7.2.4 Alarm Delay
The alarm delay is a parameter that can optionally be set via the ADICOS service software.
The purpose of the alarm delay is to prevent the alarm from being triggered until the alarm
conditions have been met for a previously defined minimum time (in minutes).
WARNING!
Incorrect parameterization of the alarm delay can cause the detector to fail.
• Detector parameters may be modified only by properly trained personnel!
• When in doubt, consult the manufacturer!
7.2.5
Pre-alarm
If the ADICOS HOTSPOT-1000 is equipped with a pre-alarm module and properly configured,
set 2 of the saved limit combinations automatically acts as the trigger criterion for the pre-
alarm. If the limits specified in set 2 are exceeded, the pre-alarm module relay switches and
the red signal LED “Alarm” flashes.
7.2.6
Peak Suppression
In some cases it makes sense to ignore when thresholds being exceeded only briefly. For
example: In a building where combustibles are stored and where vehicles drive in and out, the
short-term effects of the passing vehicles can be ignored. The hot exhaust pipes or reflections
from the shiny metal surfaces should not trigger an alarm.