for smoke entry testing. Set the generator to represent 4%/ft to 5%/ft 
obscuration  as  described  in  the  Trutest  manual.  Using  the  bowl 
shaped applicator, apply aerosol until the panel alarms. 

Additionally, canned aerosol simulated smoke (canned smoke agent) 
may  be  used  for  smoke  entry  testing  of  the  smoke  detector. 
Recommended aerosol smoke products are: 

Manufacturer 

Model 

Trutest 

AERO400 

When used properly, the canned smoke agent will cause the smoke 
detector  to  go  into  alarm.  Refer  to  the  manufacturer’s  published 
instructions for proper use of the canned smoke agent. 
3) 

After testing, cut off the power above 10 seconds and reset the 

detector  and  then  notify  the  proper  authorities  that  the  system  is 
back in operation.   

Warning:

  Canned  aerosol  simulated  smoke  (canned  smoke  agent) 

formulas  will  vary  by  manufacturer.  Misuse  or  overuse  of  these 
products may have long term adverse  effects  on the smoke detector. 
Consult  the  canned  smoke  agent  manufacturer’s  published 
instructions for any further warnings or caution statements. 
When  testing  is  complete,  restore  the  system  to  normal  operation 
and notify the proper authorities that the system is back in operation.  

Maintenance

 

1.  The  detector  must  be  cleaned  once  a  year  to  ensure  normal 

operation of the system. 

2.  Before cleaning, notify the proper  authorities that the  system is 

undergoing maintenance  and will temporarily be  out of service. 
Disable  the  zone  or  system  undergoing  maintenance  to  avoid 
unwanted alarms. 

Chamber Clearing Steps: 

a)  Open the top cover  of detector,  and draw  out the sensing 

chamber  by  slightly  lifting  its  two  sides  using  a  straight 
screwdriver, as shown in Fig. 6.

 

b)  Use  a  vacuum  cleaner  or  cleaned,  compressed  air  to 

remove dust and debris from the insect guard and the sensing 
chamber.  The  sensing  chamber  can  also  be  cleaned  by  clear 
water  and  brush.  Put  the  sensing  chamber  in  clean  water  to 
brush the dust inside and take out to dry it. 

 

c)  Install the sensing chamber and the top cover back.

 

Cautions   

1.  Dust  covers  can

’t be  removed  until the project is  put into use 

formally. Take well care of dust covers for future use.   
2.  Dust covers effectively but not absolutely prevent dust particles 
from  going  into  detectors.  So,  we  recommend  that  detectors 
should  be  removed  prior  to  construction,  decoration,  or  other 
activities producing dust. The proper authority should be informed 
of detectors removing.   
3.  Be careful not to damage the detector in maintenance. 
4.  The  smoke  detector  may  not  sense  fire  that  where  smoke 
cannot reach it, such as  in chimneys, in walls, on roofs, or  on the 
other side of closed doors. 
5.  The detector cannot monitor the place beyond protection area. 
6.  The  detector  may  not  warn  you  about  fires  caused  by 
insufficient  safety  measures,  violent  explosions,  leaking  gas, 
improper  storage  of  flammable  materials  like  diluents  and  other 
safety hazards, arson or children playing with fire. 
7.  The  alarm  of  a  smoke  detector  used  in  high  velocity 
environment  will  be  delayed  due  to  dilution  of  smoke  by  frequent 
and fast airflow.   
 
 
 
 
 
 
 
 
 
 

8.  Smoke  detectors  have  their  own  service  life.  In  order  to  keep 
the  detector  working  in  good  condition,  please  maintain  them 
according  to  recommendations  from  manufacturers  and  relative 
state standards. 
9.  The detectors must be tested regularly, at least once a year. 
10. Smoke  detectors  are  not  to  be  used  with  detector  guards 
unless the combination has been evaluated and found suitable for 
that purpose. 

Specification

 

Operating Voltage 

16VDC

28VDC 

Standby Current 

6

0μA 

Alarm Current 

55mA 

Fire LED 

Red, flash in polling and illuminate in 
alarming. 

Remote indication 
output 

Polarity-sensitive output, directly connecting 
with remote indicator (built in 10k resistor in 
series, max. output current is 2mA); don

’t 

illuminate when in normal; flash in alarming. 

Max. ripple 
voltage 

2V(peak to peak value) 

Alarm reset 

Instant power down (10s Min, 1.0VDC Max 

Wiring 

Two-wire, polarity sensitive. 

Sensitivity Range 

1.23%~3.20% per ft 

Environment 
Temperature 

32

℉(

0

℃)~

100

℉(

+37.8

℃)

 

Relative Humidity 

95%, non condensing 

Material and color 

ABS, white (RAL 9016) 

Ingress Protection 
Rating 

IP2X 

Dimension 

Diameter:100mm Height: 44.5mm (without 
base) 

Mounting Hole 
Spacing 

45mm-75mm 

Weight 

About 110g 

Accessories and Tools

 

Model 

Name 

Remark 

P-9910B 

Hand held programmer 

Supplied separately 

DB-M01 

Base 

Supplied separately 

T-MT 

Commission tool 

Supplied separately 

C-9314P 

Remote Indicator 

Supplied separately 

BP-9314P 

Base  Plate  for  Remote 
Indicator 

Supplied separately 

Limited Warranty

 

GST

  warrants  that  the  product  will  be  free  from  defects  in  design, 

materials  and  workmanship  during  the  warranty  period.  This 
warranty  shall  not  apply  to  any  product  that  is  found  to  have  been 
improperly  installed  or  used  in  any  way  not  in  accordance  with  the 
instructions  supplied  with  the  product.  Anybody,  including  the 
agents, distributors or employees, is not in the position to amend the 
contents  of  this  warranty.  Please  contact  your  local  distributor  for 
products not covered by this warranty. 

 