GST-NRP00/GST-NRP00-HU/GST-NRP00-PT
Network Repeater Panel Installation and Operation Manual
In the above screen, you can operate as follows:
Enter 3-digit zone number or “*” at the cursor position after letter “Z”.
Enter 3-digit device code or “*” at the cursor position after letter “C”.
Enter 2-digit device type or “*” at the cursor position after letter “T”.
Example 1, in order to disable a photoelectric detector whose device code is 001 in
Zone 1, you need to input in sequence the zone number 001, device code 001 and
device type 03.
Example 2, in order to disable all alarm devices with device type between 01 and 11 in
Zone 1, you need to input in sequence the zone number 001, device code *** and
device type **. Please note that the asterisk mark “**”is not allowed to use for action
devices whose device type between 12 and 65.
In the screen as in Fig. 6-8, inputting number 2, you can enter device enable screen as
shown in Fig. 6-10. In this screen, you can enable the device. Refer to description below
Fig. 6-9 for operations.
Fig. 6-10
In the screen as in Fig. 6-8, inputting number 3, you can enter Delete Net Disable
screen as shown in Fig. 6-11. In this screen, inputting number of disable information,
and pressing
Enter
key, the disable message from connected FACP can be deleted.
Fig. 6-11
Delete Net Disable
Number
: 000
Enable
Z000C000T00NoDefine
Page 18