Testing, commissioning & LED indications 

When  installation  is  complete,  the  device  should  be 
thoroughly  walk  tested  to  ensure  the  desired  protection  is 
being achieved, and any adjustments to the device are made 
to cater for the specific location and any local site conditions. 

Note

:  LED’s  are  disabled  during  normal  use  if  the  RLED 

switch is ON. 

State 

Colour 

Flash 

Warm up 

 

Flash 0.5s on 0.5s 

off 

Alarm 

 

 

PIR only on 
GD20/GCD 

 

 

MW only on 
GD20/GCD 

 

 

Walk test 

Walk  test  all  devices  to  ensure  you  have  adequate 
coverage,  and  that  there  are  no  obstructions  in  the 
detection area. 

GD20 & GCD Microwave Range Adjustment 

Devices  are  supplied  with  the  microwave  adjustment 
potentiometer set at the mid- point. 

The microwave should be adjusted according the area to 
be protected, and great care should be taken to ensure 
the microwave cannot “see” beyond protected area. LED 
indication of the microwave 

pickup allows for accurate 

setting of the detection area. 

 

Power up the device 

 

Walk test the device taking note of the

 LED 

indications. 

 

Adjust the Microwave range until the desired 
coverage is achieved. 

 

GD2

0 Microwave

 Coverage 

 

GCD Microwave Coverage 

 

Resistance & voltage readings 

Resistance and voltage readings should be recorded at the 
time of installation. 

 

Voltage readings should be taken at the device 

 

Resistance reading should be taken at the CIE or 
ACE where the circuit is terminated. 

 

Summary of Contents for GCD

Page 1: ... anti clockwise Slide the front down and towards you to remove For ceiling mount devices remove the facia by turning it anti clockwise and then unlock as above Figure 1 Locking Mechanism Figure 2 Ceiling facia removal Mounting and cable entry Location Ensure you have the correct device for the intended application and that it is sited correctly in the desired location The field of view should be fr...

Page 2: ...imum stability When corner mounting care should be taken to ensure the chassis is not twisted if the corner is uneven then two fixings on the same side would be acceptable Where removal from mounting detection is required you must ensure that the tamper fixing is opposite to at least one of the corner or wall fixings Dependent on the mounting substrate suitable fixings may be required The size and typ...

Page 3: ...ies are used care should be taken to ensure that the cable passes around the post as shown This helps avoid cable snagging when refitting the front chassis NOTE Do not use the screw fixing points to route cable Corner mount Wall ceiling flat surface mount Cable routing Terminal Block tilt ...

Page 4: ...identification Terminal block identification 1 to Aux 12V 2 to Aux 0V 3 A Alarm 4 B Alarm 5 C Tamper 6 D Tamper 7 RLED can be used to control the LED for walk testing Terminal block RLED terminal The RLED Remote LED terminal can be used to control the LED for walk testing from the panel To use the RLED feature put switch 1 in the up position which will disable the LED When an output is triggered 0V ...

Page 5: ...D CloakWise is a proprietary detection algorithm that can distinguish the presence of an intruder even if the unauthorised person attempts to mask or cloak their presence Utilising advanced signal processing techniques to both microwave and PIR channels the CloakWise technology can recognise cloaking attempts and detect accordingly CW mode will also provide excellent detection when the ambient tem...

Page 6: ...n area GD20 GCD Microwave Range Adjustment Devices are supplied with the microwave adjustment potentiometer set at the mid point The microwave should be adjusted according the area to be protected and great care should be taken to ensure the microwave cannot see beyond protected area LED indication of the microwave pickup allows for accurate setting of the detection area Power up the device Walk t...

Page 7: ...7 13 P N MAINST GUARDALLPIR REV 1 0 ISS 15MAR21 Variants Guardall GP15 G2 Coverage Pet Coverage ...

Page 8: ...8 13 P N MAINST GUARDALLPIR REV 1 0 ISS 15MAR21 Guardall GQ20 G2 Coverage Pet Coverage ...

Page 9: ...9 13 P N MAINST GUARDALLPIR REV 1 0 ISS 15MAR21 Guardall GD20 G2 Coverage Pet Coverage ...

Page 10: ...10 13 P N MAINST GUARDALLPIR REV 1 0 ISS 15MAR21 Guardall GCQ DO NOT USE Guardall ...

Page 11: ... AFU 0004 Screws Fixings To ensure maximum stability 2 screws should be used for either mounting option Dependent on the mounting substrate suitable fixings may be required The size and type will depend on the choice of fixing screw Ceiling mount No 6 No 8 CSK 15 25mm Wall mount No 6 Pan head 15 25mm Ceiling mount installation ...

Page 12: ...ting Temperature Weight GP15 GQ20 GCQ 9 3mA GD20 11 5mA GCD 15 5mA 0 95 non condensing 10 C to 55 GP15 GQ20 GCQ no ring or fascia 106g GP15 GQ20 with fascia and insert 124g GCQ with ring 163g GD20 CD no ring or fascia 110g GD20 with fascia and insert 128g GCD with ring 167g Dimensions Wall Mount Width 65mm Height 112mm Depth 43mm Ceiling Mount 125mm Diameter Depth 43mm Regulatory information Manuf...

Page 13: ...s product for specific applications In no event is Carrier Fire Security Australia Pty Ltd responsible or liable for any damages incurred by the buyer or any third party arising from its use or their inability to use the product Guardall is a Carrier brand Contact information For contact information see www firesecurityproducts com au ...

Reviews: