Page 37
GUARDIAN SCC-40
Issue (Auto VI) & V3.6t 07/12/00
CONTROL
COMPRESSOR CONTROL OPERATION
POWER UP
After a power up the controller checks the integrity of the parameters it maintains
in EEROM memory. If this check fails the controller will go to the OFF MANUAL
mode. Otherwise these parameters are used and the controller reverts to its
previous mode.
All timers are reset so that the compressor cannot restart until the time after stop
timer has elapsed (2 mins). This will give the operator sufficient time to change
modes etc. The controller checks for any fault conditions and if any are present
it displays the tripped status, otherwise
‘WAITING’
status is displayed
READY/WAITING
After a power reset the waiting status is displayed until the time after stop timer
has elapsed, and the temperature of the oil is greater than the inhibit start setpoint
as set in
Filter Temp Low Alarm,
after which the ready status is displayed.
If an external start/stop refrigeration signal is used then the waiting status is
displayed whilst the stop signal is present.
The controller will allow up to 20 starts per hour. It achieves this by maintaining
a time between starts timer.This timer is reset each time the compressor is
started. If this timer has not elapsed, after the compressor has stopped, then the
waiting state will be displayed for the remaining time.
Once the Ready state is indicated the controllers next actions are dependant on
the mode selected:-
i) MANUAL mode
- Provided COMPRESSOR is selected the controller will
respond to START being pressed.
ii) LOCAL AUTOMATIC
- The controller looks for the suction pressure to be above
the control band or the external refrigeration signal to go to start.
iii) REMOTE AUTOMATIC
- In a pack system of upto six compressors the
compressor with the least runtime hours and which is also in the ready state is
considered to be the Master. Once the control temperature/suction pressure goes
above the control setpoint then the Master compressor will start.
Summary of Contents for SCC 25
Page 12: ...Page 12 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Consultant Format SCC40 Std ...
Page 51: ...Page 51 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Drawing ...
Page 52: ...Page 52 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Wallbox Wiring ...
Page 76: ...Page 76 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard Wallbox Internal wiring ...
Page 77: ...Page 77 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard SCC 40 Drawing ...