GST301 Extinguishing Control Panel
Installation and Operation Manual
Page 3
2) Indicators
Power
Green. Lighted when power supplied.
AC Fault
Amber. Lighted when there is AC Fault.
Batt Fault
Amber. Lighted when battery voltage is below 5V.
Gas Release
Red. Flashes during delay time. Lighted after gas
released. Extinguished by reset.
Fire
Red. General fire indication. Lighted by any fire signal.
Extinguished by reset.
Silence
Green. Lighted if the panel is silenced. Extinguished when
it re-sounds.
Auto Enable
Green. Lighted if the panel is in automatic mode. Off for
manual only mode.
Evacuate
Green. Flashes when “Evacuate” key is pressed.
Extinguished by reset.
DELAY TIME
Red. Indicating the time (in second) before gas releasing.
Zone1 ACTIVE
Red. Flashes when Zone1 is in alarm. Lighted steadily
after it’s silenced. Extinguished by reset.
Zone1 Fault/ISO
Amber. Flashes when Zone1 has any fault. Off when the
fault is removed. Steadily lighted when Zone1 is isolated.
Zone2 ACTIVE
Red. Flashes when Zone2 is in alarm. Lighted steadily
after it’s silenced. Extinguished by reset.
Zone2 Fault/ISO
Amber. Flashes when Zone2 has any fault. Off when the
fault is removed. Steadily lighted when Zone2 isolated.
Aux Zone ACTIVE
Red. Flashes when the AUX Zone is in alarm. Lighted
steadily after it’s silenced. Extinguished by reset.
Aux Zone Fault/ISO
Amber. Flashes when the AUX zone has any fault.
Steadily lighted when the AUX zone is isolated. OFF
when the fault is removed.
Cylinder ACTIVE
Green. Flashes when the release output is active.
Extinguished after output finished.
Cylinder FAULT/ISO
Amber. Flashes when the gas release output circuit has
any fault. Lighted steadily in isolated mode.
Start ACTIVE
Green
. Flashes when the “START” key on the panel or the
Emergency Start Button in field is pressed.
Start FAULT
Amber. Lighted by fault with Emergency Start Button
Circuit. Extinguished when fault removed.
Stop ACTIVE
Green
. Flashes when the “STOP” key on panel or the
field Emergency Abort Button is pressed.
Stop FAULT
Amber. Lighted by fault with Emergency Abort Button
Circuit. Extinguished when fault removed.
Pressure Switch ACTIVE Green. Lighted if the pressure switch is active (gas
released) or after gas release output started (no pressure
switch). Extinguished by reset.