background image

7

English (US)

5.2 Changing the terminal box position

If the pump is already installed in the system, 
the system must be drained or the isolation 
valves on both sides of the pump must be closed 
and the pressure released/relieved by removing 
the vent plug.

Only after the pressure has been relieved and 
the pump drained should you proceed with the 
next steps.

5.2.1 Rotating the terminal box

To change the position of the terminal box, 
follow these steps:

1. Remove the four (5 mm) allen-head screws 

holding the pump head onto the pump 
housing.

2. Carefully lift/slide the pump head out and 

away from the pump housing. Next rotate the 
pump head and locate the terminal box in the 
desired position. The terminal box can be 
rotated in steps of 90 °. Review fig. 

1

 an

fig.

2

 for possible/permissible positions. 

DO NOT locate the terminal box beneath the 
pump.

3. Make sure the O-ring is properly seated in 

the pump housing.

4. Replace the pump head onto the pump 

housing.

5. Diagonally tighten the 5 mm allen-head 

screws evenly. 
Torque to: 7 ft lbs. / 9.5 Nm.

6. Check to ensure the rotor turns freely. Do 

this by removing the vent plug in the middle 
of the pump nameplate. Insert a 
medium-size, flat-blade screwdriver into the 
slot at the exposed end of the shaft. Gently 
turn the shaft. If it does not turn easily, 
repeat steps 1 through 5 above. If the rotor 
spins freely, proceed to step 7. Do not put 
the vent plug back into the pump until the 
end of step 9.

7. The position of the nameplate can be 

changed by easing the outer edge of the 
plate at the cutout with a screwdriver. Turn 
the nameplate to the required position and 
push into place.

8. Follow electrical instructions in section 

5.3 Electrical connection

.

9. Refill the system, open the isolation valves 

and vent the system. Also allow air to vent 
out of the pump; once water flows out the 
vent hole, replace the vent plug removed in 
step 6. See additional instructions in section 

6.1 Vent the piping system

.

10. Figur

2

 shows acceptable terminal box 

positions along with recommended drip 
loops (dashed lines) in the electrical wiring 
harness based on entry point.

Fig. 2

Acceptable terminal box positions

Warning

Before starting any work on this 
circulator, be sure electrical supply 
has been switched off and it cannot 
be accidentally switched on.

Warning

Exercise caution when draining the 
system or removing the vent plug 
as the fluid in the system may be 
scalding hot and under pressure.

Caution

Use caution as the rotor assembly 
can fall out of the pump head or 
pump housing if the pump head is 
pulled too far away from the pump 
housing.

TM

04 563

6 360

9

Terminal box

position A

Terminal box

position B

Terminal box

position C

Summary of Contents for UPS 26-150

Page 1: ...NDFOS INSTRUCTIONS Grundfos UP XL Maintenance free circulators with insulating shell if equipped Installation and operating instructions 3191277 Conforms to UL STD 514C Certified to CSA STD C22 2 No 1...

Page 2: ...easurement 12 7 4 Insulation resistance lead to ground 13 7 5 Winding resistance line to line 13 7 6 Resistance tables 13 8 Replacing components 14 8 1 Removing the pump head 14 8 2 Fitting the pump h...

Page 3: ...ty the defective product must be returned to the distributor or dealer of Grundfos products from which it was purchased together with proof of purchase and installation date failure date and supportin...

Page 4: ...These pumps are intended for indoor use only If installed outdoors the pump must be protected by an appropriate well ventilated water tight enclosure to keep out moisture and dirt Minimum ambient tem...

Page 5: ...in solid particles fibers or mineral oils The pump is lubricated and cooled by the liquid being pumped Therefore the pumped liquid must always be allowed to circulate through the pump Extended periods...

Page 6: ...the pump housing indicate the direction of water flow The pump may be installed in vertical or horizontal piping but the motor shaft must always remain horizontal as shown in fig 1 Fig 1 Installation...

Page 7: ...the shaft Gently turn the shaft If it does not turn easily repeat steps 1 through 5 above If the rotor spins freely proceed to step 7 Do not put the vent plug back into the pump until the end of step...

Page 8: ...wer supply connections 115 V and 108 230 V with internal drip loop Warning Risk of electrical shock The electrical connection and protection should be carried out in accordance with the latest edition...

Page 9: ...n shells over the pump volute as illustrated in fig 6 If the shells do not mate flange bolts are installed in the wrong direction review step one and or switch mating shell location 4 Proper amount of...

Page 10: ...st be turned off before changing speeds The speed in the three positions appears in the following table also see fig 10 UP models Speed is fixed on Speed 3 High and cover does not have a switch cover...

Page 11: ...eaker and change speed switch into position c The pump has been cut out by the thermal overload switch due to high liquid temperature Check that the liquid temperature falls within the specified range...

Page 12: ...mp is operating 2 Set the ammeter to the proper scale 3 Place the tongs of the ammeter around the leg to be measured 4 Compare the results with the amp draw information on the motor nameplate 5 Repeat...

Page 13: ...eference touch the leads of the megohmmeter to the appropriate pair of connectors Check all pairs that are present and write down and label RA1 RS1 RS2 all readings In T box at L N UP will Speed 3 Hig...

Page 14: ...leads from the terminal box 5 Disconnect and remove the conduit from the terminal box 6 Loosen and remove the four 5 mm allen head screws which connect the pump head housing to the pump housing 7 Remo...

Page 15: ...o 7 ft lb 9 5 Nm 7 Check to make sure the rotor turns freely Do this by removing the vent plug in the middle of the pump nameplate Insert a medium size flat blade screwdriver into the slot at the expo...

Page 16: ...it from the stator pump head Installation 1 Carefully press the terminal box into the stator socket 2 Replace the two T15 Torx head screws and torque to 1 5 ft lbs 2 Nm 3 Replace the wiring refer to...

Page 17: ...pressure 145 psi 10 bar Max sound pressure level 30 dB A Water hardness 14 dH Open systems domestic potable hot water Fluid Ambient Min 36 F 2 C 33 F 1 C Max 149 F 65 C 100 F 38 C Caution In domestic...

Page 18: ...18...

Page 19: ...3500 www grundfos us GRUNDFOS Canada 2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www grundfos ca GRUNDFOS M xico Boulevard TLC No 15 Parque Industri...

Page 20: ...CM 1161312 www grundfos com The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copy...

Reviews: