LED s on the front of the Valve Controller flash in a repetitive sequence from the bottom to the top green y...

Page 9: ...pairing mode the three LED s scrolling from bottom to top or a solid yellow Action LED will illuminate If the unit goes back into either of these conditions we need to move the Level Sensor or Antenna...

Page 10: ...the face for at least 90 seconds Do not try to pull it off after the 90 seconds as the putty will continue to cure for the next hour or two g Mount the Antenna Peel the backing tape off the rear of th...

Page 11: ...1 5 for 2 seconds and remove it b Once the magnet has been removed the ACTION LED will illuminate for five 5 seconds When this occurs the valve will open for five 5 seconds before closing Confirm that...

Page 12: ...tom of the Sensor housing Use the magnet to reset the sensor in the pool by holding the magnet on the face of the sensor for five 5 seconds as shown in Fig1 6 When the magnet is removed after five 5 s...

Page 13: ...e as follows a Solenoid This is operated electrically by the LevelSmart Valve Controller The solednoid can be operated manually by opening it turn counterclockwise to allow flow through the valve Howe...

Page 14: ...eded contact H2flow Controls for further assistance Overfilling Use of out of spec valve DC Voltage etc Use only the components supplied with the LevelSmart unit If need ed replacement parts can be pu...

Page 15: ...tained Valve or Valve Control ler not operating Activate valve using magnet see Section 5 Con firm Action LED illuminates If so check for water flowing through valve If not use a voltmeter check for 2...

Page 16: ...and in any case where the product has been disassembled by anyone other than authorized Seller s representatives EXCEPT FOR THE LIMITED WARRANTY OF REPAIR AND REPLACEMENT STATED ABOVE SELLER DISCLAIMS...

Reviews: