Issue (Auto VI) & V3.6t 07/12/00
System Settings
SUCTION
OIL
==SE tUp=
Press
“
@
next
”
to sequence through Setup selections
DISCHARGE
FILTER
Press
“
@
raise
”
or
“
@
lower
”
to change settings
==== syst
Press
“
@
accept
”
to accept settings
Starts per hour
sHnn
nn = 02 to 19
Loading pulse width
Lpnn
nn = 2 to 50 % ( % of 6 Second Pulse )
Starting Pulse
Spnn
nn = 0 to 100 % ( % of 6 Second Pulse )
Initial Starting Pulse, Until at Minimum Removed.
Loading pulses when
Slide at Maximum.
LpSt
or
LpPu
= Load Pulses stopped @ max
= Load Pulses continued @ max
Unloading pulse width
Upnn
nn = 2 to 50 %
( % of 6 Second Pulse )
Pump Selection
yyyy
YYYY=PunP
PunP,
Pump Run Compressor
P-St
P-ST,
Pump Start Compressor
no-P
no-P,
No Pump Compressor
FiLt
FiLt, Special, Contact Guardian.
Oil Differential alarm trip
delay.
dtnn
nn = 0 to 9.9 minutes
Bypass delay if ‘bY_P’
btnn
nn = 0 to 99 seconds
If 2Fan,
.
bFnn
nn = 0.5 to 9.9 Bar
Additional cut-in above setpoint of Fan1
in
Discharge, Pressure, Setpoint
NOT USED
Lbnn
Economiser back-off
retry time
Etnn
nn = 0 to 99 minutes
Motor start speed if
Inverter %
Stnn
nn = 0 to 99 %
Inverter speed
increment %
Sinn
nn = 1 to 20 %
Auxiliary relay VI-1 and
VI-2 operation mode
yyyy
YYYY=noUi
no VI or auxiliary relay control
ui-1
Switch on VI-1 output
ui-2
Switch on VI-2 output
both
Switch on VI-1 & VI-2 outputs
auto
do Auto VI (special Eprom)
2-SP
two speed motor control (see later section)
StbY
Standby compressor switch over
bY-P
Discharge bypass valve operation
FANS
2-stage condenser fans control
Summary of Contents for SCC 25
Page 12: ...Page 12 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Consultant Format SCC40 Std ...
Page 51: ...Page 51 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Drawing ...
Page 52: ...Page 52 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Wallbox Wiring ...
Page 76: ...Page 76 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard Wallbox Internal wiring ...
Page 77: ...Page 77 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard SCC 40 Drawing ...