GST301 Extinguishing Control Panel
Installation and Operation Manual
Page 11
Fig. 13 Typical system connection
6
Commission
1) Configuring the outputs
Defaults of sounder outputs and gas release output are at 24VDC Active type. To
meet the condition on site, these outputs can be changed to normally-open or
normally-closed dry contact output. These output types can be configured through
X1, X2, X3, F3, F4, F5 (on the main board).
X1 and F3 is used to set SOUNDER 1, X2 and F4 for SOUNDER 2, and X3 and F5
for gas release output. Please refer to Fig. 14 below to set X1, X2 or X3.
Fig. 14 Output configuration
Note: if the output type is configured to normally-open or normally-closed
dry contact, the current fuse (F3, F4 or F5) must be removed.