Network Repeater Panel Installation and Operation Manual
6.3 Instructions for Operator (Operator Password Required)
6.3.1
Resetting the System
Pressing
RESET
can reset the repeater panel and all the control modules, outputs and
detectors connected to the network FACPs, but will leave the disabled devices as they
are. The LCD displays “RESET IN SYSTEM”. LEDs will be turned off (Except for
“POWER ON” LED). “RESET” information will be written into running log. If there is still
fire alarm, fault and action not acknowledged after pressing the
RESET
key, the
repeater panel will remain relative sound indications. If all messages have been
acknowledged by pressing
RESET
key, the system returns to normal display state.
6.3.2
Checking All Visual and Audible Indications
In normal monitoring state, you can check all visual and audible indications of the
repeater panel by pressing
TEST
.
6.3.3
Silence
Pressing
SILENCE
can silence the sounders and bells.
6.3.4
Evacuation
Pressing EVAC can manually start all sounders and bell to evacuate people.
6.3.5
Disable/Enable
Devices are disabled when a device is fault and the fault cannot be removed
immediately. This device can then be temporarily disabled and enabled after it’s
repaired.
Pressing
ENABLE/DISABLE
, the screen will be shown as in Fig. 6-8.
Fig. 6-8
In the screen as in Fig. 6-8, inputting number 1, you can enter device disable screen as
shown in Fig. 6-9.
Fig. 6-9
Disable
Z000C000T00NoDefine
*Disable/Enable*
1 Disable Devices
2 Enable Devices
3 Delete Net Disable
Page 17