FAILURE
27
ADICOS HOTSPOT-1000
410-2410-001 EN12
8.4.2 Replacing the ADICOS HOTSPOT-1000
An old ADICOS HOTSPOT-1000 has to be replaced when
•
The serviceable life of the detector has been exhausted
•
It is foreseeable that functioning will decline prematurely
•
A change in the operating conditions requires a different type of detector
When the ADICOS HOTSPOT-1000 is replaced, the parameter set from the previous device
can be imported if the following conditions are met:
•
The detector is mounted in the same position.
•
There is a data backup of the parameterization available.
•
The detector is not being replaced because the buiding is to be used for a different purpose.
To replace the detector, switch off the system and detach the old detector. Install the new
detector as described in this manual.
9 Failure
Failure of the ADICOS HOTSPOT-1000 is indicated by the yellow signal LED lighting up as well
as by the “Failure” signal relay deenergizing.
The ADICOS HOTSPOT-1000 recognizes the following states and causes of failure:
Failure
Description
Measure
Undervoltage / cur-
rent failure
Operating voltage falls be-
low 20 V (even only briefly).
Check supply voltage
and wiring; use a more
powerful or additional
power pack; self-resetting
Checksum ROM/EEPROM
The checksum is no longer
right after restart or reset.
Replace detector
Test failure
The ADICOS service
software was used to
trigger a false failure
for test purposes.
Cancel test failure with
ADICOS
service software
Sensor fault
The IR sensor is defective
Replace detector
Undertemperature
Failure is triggered below
the default temperature limit
(inside temperature: -15 °C)
Use the detector heat-
er or insulate the de-
vice sufficiently
Use the ADICOS service software to precisely analyze the failure states!