SPECIFICATIONS

Model Number:

ADH

Electrical Rating:

120 VAC, 60 HZ, 80mA, max, 9 volt battery back-up

Interconnect Quantity:

18 alarms maximum, no more than 12 can be smoke

alarms
U.L. Alarm Point temperature:

58°C (135°F) fixed temperature

U.L. Maximum ambient               
temperature at unit:

38°C (100°F)

Operating temperature:

-23°C to 70°C (-10°F to 158°F)

U.L. Recommended coverage: 232 sq.m. (2500 sq.ft) See Note A.
U.L. Recommended spacing:

15 meters (50 feet)

Maximum distance from wall:

7.5 meters (25 feet) See Note B

NOTE A:

Maximum alarm coverage has been determined by UL to provide detection time

equal to sprinkler devices spaced at 3 meter (10 foot) intervals (9.25 sq m/100 sq ft area) on
a smooth ceiling 4.8 meters (15.75 feet) high. Higher ceilings can adversely affect detection
time. In some instances, earlier detection may be obtained by reducing the distance
between detectors. See the latest edition of the NFPA 72E, Automatic Fire Detectors.

NOTE B:

Maximum distance is measured from any wall partition or ceiling projection

extending down more than 30.5 cm (12 in).

HEAT ALARM FEATURES

• This heat alarm is powered by 120V AC and a 9-volt battery back-up

source. AC/DC heat alarms offer added protection in the event of a
power failure or a drained battery.

• Unique power connector prevents interconnection with incompatible

heat alarms, smoke alarms, or security systems.

• This heat alarm is interconnectable to a maximum of 18 alarms, no more

than 12 of which can be smoke alarms. This alarm can be interconnect-
ed only with Firex devices. It is interconnectable with Firex models ADH
(5700 Series), G-6 (406 Series), G-18 (418 Series), PG (484 Series), ADC
(4518 Series), FADC (4618 / 5000 Series), TPCI (4671 Series), COE
(10000 Series), COEA (10400 Series), FADCM (12000 Series), and GCM
(12400 Series). It is NOT interconnectable with the Firex model FXW-R
(428 Series).

• Optional tamper-resist feature. 
• Unique “battery missing” lockout – heat alarm will not attach to the

mounting bracket if a battery is not in the battery pocket.

• I m p roperly connected or weak battery signal – heat alarm will sound a

s h o rt beep once a minute if the battery is weak or improperly connected.

• Green LED indicates that the heat alarm is receiving AC power, working

under normal operation, or in alarm.

• Loud alarm horn—85 decibels at 3 meters (10 feet)—sounds to alert you

to an emergency.

• Test button checks heat alarm operation.

I M P O RTANT SAFETY INFORMAT I O N

PLEASE READ AND SAVE 

THESE INSTRUCTIONS

W A  R  N  I  N G

This heat alarm requires constant 120-volt, AC power AND a work-
ing 9-volt battery to operate properly.

This heat alarm WILL NOT work

if AC power is not connected, has failed, or has been interrupted for any
reason AND if the battery is removed, drained or improperly connected.
DO NOT use any other kind of battery except as specified in this manu-
al. DO NOT connect this heat alarm to any smoke alarm, heat alarm, or
auxiliary device, except those listed in this manual.

The Push-to-Test button accurately tests all heat alarm functions.

For temperatures that are below -23°C (-10°F) use a hand held hair dryer
and blow hot air into heat alarm to test.  DO NOT use any other test
method. 

Test heat alarm weekly to ensure proper operation. 

This heat alarm should be installed only by a licensed, qualified
electrician. 

Observe and follow all local and national

electrical and

building codes for installation.

!

1

120V AC
Heat Alarm

with 

9 V

B a t t e ry 
B a c k - u p

352-00107-001 Rev A

MODEL ADH

PLEASE READ AND SAVE

THIS MANUAL

Installer: Please leave this
manual with the pro d u c t .

WARNING!

Heat alarms are not life safety devices and are not designed to

detect smoke or fire. Heat alarms detect temperatures of 135°

F

or greater,

and are intended to be used as supplements to smoke alarms by pro v i d i n g
early warning. See the IMPORTANT SAFETY INFORMATION section of this
manual.

Printed information describing proper installation, operation, testing,
maintenance, evacuation planning, and repair service is provided with
this equipment in this manual.

Summary of Contents for ADH

Page 1: ...ockout heat alarm will not attach to the mounting bracket if a battery is not in the battery pocket Improperly connected or weak battery signal heat alarm will sound a shortbeep once a minute if the battery is weak or improperly connected Green LED indicates that the heat alarm is receiving AC power working under normal operation or in alarm Loud alarm horn 85 decibels at 3 meters 10 feet sounds t...

Page 2: ...T Heat alarms give an audible warning when the temperature at the alarm reaches 58 C 135 F Heat alarms are ideal for kitchens garages base ments boilers rooms attics and other areas where there are normally high levels of fumes smoke or dust which are also areas where smoke alarms should not be installed due to risk of false nuisance alarms For your information the National Fire Protection Associa...

Page 3: ...arning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows A heat detector installed in each separate sleeping area in the vicinity but outside the bedrooms and heat or smoke alarms in the living rooms dining rooms bedrooms kitchens hallways attics furnace rooms closets utility and storage rooms basements and attached g...

Page 4: ...nnect wire location shall be in accordance with NEC Article 300 3b THIS HEAT ALARM SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION S STANDARD 72 National Fire Protection Association Batterymarch Park Quincy MA 02269 Install heat alarm on a 10 cm 4 inch octagon or single gang junction box only 1 From back of heat alarm remove mounting plate To deter a person from tam...

Page 5: ...OE 10000 Series COEA 10400 Series FADCM 12000 Series and GCM 12400 Series It is NOT interconnectable with the Firex model FXW R 428 Series Connect heat alarms to a single AC branch circuit If local codes do not permit be sure the neutral wire is common to both phases RED AND GREEN LED INDICATORS This heat alarm features separate red and green LED indicators The LEDs indicate the following GREEN LE...

Page 6: ...attery from pocket Disconnect and discard drained battery from battery connector 7 Connect a fresh 9 volt battery to connector The battery will fit only one way Be sure battery connector is securely attached to battery terminals 8 Place battery into battery pocket 9 Close battery pocket door Push down until it snaps into place 10 Replace connector plug Connector will snap into place Gently tug con...

Page 7: ...at main fuse box or cir cuit breaker before taking trouble shooting action WARNING DO NOT disconnect battery or AC power to quiet an unwanted alarm This will remove your protection Fan the air or open a win dow to remove heat or dust PROBLEM SOLUTION Heat alarm does not 1 Check that AC power is sound when tested turned on 2 Tu rnoff power Remove heat alarm from mounting plate mounting plate and a ...

Page 8: ...ARRANTIES OF MERCHANTABILITY AND FIT NESS FOR A PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF FIVE 5 YEARS FROM PURCHASE DATE Some states do not allow limitations on how long an implied warranty lasts so the above limitations may not apply to you IN NO CASE SHALL INVENSYS CONTROLS BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED WHAT...

Page 9: ... fixé au support de fixation si le compartiment de pile est vide Signal de pile faible ou de mauvaise connexion Le détecteur de chaleur émettra un bip court une fois par minute pour signaler que la pile est faible ou mal installée Le voyant DEL vert indique que le détecteur de chaleur reçoit du courant alternatif fonctionne normalement ou est en alerte L avertisseur sonore 85 décibels à 3 mètres 1...

Page 10: ...ies et leurs biens De plus le détecteur de chaleur peut cesser de fonctionner à n importe quel moment EMPLACEMENT DES DÉTECTEURS DE CHALEUR Les détecteurs de chaleur émettent un avertissement audible lorsque la température atteint 58 C 135 F au niveau du détecteur Les détecteurs de chaleur sont idéals pour les cuisines les garages les sous sols les chaufferies les greniers et tout autre endroit où...

Page 11: ...haleur dans chaque aire séparée de couchage à proximité mais à l extérieur des chambres à coucher et des détecteurs de fumée et de chaleur dans le salon la salle à manger les chambres la cuisine l entrée le grenier la salle de la chaudière les placards les pièces de stockage la buanderie le sous sol et le garage 3 INSTALLATION DE DÉTECTEUR DE FUMÉE Installez un détecteur de chaleur le plus près po...

Page 12: ...eut s appliquer L emplacement du câblage d inter connexion doit être conforme à l arti cle NEC 300 3b CE DÉTECTEUR DE CHALEUR DOIT ÊTRE INSTALLÉ CONFORMÉMENT À LA RECOMMANDATION 72 DE LA NATIONAL FIRE PROTECTION ASSOCIATION National Fire Protection Association Batterymarch Park Quincy MA 02269 Installez le détecteur de chaleur uniquement sur une boîte de raccordement sim ple ou octogonale de 10 cm...

Page 13: ...s plus de 12 peuvent être des détecteurs de fumée Ce détecteur est compatible avec les modèles de détecteurs de fumée Firex ADH série 5700 G 6 série 406 G 18 série 418 PG série 484 ADC série 4518 FADC séries 4618 5000 TPCI série 4671 COE série 10000 COEA série 10400 FADCM série 12000 et GCM série 12400 Il n est PAS con nectable avec le modèle Firex FXW R série 428 Reliez les détecteurs de chaleur ...

Page 14: ...t de pile faible retentit à raison d une fois par minute même si le détecteur est alimenté en électricité Les piles devraient être remplacées régulièrement même lorsque le détecteur de chaleur est alimenté en élec tricité Pour ce type de détecteur de chaleur utilisez uniquement les piles sui vantes Eveready 522 ou 1222 ou Duracell MN 1604 AVERTISSEMENT N UTILISEZ QUE LES PILES INDIQUÉES DANS CE MA...

Page 15: ...X sorties pour chaque pièce et un chemin d évacuation vers l extérieur à partir de chaque sortie Apprenez à tous les membres du foyer à toucher la porte pour vérifier si elle est brûlante et d utiliser une autre sortie dans ce cas là APPRENEZ LEUR À NE PAS OUVRIR LA PORTE SI ELLE EST BRÛLANTE Apprenez aux membres du foyer à ramper sur le sol pour rester au dessous des fumées des vapeurs et des gaz...

Page 16: ... QUELQUE NATURE QUE CE SOIT MÊME SI LAPERTE OU LE DOMMAGE EST CAUSÉ PAR SA NÉGLIGENCE OU SA FAUTE Certains États ou certaines provinces n autorisentpas l exclusionou la limita tion des dommages accessoires ou indi rects parconséquent la limitation ou l exclusion ci dessus pourraitne pas s appliquerà vous La présentegarantie vous accorde des droits spécifiques reconnus par la loi et vous pourriez a...

Reviews: