7.4 Insulation resistance 

(lead-to-ground)

To check the insulation resistance 
(lead-to-ground) of the motor and leads, use a 
megohmmeter and follow these steps:

1. Turn the POWER OFF.

2. Disconnect all electrical leads to the motor.

3. Set the scale selector on the megohmmeter 

to R x 100K, touch its leads together, and 
adjust the indicator to zero.

4. Touch the leads of the megohmmeter 

individually to each of the motor leads and to 
ground (i.e. L to ground; N to ground, etc.).

Fig. 13

Insulation resistance measurement

Evaluation

The resistance values for new motors must 
exceed 1,000,000 ohms. If they do not, replace 
power head.

7.5 Winding resistance (line-to-line)

To check the winding resistance of the motor 
windings, use a megohmmeter and follow these 
steps.

1. Turn the POWER OFF.

2. Disconnect all electrical leads to the motor.

3. Set the scale selector on the megohmmeter 

to R x 1, touch its leads together and adjust 
the indicator to zero.

4. Using the charts in section 

7.6 Resistance 

tables

 for reference, touch the leads of the 

megohmmeter to the appropriate pair of 
connectors. Check all pairs that are present 
and write down and label (RA1, RS1, RS2) 
all readings.

– In T-box at L & N: UP will = Speed 3/High

– In T-box at L & N: UPS value depends on 

the selected speed (Speed 1, 2, or 3) 

– For both UP and UPS: with the terminal 

box removed, check all combinations RA, 
S1, S2.

5. Compare your readings to the matching 

model, phase and voltage listed in the charts 
in section 

7.6 Resistance tables

.

Evaluation

The resistance values must fall within the 
tolerances listed in section 

7.6 Resistance 

tables

. If they do not, replace the power head.

7.6 Resistance tables

Checking connections in the terminal box at the 
power connections L and N; see fig. 

14

 for 115 V 

and 208-230 V.

* T can only be checked with the terminal box 

removed; if the thermiks is open the pump will 
not run.

Fig. 14

Power connections L and N

TM

04 56

38 360

9

Connection

Ohm value 

range

Nominal

115 V

L to N 

(Speed 3)

=

6.9 - 8.01

7.55

L to N 

(Speed 2)

=

9.7 - 11.38

10.54

L to N 

(Speed 1)

= 12.97 - 15.23

14.10

Connection

Ohm value 

range

Nominal

208 V 

230 V

L to N 

(Speed 3)

= 34.63 - 40.66

37.65

L to N 

(Speed 2)

= 41.57 - 48.81

45.19

L to N 

(Speed 1)

= 56.67 - 66.53

61.60

TM

04

 56

33

 36

09

L N

Summary of Contents for UPS 26-150

Page 1: ...NDFOS INSTRUCTIONS Grundfos UP XL Maintenance free circulators with insulating shell if equipped Installation and operating instructions 3191277 Conforms to UL STD 514C Certified to CSA STD C22 2 No 1...

Page 2: ...easurement 12 7 4 Insulation resistance lead to ground 13 7 5 Winding resistance line to line 13 7 6 Resistance tables 13 8 Replacing components 14 8 1 Removing the pump head 14 8 2 Fitting the pump h...

Page 3: ...ty the defective product must be returned to the distributor or dealer of Grundfos products from which it was purchased together with proof of purchase and installation date failure date and supportin...

Page 4: ...These pumps are intended for indoor use only If installed outdoors the pump must be protected by an appropriate well ventilated water tight enclosure to keep out moisture and dirt Minimum ambient tem...

Page 5: ...in solid particles fibers or mineral oils The pump is lubricated and cooled by the liquid being pumped Therefore the pumped liquid must always be allowed to circulate through the pump Extended periods...

Page 6: ...the pump housing indicate the direction of water flow The pump may be installed in vertical or horizontal piping but the motor shaft must always remain horizontal as shown in fig 1 Fig 1 Installation...

Page 7: ...the shaft Gently turn the shaft If it does not turn easily repeat steps 1 through 5 above If the rotor spins freely proceed to step 7 Do not put the vent plug back into the pump until the end of step...

Page 8: ...wer supply connections 115 V and 108 230 V with internal drip loop Warning Risk of electrical shock The electrical connection and protection should be carried out in accordance with the latest edition...

Page 9: ...n shells over the pump volute as illustrated in fig 6 If the shells do not mate flange bolts are installed in the wrong direction review step one and or switch mating shell location 4 Proper amount of...

Page 10: ...st be turned off before changing speeds The speed in the three positions appears in the following table also see fig 10 UP models Speed is fixed on Speed 3 High and cover does not have a switch cover...

Page 11: ...eaker and change speed switch into position c The pump has been cut out by the thermal overload switch due to high liquid temperature Check that the liquid temperature falls within the specified range...

Page 12: ...mp is operating 2 Set the ammeter to the proper scale 3 Place the tongs of the ammeter around the leg to be measured 4 Compare the results with the amp draw information on the motor nameplate 5 Repeat...

Page 13: ...eference touch the leads of the megohmmeter to the appropriate pair of connectors Check all pairs that are present and write down and label RA1 RS1 RS2 all readings In T box at L N UP will Speed 3 Hig...

Page 14: ...leads from the terminal box 5 Disconnect and remove the conduit from the terminal box 6 Loosen and remove the four 5 mm allen head screws which connect the pump head housing to the pump housing 7 Remo...

Page 15: ...o 7 ft lb 9 5 Nm 7 Check to make sure the rotor turns freely Do this by removing the vent plug in the middle of the pump nameplate Insert a medium size flat blade screwdriver into the slot at the expo...

Page 16: ...it from the stator pump head Installation 1 Carefully press the terminal box into the stator socket 2 Replace the two T15 Torx head screws and torque to 1 5 ft lbs 2 Nm 3 Replace the wiring refer to...

Page 17: ...pressure 145 psi 10 bar Max sound pressure level 30 dB A Water hardness 14 dH Open systems domestic potable hot water Fluid Ambient Min 36 F 2 C 33 F 1 C Max 149 F 65 C 100 F 38 C Caution In domestic...

Page 18: ...18...

Page 19: ...3500 www grundfos us GRUNDFOS Canada 2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www grundfos ca GRUNDFOS M xico Boulevard TLC No 15 Parque Industri...

Page 20: ...CM 1161312 www grundfos com The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copy...

Reviews: