background image

 

30309460 

     

                                                                                           

                         

  Issue 1.06

 

                                       

 

Features

 

 

Providing for connections to remote indicators.   

 

A magnet test available. 

 

Standard: UL268

 

Description

 

DC-M9102  Conventional  Photoelectric  Smoke  Detector  (the 
detector)  is  a  new-generation  product  by  building  in  a 
microprocessor,  embedding  a  solid  fire  analyzing  program,  and 
performing effectively and efficiently. 

Checking a fire alarm signal, the detector will send it to a fire alarm 
control panel (FACP) or addressable zone monitor unit by means of 
current changes. The detector indicates its fire condition by turning 
on fire LED and keeping the LED on until it is reset. 

Using  infrared  scattering  technology,  with  an  innovative  chamber, 
the  detector  receives  very  weak  infrared  light  under  normal 
smokeless  condition.  If  smoke  particles  enter  the  chamber,  the 
received  light  signal  will  increase  by  scattering.  When  smoke 
density reaches certain density, the detector will output fire signal. In 
order  to  reduce  interference  and  power  consumption,  the  emitting 
circuit works in pulse mode to prolong the life of IR LED.

 

Connection and cabling

 

The  detector  connects  with  our  UL  certified  GST-M200  FACP  and 
I-M9300 Module. DB-M01 base shown in Fig. 2 is used together.

 

5

45

75

Cable Entry

Mounting

Hole

 

Fig. 1                                              Fig. 2

 

Please install the base according to the following steps: 

1) 

Locate  the  mounting  holes  on  the  rubber  seal  of  the  base 
according  to  the  holes  on  the  electrical  junction  box,  and 
punch the holes with a screwdriver. 

2) 

Count  the  number  of  cables  needed  and  punch  correct 
number of holes with a screwdriver on the rubber seal at the 
cable  entry  position.  Thread  the  cables  through  the  cable 
entry holes.   

3) 

Install the base onto the junction box with screws.   

Warning:  Do  not  punch  mounting  holes  and  cable  entry  holes 
bigger than needed. Do not punch more holes than needed. 

There  are  four  terminals  with  number  on  the  base. 

“1” is connected 

with  output  anode  of  I-M9300  module; 

“2”  is  used  as  output, 

connected  with  anode  of  next  detector  (Terminal  1)  and  also 
connected  with  anode  of  remote  indicator; 

“3”  is  connected  with 

output cathode of I-M9300 module or the cathode of the power supply; 
“4” connects with the  cathode  of  remote indicator.  Connect 4.7k/1w 
resistor to terminal 2  and 3  of the  base.  Maximum 15 detectors can 
be connected to the output circuit of I-M9300 The system connection 
is shown in Fig. 3. 

Remote Indicator

O

-

O

+

I-M9300

Conventional Detector

4.7

k
Ω

 

Res

istor

Remote Indicator

Conventional Detector

 

Fig. 3 

Recommended Wiring 

1.0mm

or above fire cable for all terminals laid through metal conduit 

or flame proof conduit, subject to local codes. 

Note: Different color cables are used to avoid wiring mistake.

 

 

Installation 

Refer to 

D Series Detector Application Bulletin 

for additional installation 

instructions

Fix  the  base  with  two  taping  screws.  Then  align  A  (Fig.1)  on  the 
bottom  of  the  detector  to  B  (Fig.2)  of  the  base,  and  rotate  the 
detector clockwise to mark C.

 

Mounting of the detector is shown in Fig.4.

 

Electrical Box

Conduit

Orientation Base

Detector

54.5mm

 

Fig. 4 

Application

 

Notes:  The  alarm  current  depends  on  the  current  limit  of  the 
control  panel.  24VDC  cannot  power  the  detector  directly. 
Otherwise the detector will be blown up for lack of current limit 
resistor.

 

Testing 

Before  testing,  please  ensure  that  the  detector  has  been 
installed  correctly  and  powered  up.  After  10  seconds,  testing 
can begin.   

Before  testing,  notify  the  proper  authorities  that  the  system  is 
undergoing  maintenance  and  will  temporarily  be  out  of  service. 
Disable  the  zone  or  system  undergoing  maintenance  to  avoid 
unwanted alarms.

  

All  detectors  must  be  tested  after  installation  and  periodically 
thereafter.  Testing  methods  must  satisfy  the  Authority  Having 
Jurisdiction  (AHJ).  Detectors  offer  maximum  performance  when 
tested  and  maintained  in  compliance  with  NFPA  72.  The  detector 
can be tested in the following way:   

Test zone

                   

 

Fig. 5                                                    Fig. 6 

1) 

Magnetic test 

Magnet test zone is shown in Fig.5. Put the magnet  of commission 
tool close to the zone of the detector and hold on for a few seconds 
until the detector generates alarm.   
2) 

Smoke test 

The Trutest model 300 Aerosol Smoke Detector Tester can be used 

DC-M9102   

Conventional Photoelectric 

Smoke Detector 

Reviews: