GST301 Extinguishing Control Panel
Installation and Operation Manual
Page 12
2) Configuring the Emergency Start Button
Press the emergency start button in field can start the gas release with or without
delay. Short X1
(on the display board) to set with delay and remove the jumper to
set without delay. Default setting is with delay.
3) Configuring the discharge output
The discharge output can be started by pressure switch or directly by gas release
output. Short X2
(on the display board) to set as using pressure switch, remove the
jumper to set as not using pressure switch (active after gas release output). Default
setting is using pressure switch.
4) Configuring the remote output type
The discharge, fire, fault remote output types can be changed to normally-open or
normally-closed dry contact type through setting X5, X4, X6. X5 for discharge
remote output. X4 for fire remote output. X6 for fault remote output.
Setting method for X4, X5, and X6 is shown in Fig. 15.
Fig. 15 Remote output setting
5) Setting gas release delay time
The gas release delay time can be set from 0 to 90 seconds by adjusting S1 (on the
display board). Details are shown in Table 1. Default set is 30s.
Table 1
Position of S1
0
1
2
3
4
5
6
7
8
9
Delay time
0
10
20
30
40
50
60
70
80
90
6) Setting gas release output pulse duration
The gas release output is in pulse type. The pulse duration can be set from 2 to 45
seconds by adjusting S2
(on the display board). Details are shown in the following
table. Default setting is 5 seconds. See Table 2.
Table 2
VI Operation
1
Cause and Effect
The following table shows the actions of the panel under different conditions.
Position of S2
0
1
2
3
4
5
6
7
8
9
Pulse duration
2
5
10
15
20
25
30
35
40
45