6.1.2 Insulation of the pump in systems with condensate formation

If the pump is insulated, the terminal box and in particular the 
heat deflection plate must not be covered in order to guarantee 
adequate cooling by the surrounding air. If the pump is installed 
in a casing or if thermal insulation jackets are mounted on the 
pump, the air temperature inside must be estimated. If the 

temperature of the ambient air is predicted to be permanently 
higher than 55 °C, please contact your after-sales service.
Diffusion-tight insulation shells for cold water applications must 
not be mounted on the pump head. The drain holes arranged in 
the stator casing must remain free at all times.

6.2 Electrical connection

ATTENTION!

WARNING! Risk of electric shock

The electrical connection must be made by an electrician approved by the 
local utility company in accordance with the locally valid regulations (e.g. 
VDE regulations).

ATTENTION!

Warning! Risk of electric shock!

If the cable is separated from the pump by force, there is a risk of 
personal injury:

During generator operation of the pump (driven rotor), a dangerous 
voltage can occur on the module contacts.

Never insert sharp objects (nails, screwdriver, wire) in the contact on the 
terminal box.

The free end must be connected in the system's switch box (Fig. 
3.1 in appendix on page  IV).

Black/brown flexible wire: 

L1 (phase)

Blue flexible wire: 

N (neutral conductor)

Green-yellow flexible wire: 

  (protective earth)

The mains connection cable must be routed into the 
system's switch box using a strain relief. The strain relief 
device and impermeability against dripping water/
condensate must be ensured. If necessary, the cable must 
be furnished with a water drip-off loop to prevent water from 
entering the switch box.

The following minimum requirements must be fulfilled in the 
event of a switch-off via an external/on-site circuit relay:

Nominal current > 10 A

Nominal voltage 250 V AC

Leakage current per pump I

eff

  



3.5 mA (according to EN 

60335)

The pump can be protected using a fault current circuit 
breaker.

Labelling FI:  

   or  

  

Current type and voltage of the mains connection must be in 
accordance with the specifications on the type plate,

Mains connection voltage: 1 ~ 230 V, 50/60 Hz, DIN IEC 
60038.

Line side fuse protection: See type plate,

The pump/system must be earthed according to regulations.

ATTENTION!

CAUTION! Risk of damage to the pump

All poles of the pump must be disconnected from the mains within the 
switch box during insulation tests with a high-voltage generator.

The strain relief of the cable and impermeability against 
dripping water/condensate must be ensured. If necessary, 
the cable must be furnished with a drip-off loop in order to 
prevent water from entering the switch box. The control 
cable covers the following control functions:

Control via analogue signal PWM (3-core cable) (Fig. 3.1 in 
appendix on page  IV
):

Flexible wire no. 1 (brown): Nominal value for pump 
(PWM signal)

Flexible wire no. 2 (blue): Signal ref. (GND)

Flexible wire no. 3 (black): Feedback from pump (PWM 
signal)

Connection diagram (see Fig. 3.2 in appendix on page  IV)

PWM signal only in conjunction with pCO5+ on analogue 
outputs N1-J4/Y3 and Y4

Pump runs with max. speed if the analogue signal is not 
connected to the heat pump manager.

7 Maintenance

Maintenance and repair work must only be carried out by 
qualified specialists!

ATTENTION!

WARNING! Risk of electric shock

Risks resulting from electrical energy must be ruled out

Disconnect the system/pump(s) from the power source and secure it/
them against unauthorized restarting before carrying out any 
maintenance or repair work.

ATTENTION!

WARNING! Risk of scalding

With high medium temperatures and system pressures, let the pump cool 
down and depressurise the system.

8 Terminal box position

Summary of Contents for UPH 70-25P

Page 1: ...6 20 FD 9304 UPH 70 25P UPH 80 25P Montage und Gebrauchsanweisung Installation and Operating Instructions Instructions d installation et d utilisation Elektronische Umw lzpumpe Electronically circulat...

Page 2: ......

Page 3: ...ssige Betriebsweisen DE 1 3 Tansport und Zwischenlagerung DE 1 4 Bestimmungsgem e Verwendung DE 2 5 Angaben ber des Erzeugnis DE 2 5 1 Technische Daten DE 2 5 2 Lieferumfang DE 3 6 Installation und el...

Page 4: ...zur Folge haben 2 3 Sicherheitshinweise f r den Betreiber Die bestehenden Vorschriften zur Unfallverh tung sind zu be achten Gef hrdungen durch elektrische Energie sind auszuschlie en Weisungen lokale...

Page 5: ...nnung 1 230 V 10 15 1 230 V 10 15 Nennstrom max 0 52 A max 0 71 A Frequenz 50 60 Hz 50 60 Hz Isolationsklasse H H Schutzart IP44 IP X4D Aufnahmeleistung P1 max 70 W max 87 W Nennweiten 25 25 Anschluss...

Page 6: ...f hren Die Rohre sind so zu befestigen dass die Pumpe nicht das Gewicht der Rohre tr gt Die Flie richtung des Mediums muss mit dem Richtungsdreieck auf dem Pumpengeh use bereinstimmen Nur Einbaulagen...

Page 7: ...enenfalls ist das Kabel mit einer Tropfwasser Ablaufschlaufe zu versehen um zu verhindern dass Wasser in den Schaltkasten gelangt Erfolgt eine Abschaltung mittels externem bauseitigem Netzrelais sind...

Page 8: ...DE 5 452115 66 20 FD 9304 www dimplex de Deutsch UPH 70 25P UPH 80 25P...

Page 9: ...odes EN 2 3 Transport and intermediate storage EN 2 4 Intended use EN 3 5 Information on the product EN 3 5 1 Technical data EN 3 5 2 Scope of supply EN 4 6 Installation and electrical connection EN 4...

Page 10: ...3 Safety information for the operator Observe the valid accident prevention regulations It must be ensured that there are no risks resulting from electrical energy Instructions resulting from local or...

Page 11: ...nt max 0 52 A max 0 71 A Frequency 50 60 Hz 50 60 Hz Insulation class H H Degree of protection IP44 IP X4D Power consumption P1 Max 70 W Max 87 W Nominal widths 25 25 Connecting flange Rp 1 Rp 1 Permi...

Page 12: ...tem when the pump is replaced Carry out tension free installation The pipes must be mounted such that the pump does not bear the weight of the pipes The flow direction of the medium must correspond to...

Page 13: ...witch box The following minimum requirements must be fulfilled in the event of a switch off via an external on site circuit relay Nominal current 10 A Nominal voltage 250 V AC Leakage current per pump...

Page 14: ...EN 6 452115 66 20 FD 9304 www dimplex de UPH 70 25P UPH 80 25P English...

Page 15: ...nterdits FR 2 3 Transport et stockage temporaire FR 3 4 Utilisation conforme FR 3 5 Donn es concernant le produit FR 4 5 1 Caract ristiques techniques FR 4 5 2 Fournitures FR 4 6 Installation et branc...

Page 16: ...spect des consignes de s curit Le non respect des consignes de s curit peut entra ner une mise en danger des personnes et des risques de dommages de la pompe de l installation 2 3 Consignes de s curit...

Page 17: ...es enfants doivent tre surveill s pour viter qu ils ne jouent avec l appareil Ces pompes haute performance de la s rie UPM servent faire circuler des liquides pas d huiles ou de liquides ol agineux pa...

Page 18: ...1466 m langes d eau et de glycol rapport max du m lange 1 1 en cas d addition de glycol les donn es d alimentation de la pompe doivent tre corrig es selon la viscosit sup rieure en fonction du rappor...

Page 19: ...de mani re ce qu aucune goutte d eau ne puisse tomber sur le moteur de la pompe ou sur le coffret bornes 6 1 1 Modification de la position du coffret bornes Si le coffret bornes doit tre plac d une au...

Page 20: ...n du branchement secteur doivent correspondre aux donn es de la plaque signal tique Tension de raccordement secteur 1 230 V 50 60 Hz DIN CEI 60038 Fusible r seau voir plaque signal tique Mettre la pom...

Page 21: ...Diagrammes A III 2 1 Kennlinie Characteristic curve Courbe caract ristique UPH 70 25P A III 2 2 Kennlinie Characteristic curve Courbe caract ristique UPH 80 25P A III 3 Stromlaufpl ne Circuit diagrams...

Page 22: ...bilder Dimension Drawings Sch mas cot s 1 1 Ma bild Dimension Drawing Sch ma cot UPH 70 25P 1 2 Ma bild Dimension Drawing Sch ma cot UPH 80 25P OHPPHQNDVWHQVWHOOXQJHQ 7HUPLQDO ER SRVLWLRQ 3RVLWLRQ GX...

Page 23: ...Annexes UPH 70 25P UPH 80 25P 2 Diagramme Diagrams Diagrammes 2 1 Kennlinie Characteristic curve Courbe caract ristique UPH 70 25P 2 2 Kennlinie Characteristic curve Courbe caract ristique UPH 80 25P...

Page 24: ...s UPH 70 25P UPH 80 25P 3 Stromlaufpl ne Circuit diagrams Sch mas lectriques 3 1 Aderbelegung Pin configuration Brin occupation Abb Fig Fig 3 1 Abb Fig Fig 3 2 3 2 Anschlussschema Connection diagram S...

Page 25: ...mlaufpl nen Legend for Circuit Diagrams L gendes des sch mas lectriques Jx Stecker von Nx Plug from Nx Connecteur de Nx K5 Sch tz Prim rpumpe Contactor primary pump contacteur pompe primaire KMx Koppe...

Page 26: ...A VI 452115 66 20 FD 9304 www dimplex de Anhang Appendix Annexes UPH 70 25P UPH 80 25P...

Page 27: ...www dimplex de 452115 66 20 FD 9304 A VII Anhang Appendix Annexes UPH 70 25P UPH 80 25P...

Page 28: ...ales service addresses please refer to the Installation and Operating Instructions for Heat Pumps Pour les conditions de garantie et les adresses SAV se r f rer aux instructions de montage et d utilis...

Reviews: