- Tighten the clamps only after tightening the cables in their power terminals.
-
Perform the cables so that when the clamp is tightened, they do not strain the power terminals.
R.E.P.O.
This isolated input is used to turn off the UPS remotely in case of emergency.
This UPS is provided from the factory with “Remote Emergency Power Off” (R.E.P.O.) terminals short-circuited (
see "Views of
the UPS connections"
). If it is to be installed, remove the short-circuit and connect to the normally closed contact of the stopping
device by using a cable that ensures a double isolation connection.
In case of emergency, the R.E.P.O.control is opened by activating the stopping device; the UPS enters stand-by mode (see "USE"
section) and powers off the load completely.
The R.E.P.O circuit is self-powered with SELV type circuits. Therefore, no external power supply voltage is required. When closed
(normal condition) a maximum current is present.
E
XTERNAL
S
YNC
This non-isolated input can be used to synchronise the inverter output with an opportune signal coming from an external source.
If it is to be installed it is necessary to:
Use an isolation transformer with an isolated single-phase output (SELV) within the range 12÷24Vac with a power
0.5VA
Connect the transformer secondary to the "EXTERNAL SYNC" terminal (see
"Views of the UPS connections”)
using a
double isolation cable with a 1mm2 cross section. Warning: always respect the polarisation as in the figure below:
After installation, enable the control using the configuration software.
Summary of Contents for SATURN
Page 2: ......
Page 40: ...40 MENU DISPLAY ...
Page 60: ...60 ...
Page 98: ...98 MENU DISPLAY ...
Page 118: ...118 ...
Page 156: ...156 DISPLAY MENÜ ...
Page 176: ...176 ...
Page 214: ...214 MENU AFFICHEUR ...
Page 234: ...234 ...
Page 272: ...272 MENÚ PANTALLA ...
Page 292: ......
Page 293: ......
Page 294: ...0MNSATURNK30NP5LUC ...