The motors are wound for direct-on-line starting or star-delta 
starting and the starting current is between 4 and 6 times the full 
load current of the motor. 

The run-up time of the pump is only about 0.1 second. Direct-on-
line starting is therefore normally approved by the electricity sup-
ply authorities.

4.1.1 Frequency converter operation

GRUNDFOS motors: 

Three-phase GRUNDFOS motors can be connected to a fre-
quency converter. 

Note: If a GRUNDFOS MS motor with temperature transmitter is 
connected to a frequency converter, a fuse incorporated in the 
transmitter will melt and the transmitter will be inactive. The trans-
mitter cannot be reactivated. This means that the motor will oper-
ate like a motor without a temperature transmitter.
If a temperature transmitter is required, a Pt100 sensor for fitting 
to the submersible motor can be ordered from GRUNDFOS.

During frequency converter operation, it is not advisable to run 
the motor at a frequency higher than the nominal frequency (50 or 
60 Hz). In connection with pump operation, it is important never to 
reduce the frequency (and consequently the speed) to such a 
level that the necessary flow of cooling liquid past the motor is no 
longer ensured. 

To avoid damage to the pump part, it must be ensured that the 
motor stops when the pump flow falls below 0.1 x nominal flow. 

Depending on the frequency converter type, it may expose the 
motor to detrimental voltage peaks.

The above disturbance can be abated by installing an RC filter 
between the frequency converter and the motor. 

Possible increased acoustic noise from the motor can be abated 
by installing an LC filter which will also eliminate voltage peaks 
from the frequency converter. 

For further details, please contact your frequency converter sup-
plier or GRUNDFOS. 

4.2 Motor protection 

GRUNDFOS MS motors are available with or without a built-in 
temperature transmitter. 

Motors with a built-in and operational temperature transmitter 
must be protected by means of: 

a motor starter with thermal relay or 

an MTP 75 and a motor starter with thermal relay or 

a CU 3 and contactor(s). 

Motors without or with a non-operational temperature transmit-
ter must be protected by means of: 

a motor starter with thermal relay or 

a CU 3 and contactor(s). 

GRUNDFOS MMS motors have no built-in temperature transmit-
ter. A Pt100 sensor is available as an accessory.

Motors with a Pt100 sensor must be protected by means of:

a motor starter with thermal relay or 

a CU 3 and contactor(s). 

Motors without a Pt100 sensor must be protected by means of:

a motor starter with thermal relay or 

a CU 3 and contactor(s). 

4.2.1 Required motor starter settings 

For cold motors, the tripping time for the motor starter must be 
less than 10 seconds at 5 times the rated maximum current of the 
motor. 

Note: If this requirement is not met, the motor warranty will be 
invalidated. 

In order to ensure the optimum protection of the submersible 
motor, the starter overload unit should be set in accordance with 
the following guidelines: 

1. Set the starter overload to the rated maximum current of the 

motor. 

2. Start the pump and let it run for half an hour at normal perform-

ance. 

3. Slowly grade down the scale indicator until the motor trip point 

is reached. 

4. Increase the overload setting by 5%. 

The highest permissible setting is the rated maximum current of 
the motor. 

For motors wound for star-delta starting, the starter overload unit 
should be set as above, but the maximum setting should be as 
follows: 

Starter overload setting = Rated maximum current x 0.58. 

The highest permissible start-up time for star-delta starting or 
autotransformer starting is 2 seconds. 

4.3 Lightning protection 

The installation can be fitted with a special overvoltage protective 
device to protect the motor from voltage surges in the electricity 
supply lines when lightning strikes somewhere in the area, see 
fig. 7. 

Fig. 7

The overvoltage protective device will not, however, protect the 
motor against a direct stroke of lightning. 

The overvoltage protective device should be connected to the 
installation as close as possible to the motor and always in 
accordance with local regulations. 

Ask GRUNDFOS for lightning protective devices. 

4.4 Cable sizing 

Make sure that the submersible drop cable can withstand perma-
nent submersion in the actual liquid and at the actual tempera-
ture. 

GRUNDFOS can supply submersible drop cables for a wide 
range of installations. 

TM

0

0

 7

100

 0

6

96

0,47 µF

 1

 2

 3

 4

1. Black

2. Blue

3. Yellow/green

4. Brown

0.47 

F

TM

00

1 4

700

 0

799

82 50 45

f

PE

L3

L2

L1

Summary of Contents for SP-G

Page 1: ...SP G GRUNDFOS INSTRUCTIONS Installation and operating instructions ...

Page 2: ... 60335 1 2002 e EN 60335 2 41 2003 excepto nos pontos 25 1 e 25 8 Bomba com ponta de veio livre A Grundfos declara sob sua única responsabilidade que os produtos SP G aos quais diz respeito esta declaração estão em conformidade com as seguintes Directivas do Conselho sobre a aproximação das legislações dos Estados Membros da CE Directiva Máquinas 2006 42 CE Norma utilizada EN 809 2009 Antes de col...

Page 3: ...24 Istruzioni di installazione e funzionamento 34 Instrucciones de instalación y funcionamiento 43 Instruções de instalação e funcionamento 52 Οδηγίες εγκατάστασης και λειτουργίας 62 Installatie en bedieningsinstructies 72 Monterings och driftsinstruktion 82 Asennus ja käyttöohjeet 91 Monterings og driftsinstruktion 100 ...

Page 4: ...e a month If a motor has been stored for more than one year before installa tion the rotating parts of the motor must be dismantled and checked before use The pump should not be exposed to direct sunlight If the pump has been unpacked it should be stored horizontally adequately supported or vertically to prevent misalignment of the pump Make sure that the pump cannot roll or fall over During stora...

Page 5: ...ith the filling syringe fig 3 until the liquid runs back out of the filling hole 4 Replace the screw in the filling hole and tighten securely before changing the position of the pump Torque 3 0 Nm The submersible pump is now ready for installation Fig 3 3 1 3 Refilling GRUNDFOS submersible motors MMS 6000 MMS 8000 MMS 10000 and MMS 12000 To refill the motor proceed as follows 1 Position the submer...

Page 6: ...tor makes See motor specifications 4 Electrical connection 4 1 General The electrical connection should be carried out by an authorized electrician in accordance with local regulations The supply voltage rated maximum current and cos appear from the loose data plate that must be fitted close to the installa tion site The required voltage quality for GRUNDFOS MS submersible motors measured at the m...

Page 7: ...ter must be protected by means of a motor starter with thermal relay or a CU 3 and contactor s GRUNDFOS MMS motors have no built in temperature transmit ter A Pt100 sensor is available as an accessory Motors with a Pt100 sensor must be protected by means of a motor starter with thermal relay or a CU 3 and contactor s Motors without a Pt100 sensor must be protected by means of a motor starter with ...

Page 8: ... Specific resistance 0 02 mm m q Cross section of submersible drop cable mm sin 0 436 Xl Inductive resistance 0 078 x 10 3 m 4 5 Connection of motor Three phase submersible motors must be protected see section 4 2 Motor protection For electrical connection by means of the CU 3 see the separate installation and operating instructions for this unit When a conventional motor starter is being used the...

Page 9: ...ightened diagonally to the torques stated in the following table Note Make sure that the pump chambers are aligned when assembly has been completed 5 2 Fitting of submersible drop cable Before fitting the submersible drop cable to the motor make sure that the cable socket is clean and dry To facilitate the fitting of the cable lubricate the rubber parts of the cable plug with non conducting silico...

Page 10: ...osed off to approx 1 3 of its maximum volume of water Check the direction of rotation as described in section 4 5 1 Checking of direction of rotation If there are impurities in the water the valve should be opened gradually as the water becomes clearer The pump should not be stopped until the water is completely clean as otherwise the pump parts and the non return valve may choke up As the valve i...

Page 11: ...d at a GRUNDFOS service centre If GRUNDFOS is requested to service the pump GRUNDFOS must be contacted with details about the pumped liquid etc before the pump is returned for service Otherwise GRUNDFOS can refuse to accept the pump for service Possible costs of returning the pump are paid by the customer If a pump has been used for a liquid which is injurious to health or toxic the pump will be c...

Page 12: ... rotation c The valves in the discharge pipe are partly closed blocked Check and clean replace the valves if necessary d The discharge pipe is partly choked by impurities ochre Clean replace the discharge pipe e The non return valve of the pump is partly blocked Pull out the pump and check replace the valve f The pump and the riser pipe are partly choked by impurities ochre Pull out the pump Check...

Page 13: ... the full load current there are the following possible faults The contacts of the motor starter burnt Replace the con tacts Poor connection in leads possibly in the cable joint See item 3 Too high or too low supply voltage See item 1 The motor windings are short circuited or partly disjointed See item 3 Damaged pump is causing the motor to be overloaded Pull out the pump for overhaul The resistan...

Page 14: ... Bride Flangia Brida Flange Φλάντζα Flens Fläns Laippa Flange Motor Motor Moteur Motore Motor Motor Κινητήρας Motor Motor Moottori Motor Direct On Line Starting Direktanlauf Démarrage direct Avviamento diretto Arranque directo Arranque directo Απευθείας Εκκίνηση Directe aanloop Direktstart Suorakäynnistys Direkte start Star Delta Starting Stern Dreieck Anlauf Démarrage étoile triangle Avviamento Y...

Page 15: ... 3 x 400 V I 40 A L 140 m U 2 Lx L U 140 2 70 m q 25 mm 2 TM00 1346 5092 I 40 A U 2 U 3 x 400 V L 140 m Example U 3 x 380 V I 10 A L 120 m U 2 Lx L U 120 2 60 m q 6 mm 2 TM00 1345 5092 I 10 A U 2 U 3 x 380 V L 120 m ...

Page 16: ...3 x 220 V I 5 A L 105 m U 3 Lx L U 105 3 35 m q 2 5 mm 2 TM00 1348 5092 I 5 A U 3 U 3 x 220 V L 105 m Example U 3 x 415 V I 100 A L 150 m U 3 Lx L U 150 3 50 m q 50 mm 2 TM00 1347 5092 I 100 A U 3 U 3 x 415 V L 150 m ...

Page 17: ...112 ...

Page 18: ...113 ...

Page 19: ...114 ...

Page 20: ...ps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tālr 371 714 9640 7 149 641 Fakss 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilnius Tel 370 52 395 430 Fax 370 52 395 431 Malaysia GRUNDFOS Pumps Sdn Bhd 7 ...

Page 21: ...www grundfos com Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 96432078 0711 Repl 96432078 0506 ECM 1078259 ...

Reviews: