3. Additional Information

 

 

3.1 Troubleshooting

 

 
When an error item is alarmed from the Lithium Ion Battery  Management System (LIBM 

II), take appropriate corrective actions by following the instructions shown in the table below.

 

 

 

Item 

Occurrence 
Condition 

Check Item and Process

 

1

 

Cell Voltage 
Up Error 

When the maximum 
cell voltage exceeds 
the set value 

(1) Check that the charge is stopped. If the charge continues, 

take an action such as stopping the charger or turning off 
the breaker to stop the charge. 

(2) Contact us.

 

2

 

Cell Voltage 
Down Error 

When the minimum 
cell voltage 
becomes less than 
the set value 

(1) Check that the discharge is stopped. If the discharge 

continues, take an action such as turning off the breaker to 
stop the discharge. 

(2) Contact us.

 

3

 

Battery Temp 
Up Error 

When any module 
temperature 
exceeds the set 
value 

(1) Check the battery module temperature. If the temperature 

exceeds the setting value, check that the charge/discharge 
is stopped. If the charge/discharge continues, take an action 
to stop the charge/discharge.   

(2) Check the ambient temperature. If the ambient temperature 

exceeds the battery’s operating temperature range, lower 
the ambient temperature. 

(3) Check the module temperature once the ambient 

t

emperature becomes within the battery’s operating range. If 

the module temperature remains high, contact us.

 

4

 

Battery Temp 
Down Error 

When any module 
temperature 
becomes below the 
setting value 

(1) Check the battery module temperature. If the temperature 

lowers the setting value, check that the charge/discharge is 
stopped. If the charge/discharge continues, take an action to 
stop the charge/discharge. 

(2) Check the ambient temperature. If the ambient temperature 

lowers the battery’s operating temperature range, increase 
the ambient temperature. 

(3) Check the module temperature once the ambient 

temperature becomes within the battery’s operating range. If 
the module temperature remains low, contact us.

 

5

 

Module 
Communication 
Error

 

When no reply from 
the battery monitor 
board after 30 sec. 
or longer 

(1) Check if the communication line between the battery module 

and the Lithium Ion Battery Monitor (LIBM) and the 
communication line between the modules are not 
disconnected.   

(2) Check that the charge/discharge is stopped. If the 

charge/discharge continues, take an action such as turning 
off the breaker to stop the charge/discharge. 

(3) If there is no problem, contact us.

 

6

 

Battery 
Management 
System Error 
(LIBM Error) 

If there is an error to 
the setting value 
memorized in 
nonvolatile memory 

(1) Check that the charge/discharge is stopped. If the 

charge/discharge continues, take an action such as turning 
off the breaker to stop the charge/discharge. 

(2) Contact us.

 

 

Summary of Contents for LIM50EN-12S2-F2

Page 1: ...afely read this Instructional Manual before installing the batteries Read the Safety Precautions pages 3 5 before using the product Retain this Instruction Manual for future reference and keep it in a...

Page 2: ...7 2 Installation and Operation 2 1 Unpacking and Inspection 9 2 2 Installation and Wiring 10 2 3 Connector Input Output Summary Table 13 2 4 Charging and Discharging 14 2 5 Storage 15 2 6 Maintenance...

Page 3: ...rious injury is an injury such as loss of eyesight wound burn electric shock and bone fractures that may require hospitalization and long term health care Note 2 Minor or Moderate Injury is an injury...

Page 4: ...r Prohibited Do not expose to moisture and do not immerse in water When installing outdoor place module in enclosure which meets water proofing specification Prohibited General Do not short the batter...

Page 5: ...when transporting or carrying The batteries are heavy Do not stack the batteries in or out of their shipping boxes Do not leave the battery monitor board operating The battery can be over discharged...

Page 6: ...y monitor board monitors the module temperature and balances the battery voltage Lithium ion Battery Monitor LIBM II A device that receives battery module information sent by battery monitor board Bas...

Page 7: ...ative Battery Terminal with Terminal Protection Cover 4 Battery Monitor Board Built In 1 Positive Battery Terminal with Terminal Protection Cover 5 Communication Connector CN2 Communication Transmitte...

Page 8: ...s at the left 3 Terminal Protection Cover The cover protecting the positive and negative battery terminals Note that the exposed terminals are danger After wiring make sure to install terminal protect...

Page 9: ...ry module is heavy Be careful when carrying When handling do not drop tip over or stack the battery modules For carrying the battery module be sure to tightly hold the handles on the front side and th...

Page 10: ...e following items prior to setting up and installing the battery module Mount securely the battery module fixing parts at front and rear see p 7 to avoid any direct force to the battery terminals Moun...

Page 11: ...ckness of the cable connected to the battery terminal to 60 mm 2 or less and use a wire gauge appropriate to the conduction current The crimp terminal size is M8 In lieu of a cable a copper bar may be...

Page 12: ...amaged When tightening is difficult stop tightening and check if the nut is cross threaded check for the presence of foreign material on the threads Also check if the nut thread pitch is correct Then...

Page 13: ...module communication and CN2 is a transmitter of module communication Table 1 Connector Input Output and Pin Assignments Name Connector Model Name Application Pin Number Remark CN1 D1200D 6P 1 1903131...

Page 14: ...iate charger and read the instruction manual and specifications manual before use Precautions during Charging Discharging 1 Charge Discharge Control Control the battery charge discharge to the require...

Page 15: ...e Discharge When charging or discharging always monitor the batteries with the Lithium Ion Battery Management System LIBM II Failure to monitor the batteries could make the batteries unusable and coul...

Page 16: ...control power stop of this Lithium Ion Battery System LIBM II CAUTION The power source for the battery monitor board is the battery itself If the battery module remains connected to an operating batt...

Page 17: ...charging use the charger with constant current constant voltage CCCV function and Over Voltage Protection OVP function 2 Set the Over Voltage Protection OVP to 49 2 V 4 10 V battery 3 Set the constant...

Page 18: ...azards associated with lithium ion cells If removal of battery module is necessary for inspection avoid doing so when it is in the fully charged state We recommend discharging the module to its lowest...

Page 19: ...perature becomes within the battery s operating range If the module temperature remains high contact us 4 Battery Temp Down Error When any module temperature becomes below the setting value 1 Check th...

Page 20: ...Effective Value Cooling Method Self Cooling 1 Values inside parentheses are the dimension for the protruding handle 3 2 3 Cell Outline Item Description Positive Electrode Lithium Coated with transitio...

Page 21: ...egulations before disposing of a lithium ion battery For disposal of used battery be sure to contact us Contact Information as of December 2014 GS Yuasa International Ltd KYOTO HEAD Office 1 Inobanba...

Reviews: