GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 5
2.4 Detecting Loop Parameters
LOOP OUT (
+
,
-
):
Polarized signal cable from the FACP connecting up to 235
addressable devices.
LOOP IN (
+
,
-
):
Polarized signal cable returning to the FACP.
Output Voltage: 21V
~
27V pulse
Output Current: 0mA
~
300mA
Type of Loop: Class A loop
Recommended Wiring (subject to local installation codes):
GST FireCable ® 2E/1.0 2 core and Earth 1mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1mm
2
CSA
Recommended Cable Length
≤
1000m
2.5 Output Loop Parameters
Recommended Wiring (subject to local installation codes):
GST FireCable ® 2E/1.0 2 core and Earth 1mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1mm
2
CSA
Recommended cable length
≤
1000m
2.5.1
FIRE ALARM OUTPUT (+, -)
Output Voltage: 21VDC
~
27VDC
Output Current: 0mA
~
500mA
End of Line Resistor: 4.7k
Ω
1.1.1
F.P.E. OUTPUT (+, -)
Output Voltage: 21VDC
~
27VDC
Output Current: 0mA
~
500mA
End of Line Resistor: 4.7k
Ω
2.5.2
SOUNDER CIRCUIT OUTPUT (+, -)
Output Voltage: 21VDC
~
27VDC
Output Current: 0mA
~
500mA
End of Line Resistor: 4.7k
Ω
2.5.3
FAULT OUTPUT (NC, COM, NO)
Contact Capacity: 24VDC @1.0A
In fault state, NC and COM open, NO and COM close.
2.6 Dimensions
400mm
×
560mm
×
182mm
Summary of Contents for GST200