General

Meter configuration

CONTOIL

®

oil meters consist of a flow sensor and a measurement transducer with display, totaliser and signal outputs where applicable.

The flow rate range determines the nominal size of the flow sensor. The measurement transducer is either one complete ("universal") unit
(e.g. VZF) or is a combination of complementary units (transducer group) which can be chosen to suite a particular application (VZO).

Measurement transducer VZF / VZFA

Transducer group VZO / VZOA

with relay and analogue outputs

with RV pulser,  

and electronic display

mechanical display

The flow sensor and the measurement transducer are calibrated jointly and form one metering unit.
For optimal results for differential measurements, meters of types VZFA or VZOA with special calibration should be used.
If the measurement transducer is replaced at a later stage, a certain divergence in measured values is to be expected.

Applications, planning and installation 

CONTOIL

®

oil meters must only be used for their intended purpose and comply with safety regulations. 

IBE

 devices are manufac-

tured according to valid standards and guidelines. 

IBE 

guarantees the quality of the product in the context of its General Terms of

Business. The owner or operator will be liable for the correct installation as well as the appropriate handling of the equipment upon its re-
ceipt. The instructions for assembly and operation are to be followed exactly. None of the information stated here releases planners, in-
stallers and operators from their own careful and comprehensive assessment of the respective plant configuration in terms of functional
capability and operational safety.

Safety precautions 

• The design of the plant must ensure that the meter cannot be damaged, especially from the effects of icing, torsion in the piping, 

excessive heat expansion of the piping, misaligned pipes during installation, intrusion of foreign bodies or silt-up.

• The clearance distance of the piping must be adhered to when mounting the meter. If using flanged connections, the correct number of

connector elements must be fitted and they must be tightened with the correct torque in accordance with the screw manufacturer’s 
instructions.

• Comply with the permissible operating data as defined on the type plate. Pressure test with a maximum of 1.5 x the nominal 

pressure (PN).

• Make sure that no hazardous fumes can build up in the piping and in the meter during commissioning, decommissioning and 

dismantling.

• The meter must at all times be completely filled with liquid during operation.
• Check the meter periodically for tightness of the connections and for proper functioning.
• If work is to be done on the installation, before each intervention:

a) release the pressure in the installation 
b) if hazardous liquids are used, wear protective clothing and safety goggles
c) place a collecting tray underneath the installation.

Schematic view. For details, see 
the Dimensional Drawings section.

Flow sensor

Summary of Contents for CONTOIL VZF Series

Page 1: ...CONTOIL DN15 50 VZO VZOA VZF VZFA Table of contents General Meter Configuration 14 Application planning and installation 14 Safety precautions 14 Plant design Layout of piping 15 Meter installation 1...

Page 2: ...osages 29 Circuit lectrique 29 Montage du compteur Pr paration au montage 30 Montage du compteur dans la conduite 30 Raccordements lectriques 31 Prescriptions de s curit 31 Sch ma de raccordement 31 E...

Page 3: ...ngsanleitung ist genau zu beachten Alle hierin angegebenen Hinweise entbinden Planer Installa teure und Betreiber nicht von einer eigenen sorgf ltigen und umfassenden Beurteilung der jeweiligen Anlage...

Page 4: ...sind vom Messger t zu erfassen Tank Pumpe R ckschlag ventil Tank lz hler lz hler Richtige Auslegung von Messger t und Zubeh r Bei Verwendung des Messger tes f r Viskosit ten ber 5 mPa s oder beim Ein...

Page 5: ...t werden Der im Z hlereinlauf eingebaute Filter ist ein reiner Sicherheitsfilter und zu klein um als Schmutzfilter zu wirken W rmeisolation Die Aufbaugruppe darf nicht mit einer W rmeisolation versehe...

Page 6: ...ie richtige Leitung d h der Vorlaufz hler in die Zuleitung zum Verbraucher und der R cklauf z hler in die R ckleitung eingebaut werden Besonderheiten Marine Auf Schiffen wird darauf geachtet dass der...

Page 7: ...rgibt die h chste Genauigkeit Schnelles Ventil ffnen schliessen ist aufgrund m glicher Druck schlagbildung zu vermeiden Druckschl ge k nnen die Messger te besch digen Elektrische Leitungsf hrung Elekt...

Page 8: ...fnen Druckprobe in der Anlage durchf hren Dichtigkeit kontrollieren Leitungsnetz r ckstandsfrei sp len Druckentlastung vornehmen und Anlage wieder ausser Betrieb setzen Mit diesem Probebetrieb wird si...

Page 9: ...Variante muss im Parameter Men eingestellt werden 1 potentialfreier Digitalausgang Rel 1 frei parametrierbar auf eine der drei unten genannten Funktionen 1 passiver Stromausgang 4 20 mA Analog dieser...

Page 10: ...Ruhestrom 1 mA bei 8 V 1 k Impulswert siehe Typenschild Anschluss Kabel min 2 x 0 35 mm2 und 4 6 mm Aussendurch messer auf mitgelieferten Stecker oder Option Art 80019 mit montiertem Kabel verwenden I...

Page 11: ...nd zu vermeiden damit das Messger t nicht besch digt wird Lufteinschl sse verursachen bei allen Messsystemen Fehlmessungen und k nnen im Betrieb das Messger t besch digen Dichtheitskontrolle der Ger t...

Page 12: ...Messkammer und Ringkolben der Z hler DN 15 50 demontiert werden ohne diese aus der Leitung auszubauen Der Reinigungs und Revisionszyklus ist stark von den Betriebsbedingungen abh ngig Bei g nstigen B...

Page 13: ...5 VZO VZOA 20 25 40 VZO VZOA 50 Sensor VZF A VZO 15 25 VZO 40 50 VZOA 15 50 Max Temperatur 130 180 C 130 C 180 C 130 C 180 C Impulsgeber alle RV IN RV IN RV IN RV IN Massbild 1 2 3 6 5 4 8 5 4 7 5 4 8...

Page 14: ...for assembly and operation are to be followed exactly None of the information stated here releases planners in stallers and operators from their own careful and comprehensive assessment of the respec...

Page 15: ...ed by the meter Tank Pump Nonreturn valve Tank Oilmeter Oilmeter Correct layout of meter and accessories If the meter is used for viscosities in excess of 5 mPa s or if it is mounted on the suction si...

Page 16: ...removed The filter mounted in the meter inlet is only a safety filter and is too small to act as a dirt filter Heat insulation The measurement transducer must not be insulated This could cause its pe...

Page 17: ...he correct pipes i e the supply flow meter should be installed in the pipe that supplies the consumer and the return flow meter should be installed in the return pipe Special requirements ships On shi...

Page 18: ...the higher the accuracy Fast opening and closing of the valve should be avoided as this can cause pressure or water hammer Water hammer damages the meter Electrical installations Electrical installat...

Page 19: ...he stop valves slowly when doing this Carry out a pressure test in the plant Check for leak tightness Flush the pipework until no residues are left Release the pressure and stop the plant again This t...

Page 20: ...of connection the desired one must be set in the Parameter Menu 1 potential free digital output Rel 1 freely parameterisable to one of the three functions mentioned below passive current output 4 20...

Page 21: ...V 1 k quiescent current 1 mA at 8 V 1 k pulse value see type plate connecting cable min 2 x 0 35 mm2 and 4 6 mm external diameter on plug supplied with product or use option part no 80019 with cable m...

Page 22: ...oided in order not to damage the meter Inclusions of air cause measuring errors in all types of meter and can damage them in operation Check the tightness of the connections of the device Check the fl...

Page 23: ...Maintenance spare parts Check connections periodically for tightness and if necessary tighten again For control and cleaning the measuring chamber and the ring piston of the meters DN15 50 can be rem...

Page 24: ...DN15 165 105 260 95 45 65 G 3 4 G 1 2 DN20 165 105 260 105 54 74 G 1 G 3 4 DN25 190 130 305 115 77 101 G 11 4 G 1 DN40 300 210 440 150 116 153 G 2 G 11 2 DN50 350 280 165 166 209 VZF VZFA VZO VZOA 15...

Page 25: ...ment Les instructions donn es dans le pr sent manuel ne dispensent pas les concepteurs les installateurs et les exploitants d un examen individuel minutieux et com plet de la configuration de l instal...

Page 26: ...enregistrer les quantit s consomm es par tous les utilisateurs Cuve Pompe Clapet antiretour Cuve Compteur de fuel Compteur de fuel Dimensionnement du compteur et des accessoires En utilisant des comp...

Page 27: ...e Le filtre mont dans l embout du compteur est un simple filtre de s curit et trop petit pour servir de collecteur d impuret s Isolation thermique Le dispositif compl mentaire ne doit pas tre recouver...

Page 28: ...Ils seront marqu s aller et retour lors de l talonnage et du contr le final le montage devra donc s effectuer dans la conduite correspondante Particularit s pour les applications marines Sur les navir...

Page 29: ...vertures fermetures rapides de la vanne sont viter coups de b liers Les coups de b liers peuvent endommager les compteurs Circuit lectrique Les circuits et installations lectriques sont soumis des pre...

Page 30: ...dispositifs d arr t Effectuez un test de pression Contr lez l tanch it Rincez les conduites de fa on en liminer tous les r sidus Rel chez la pression et remettez l installation hors service Ce test de...

Page 31: ...le menu de param trage 1 sortie digitale libre de potentiel Rel 1 librement param trable sur l une des trois fonctions mentionn es ci dessous 1 sortie analogique passive 4 20 mA proportionnelle au d b...

Page 32: ...plaque signal tique Syst me de contr le temp rature ambiante 10 C 70 C commutateur d tecteur de proximit selon IEC 60947 5 6 NAMUR tension de coupure 5 15 V DC ondulation r siduelle 5 courant de coupu...

Page 33: ...n purger l installation Eviter les coups de b liers pour ne pas endommager le compteur Des inclusions d air causent des erreurs de mesure quel que soit le type de compteur et peuvent l endommager Cont...

Page 34: ...et le nettoyage la chambre de mesure et le piston rotatif des compteurs DN 15 50 peuvent tre enlev s du compteur sans le d monter de la conduite Le cycle de nettoyage et de r vision d pend fortement...

Page 35: ...h1 p r DN15 165 105 260 95 45 65 G 3 4 G 1 2 DN20 165 105 260 105 54 74 G 1 G 3 4 DN25 190 130 305 115 77 101 G 11 4 G 1 DN40 300 210 440 150 116 153 G 2 G 11 2 DN50 350 280 165 166 209 VZF VZFA VZO V...

Page 36: ...HLERS H HERMANN EHLERS H HERMANN EHLERS GMBH GMBH GMBH GMBH F rdern Messen Regeln Dosieren Verdichten F rdern Messen Regeln Dosieren Verdichten F rdern Messen Regeln Dosieren Verdichten F rdern Messen...

Reviews: