GST-NRP00/GST-NRP00-HU/GST-NRP00-PT
Network Repeater Panel Installation and Operation Manual
001 0f 006 !FIRE! 05:25 // There are six devices with fire alarm signals, and this is
the first.
Zone: 001 030MCP // The number of zone with fire alarm and type and
address of the device in fire alarm.
Device-30 // Description of device in fire alarm.
Last !Fire! Zone:003 // Zone number of the last fire alarm.
Zone3 Device-066
// Description of the device and of that zone with the last fire
alarm.
5.2.2
Disposal of Fire Alarm Signal
When fire alarm occurs, first find out the location according to the information shown on
the repeater panel and verify if there is a real fire.
If it’s a real fire, please take corresponding measures as outlined below.
Step 1:
Evacuate people.
Step 2:
Call the fire department.
Step 3:
Initiate extinguishers.
If it is a false alarm, please take the following measures.
Step 1:
Press
SILENCE
to stop the sound.
Step 2:
Remove the causes of the false alarm.
Step 3:
Press
RESET
to make the FACP back to the normal state. If the device still
gives false alarm, disable it using a FACP in network and inform the installer or
manufacturer for repair.
5.3 Fault
5.3.1
Fault Indication
In case of fault, the repeater panel and FACPs in network display the fault message
simultaneously and light corresponding LED.
Mains fault: If the AC power of networked FACPs is down, the repeater panel
reports AC fault, and
Lights
COMMON FAULT
and
POWER FAULT
LED.
The LCD displays “AC FAULT”.
Generates fault sound.
Battery fault: The repeater panel reports battery fault if the battery voltage is lower
than 18.9V, and would:
Light
COMMON FAULT
and
POWER FAULT
LED.
The LCD displays “BATTERY FAULT”.
Page 10