1.1 Introduction 

This chapter introduces the relevant requirements for positioning and cabling of the Modular UPS and related 

equipment. Because each site has its requirements, it is not the aim of this chapter to provide step-by-step 

installation  instructions,  but  to  act  as  a  guide  for  the  general  procedures  and  practices  that  should  be 

observed by the installing engineer. 

Warning: installation can only be done by authorized engineers 

Do not apply electrical power to the UPS equipment before the commissioning engineer arrives at installation site. 

The UPS should be installed by a qualified engineer in accordance with the information contained in this chapter. All the 

equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation information. 

 

Note: 3-Phase 4-Wire Input Power is required 

The  standard  UPS  system  can  be  connected  to  TN,  TT  AC  distribution  system  (IEC60364-3)  of  3-phase 

4-wire, and a 3-wire to 4-wire conversion transformer is provided as an optional part.   

 

WARNING: battery hazards 

SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED WITH 

THIS EQUIPMENT. 

After battery connection, the battery terminals voltage will exceed 400Vdc and is potentially lethal. 

Follow the suggested actions here below: 

 

Eye protection must be worn to prevent injury from accidental electrical arcs. 

 

Remove rings, watches and all metal objects. 

 

Only use tools with insulated handles. 

 

Wear rubber gloves. 

 

If  a  battery  leaks  electrolyte,  or  is  otherwise  physically  damaged,  it  must  be  replaced,  stored  in  a 

container resistant to sulfuric acid and disposed of in accordance with local regulations. 

 

If  electrolyte  comes  into  contact  with  the  skin,  the  affected  area  should  be  washed  immediately  with 

water.

 

1.2 Initial Checking 

Before installing UPS, please check these items as below: 

1. Visually examine if there is any damage inside and outside the UPS rack and battery equipment due to the 

transportation. Report any such damage to the shipper immediately. 

2. Verify the product label and confirm the correctness of the equipment. The equipment label is attached on 

the back of front door. The UPS model, capacity and main parameters are marked on the label. 

1.3 Location 

1.3.1 UPS Location 

The UPS is intended for indoor installation and should be located in a cool, dry and clean environment with 

adequate  ventilation  to  keep  the  environmental  parameters  within  the  specified  operating  range  (see 

Table.9-2).   

Improper use of UPS and in condition out of the operating range invalid the warranty. 

Avoid to install the UPS in room which are exposed directly under sunlight or near sources of hot air. 

警告

  

危 险

   

警告

  

危 险

   

警告

  

危 险

   

Summary of Contents for MUST400T

Page 1: ...Quick Start Modular UPS MUST400T...

Page 2: ...urer approved accessories only WARNING high earth leakage current Earth connection is critical before connecting the input supply include both utility supply and battery Earth leakage current introduc...

Page 3: ...mal manner following the recommended operating procedures in this manual Battery voltage higher than 400Vdc All the battery maintenance and servicing procedures involving internal access need special...

Page 4: ...xceed 400Vdc and is potentially lethal Follow the suggested actions here below Eye protection must be worn to prevent injury from accidental electrical arcs Remove rings watches and all metal objects...

Page 5: ...re will reduce the battery life and operation below this temperature will reduce the battery capacity If the average operating temperature of battery is increased from 20 C to 30 C then the service li...

Page 6: ...20 C to 25 C The batteries are at maximum efficiency in this temperature range for information about the battery storage and transportation as well as the environment refer to Table 9 2 This equipmen...

Page 7: ...power terminals inside the UPS and all service activity it is recommended to leave enough free space to enable the passage of personnel with the doors fully opened It is important to leave a distance...

Page 8: ...Quick start_MUST400T_ENG_REV00 8 a 10 module cabinet b 6 module cabinet Fig 1 1 UPS Structure...

Page 9: ...xing holes on both sides of the front panel of the module See fig 1 2 Fig 1 2 Power Module Installation Diagram 1 4 9 Cable Entry Cables can enter into the UPS system both from bottom and top Cable en...

Page 10: ...e RCD device installed upstream of the input supply should be comply with Sensitive to DC unidirectional pulses class A in the network Insensitive to transient current pulses Have an average sensitivi...

Page 11: ...ermining the size of the output and bypass neutral cable as the current circulating on the neutral cable may be greater than nominal current in the case of non linear loads which is usually 1 732 time...

Page 12: ...ut Connections 4 For common bypass and rectifier inputs connect the AC input supply cables to the UPS bypass terminals X2 L21 L22 L23 X1 N1 Refer to Fig 4 11 and tighten the connections to 5 Nm M6 Bol...

Page 13: ...d the critical load and tighten the terminals screws to 5Nm M6 Bolt or to 13Nm M8 Bolt or to 25Nm M10 Bolt Note ENSURE CORRECT PHASE ROTATION WARNING If the load equipment will not be ready to accept...

Page 14: ...an die USV abschlie en Ein Differentialschutz ist ratsam Conectar el cable de tierra a el SAE Se aconseja la protecction con el interruptor diferencial Attenzione batterie interne non aprire pericolo...

Reviews: